Plan Review Details - Permit 09110339
Plan Review Stops For Permit 09110339
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-02-25 Cont ID  
Sent By dpalmer Date 2010-02-25 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2010-02-25 Time 14:32 Sent To  
Notes
2010-02-25 14:32:39OK PER JW. ONLY NEEDED TO VERIFY APPLICATION BY
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2010-02-23 Cont ID  
Sent By jwitmer Date 2010-02-23 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2010-02-23 Time 15:52 Sent To  
Notes
2010-02-23 15:56:39BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 11/ 2010
 3RD REVIEW
 ACTION: DENIED
 DESIGN CRITERIA FOR SECOND FLOOR:
 R-3 WITH 40 LB LIVE LOAD/ 10 LB DEAD LOAD FOR FLOOR
 SYSTEM.
  
 1-12) COMPLIED.
  
 13) PROVISO: SEMI-COMPLIED.SHEET A3.1 ALSO INDICATES TO
 HAVE A AIR COMPRESSOR LOCATED WEST OF THE 2 STORY AREA,
 THIS COMPRESSOR WOULD BE LOCATED ON THE FIRST FLOOR
 ROOF REQUIRING A A/C STAND. PRODUCT APPROVALS WERE
 SUBMITTED. THE UPDATED PLANS INDICATE STRAPPING OVER
 THE COMPRESSOR UNIT. THIS IS NOT AN APPROVED METHOD OF
 COMPLYING WITH 301.12 FBC-MECHANICAL/ 2007.
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND
 THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 301.12 FBC MECHANICAL/ 2007
  
 14) COMPLIED.
  
 15) PLANS APPEAR TO BE CODE COMLIANT, MUST BE LEFT IN
 FAILED UNTIL CONTRACTOR LICENSURE IS VERIFIED.
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-02-11 Cont ID  
Sent By jwitmer Date 2010-02-11 Time 11:07 Rev Time 0.00
Received By jwitmer Date 2010-02-11 Time 11:07 Sent To  
Notes
2010-02-11 11:08:49BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 11/ 2010
 3RD REVIEW
 ACTION: DENIED
 DESIGN CRITERIA FOR SECOND FLOOR:
 R-3 WITH 40 LB LIVE LOAD/ 10 LB DEAD LOAD FOR FLOOR
 SYSTEM.
  
 1) COMPLIED.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK WITHIN THE PLANS. THE PERMIT APPLICATION AND THE
 VALUE OF $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF
 WORK ON THE PERMIT APPLICATION AND THE VALUE OF THE
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3- 12) COMPLIED.
  
 13) PROVISO: SEMI-COMPLIED.SHEET A3.1 ALSO INDICATES TO
 HAVE A AIR COMPRESSOR LOCATED WEST OF THE 2 STORY AREA,
 THIS COMPRESSOR WOULD BE LOCATED ON THE FIRST FLOOR
 ROOF REQUIRING A A/C STAND. PRODUCT APPROVALS WERE
 SUBMITTED. THE UPDATED PLANS INDICATE STRAPPING OVER
 THE COMPRESSOR UNIT. THIS IS NOT AN APPROVED METHOD OF
 COMPLYING WITH 301.12 FBC-MECHANICAL/ 2007.
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND
 THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 301.13 FBC MECHANICAL./ 2004
 301.12 FBC MECHANICAL/ 2007
  
 14) COMPLIED.
  
 15) ONCE PLANS ARE OK TO ISSUE PLANS WILL NEED TO BE
 LEFT IN FAILED STATIS UNTIL CONTRACTOR LICENSURE CAN BE
 VERIFIED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-01-25 Cont ID  
Sent By jwitmer Date 2010-01-25 Time 11:00 Rev Time 1.00
Received By jwitmer Date 2010-01-25 Time 10:00 Sent To  
Notes
2010-01-25 11:06:58BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JAN. 25/ 2010
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK WITHIN THE PLANS. THE PERMIT APPLICATION AND THE
 VALUE OF $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF
 WORK ON THE PERMIT APPLICATION AND THE VALUE OF THE
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 2ND REQUEST, THE PERMIT APPLICATION AND SHEET 2.1
 INDICATES THE REPAIR OR REPLACEMENT OF 2X10 FLOOR
 JOIST, PLEASE PROVIDE SPECIES, GRADE OF WOOD, THE LIVE
 AND DEAD LOADS TO BE ASSUMED. TABLE 2308.8(1). PROVIDE
 ALLOWABLE DEFLECTION OF THE STRUCTURAL MEMBERS.
  
 4-8) COMPLIED.
  
 9) THE BATH EGRESS WINDOW WILL BE CONSIDERED A
 HAZARDOUS LOCATION. R308.4(5) & (10)PLEASE PROVIDE THE
 WINDOW SILL HEIGHT ABOVE THE TUB OR SHOWER FLOOR. BOTH
 WINDOWS ON THE NORTH END OF THE BUILDING ARE LOCATED
 DIRECTLY ABOVE THE ONLY MEANS OF EGRESS ( STAIRWAY)
 REQUIRING A 1HR SEPERATION 1023.6.
  
 10) 2ND REQUEST, 1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 / FL ADMINISTRATIVE RULE 9B-72,
 COMPONENTS & CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 10A) OPERABLE WINDOWS
 10B) MULLIONS PLANS ARE NOT CLEAR AS IF THERE IS A
 FRAMING MEMBER BETWEEN WINDOWS?
 10C) EGRESS DOOR
 10D) STORM SHUTTERS OR PANELS
 10E) PRE-MANUFACTURED A/C STAND. QUESTION # 13.
 10F) ROOFING ASSEMBLIES, IF WORK IS TO BE ACCOMPLISHED
 ON THE ROOF
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12)COMPLIED.
  
 13) SHEET A3.1 ALSO INDICATES TO HAVE A AIR COMPRESSOR
 LOCATED WEST OF THE 2 STORY AREA, THIS COMPRESSOR WOULD
 BE LOCATED ON THE FIRST FLOOR ROOF REQUIRING A A/C
 STAND. PRE-MANUFACTURED A/C STANDS WILL REQUIRE PRODUCT
 APPROVALS, FL ADMINISTRATIVE RULE 9B-72 (31)(G).
  
 14) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) ONCE PLANS ARE OK TO ISSUE PLANS WILL NEED TO BE
 LEFT IN FAILED STATIS UNTIL CONTRACTOR LICENSURE CAN BE
 VERIFIED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-18 Cont ID  
Sent By jwitmer Date 2009-11-18 Time 01:58 Rev Time 3.30
Received By jwitmer Date 2009-11-18 Time 12:30 Sent To  
Notes
2009-11-18 16:19:47BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 NOV.11/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT PROVIDE WHAT TYPE OF OCCUPANCY IS
 BUILDING IS DECLARING. IT APPEARS TO BE A MIXED USE
 BUILDING AS TO THE DETAIL 6/ 2.1PLEASE DECLARE THE TYPE
 OF OCCUPANCY IS LOCATED ON THE FIRST FLOOR AND SECOND
 FLOOR. THE PROPERTY APPRAISERS LIST THE FIRST FLOOR AS
 A MEDICAL OFFICE AND UNFINISHED OFFICE UPSTAIRS. IS
 THIS A CHANGE OF USE?
 1A) WILL THE UPSTAIRS UNIT BE A DIFFERENT TENANT THAN
 THE FIRST FLOOR, FBC 708.1 WILL REQUIRE A ONE HR
 SEPERATION BETWEEN TENANTSOF THE FIRST FLOOR AND SECOND
 FLOOR TENANT.
  
 1B) IS THE BUILDING FIRE SPRINKLERED? FOR THE PURPOSES
 OF THIS REVIEW WE WILL ASUME NON-SPRIKLERED!
  
 1C) THERE WOULD ALSO BE A OCCUPANCY SEPERATION BETWEEN
 THE FIRST FLOOR OCCUPANCY AND THE SECOND FLOOR. PLEASE
 REVIEW TABLE 508.3 FOR THE REQUIRED HOURLY RATING
 BETWEEN OCCUPANCIES. FOR EXAMPLE IF THE UPSTAIRS IS A
 R3 OCCUPANCY AND THE FIRST FLOOR BEING A BUSINESS
 OCCUPANCY THEN A TWO HOUR FLOOR/CEILING ASSEMBLY WOULD
 BE REQUIRED FOR A NON-SPRINKLERED BUILDING.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK IN THE PERMIT APPLICATION AND THE VALUE OF
 $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF WORK ON
 THE PERMIT APPLICATION AND THE VALUE OF THE PERMIT .
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE PERMIT APPLICATION AND SHEET 2.1 INDICATES THE
 REPAIR OR REPLACEMENT OF 2X10 FLOOR JOIST, PLEASE
 PROVIDE SPECIES, GRADE OF WOOD, SPACING , SPANS AND THE
 LIVE AND DEAD LOADS TO BE ASSUMED. TABLE 2308.8(1).
 PROVIDE ALLOWABLE DEFLECTION OF THE STRUCTURAL MEMBERS.
  
 4) SHEET 2.1 DOE NOT INDICATE HOW THE EXISTING AND
 REPLACED FLOOR JOIST ARE GOING TO BE ANCHORED AND OR
 SUPPORTED LATERALLY, SECTION 2308.2.
  
 5) SHEET 2.1 INDICATES A NEW 3X8 GLU-LAM BEAM AND NEW
 STEEL COLUMN BUT NO MENTION OF HOW THE GLU-LAM BEAM
 WILL BE SUPPORTED AT BOTH ENDS?
  
 6) WILL THE FLOOR JOIST REQUIRE BRIDGING OR LATERAL
 SUPPORT? SECTION 2308.8.5.
  
 7) SHEET 2.1 THE NEW 4X4 STEEL COLUMN PROVIDES THE
 CONNECTION FOR THE UPPER BRACKET BUT IS MISSING THE
 BOTTOM ANCHOR TYPE AND LENGTH? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED,
  
 8) FOR THE UPSTAIRS OCCUPANCY FOR THE PURPOSES OF THIS
 PLANS REVIEW IT WILL BE ASSUMED TO BE A R3 OCCUPANCY.
 THE PLANS INDICATE THE MAIN ENTRY/ EXIT DOOR TO BE A
 2'-8" DOORWAY PLEASE REVIEW R311.4.1-2. REQUIRING A 36'
 WIDE DOOR.
  
 9) THE BATH EGRESS WINDOW WILL BE CONSIDERED A
 HAZARDOUS LOCATION. R308.4(5) & (10).
  
 10) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 / FL ADMINISTRATIVE RULE 9B-72,
 COMPONENTS & CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 10A) OPERABLE WINDOWS
 10B) MULLIONS PLANS ARE NOT CLEAR AS IF THERE IS A
 FRAMING MEMBER BETWEEN WINDOWS?
 10C) EGRESS DOOR
 10D) STORM SHUTTERS OR PANELS
 10E) PRE-MANUFACTURED A/C STAND.
 10F) ROOFING ASSEMBLIES, IF WORK IS TO BE ACCOMPLISHED
 ON THE ROOF
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 FINISHED CEILING HEIGHTS, THE BATHROOM APPEARS TO HAVE
 A A/C AIR HANDLIER OR COIL UNIT, IS THIS UNIT ABOVE THE
 CEILING, OR LOCATED WITHIN A DRYWALLED AREA ABOVE THE
 RESTROOM CEILING. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 13) SHEET A3.1 ALSO INDICATES TO HAVE A AIR COMPRESSOR
 LOCATED WEST OF THE 2 STORY AREA, THIS COMPRESSOR WOULD
 BE LOCATED ON THE FIRST FLOOR ROOF REQUIRING A A/C
 STAND. PRE-MANUFACTURED A/C STANDS WILL REQUIRE PRODUCT
 APPROVALS, FL ADMINISTRATIVE RULE 9B-72 (31)(G).
  
 14) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 A SAMPLE SCHEDULE IS ATTACHED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-22 Cont ID  
Sent By btrobaug Date 2010-02-22 Time 12:50 Rev Time 0.00
Received By btrobaug Date 2010-02-22 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-30 Cont ID  
Sent By btrobaug Date 2009-11-30 Time 11:37 Rev Time 0.00
Received By btrobaug Date 2009-11-30 Time 11:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-02-23 Cont ID  
Sent By mawillia Date 2010-02-23 Time 12:13 Rev Time 0.00
Received By mawillia Date 2010-02-23 Time 12:04 Sent To  
Notes
2010-02-23 12:12:49******APPROVED*****
  
 PLAN SHEET 1.1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-02-16 Cont ID  
Sent By mawillia Date 2010-02-16 Time 14:15 Rev Time 0.00
Received By mawillia Date 2010-02-16 Time 14:06 Sent To  
Notes
2010-02-16 14:12:00*****PARTIAL APPROVAL*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN:
  
 1. THE BUILDING EXAMINER'S COMMENTS HAVE BEEN
 ADDRESSED.
  
 2. WHEN THE CONTRACTOR'S LICENSURE HAS BEEN VERIFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-01-26 Cont ID  
Sent By mawillia Date 2010-01-26 Time 15:35 Rev Time 0.00
Received By mawillia Date 2010-01-26 Time 15:16 Sent To  
Notes
2010-01-26 15:31:53*****PARTIAL APPROVAL*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN:
  
 1. THE BUILDING EXAMINER'S COMMENTS HAVE BEEN
 ADDRESSED.
  
 2. WHEN THE CONTRACTOR'S LICENSURE HAS BEEN VERIFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-01 Cont ID  
Sent By mawillia Date 2009-12-01 Time 13:41 Rev Time 0.00
Received By mawillia Date 2009-12-01 Time 13:16 Sent To  
Notes
2009-12-01 13:41:23*****DENIED*****
  
  
 1. PLEASE PROVIDE INFORMATION ON THE BUILDING PERTINENT
 TO CONDUCTING A THOROUGH FIRE PLAN REVIEW SUCH AS:
 OCCUPANCY TYPE OCCUPANT LOAD FIRE SPRINKLER SYSTEM (IF
 ANY) FIRE ALARM SYSTEM (IF ANY)
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 4. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. PROVIDE LOCATION OF THE FIRE/LIFE SAFETY DEVICES (
 FIRE EXTINGUISHERS, EXIT LIGHTS, EMERGENCY LIGHTS,
 SMOKE ALARMS/DETECTORS) APPLICABLE TO THE OCCUPANCY
 TYPE.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-02-08 Cont ID  
Sent By btrobaug Date 2010-02-08 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2010-02-08 Time 16:56 Sent To  
Notes
2010-02-08 16:59:44B-6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-13 Cont ID  
Sent By lmartine Date 2010-01-12 Time 16:56 Rev Time 0.00
Received By lmartine Date 2010-01-12 Time 16:55 Sent To  
Notes
2010-01-13 16:56:51*********************EXPEDITED***********************
 B--1
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-14 Cont ID  
Sent By hmoser Date 2009-12-14 Time 09:42 Rev Time 0.00
Received By hmoser Date 2009-12-14 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-20 Cont ID  
Sent By rregueir Date 2010-01-20 Time 18:45 Rev Time 0.00
Received By rregueir Date 2010-01-20 Time 18:44 Sent To  
Notes
2010-01-20 18:45:33**PROVISO**
  
 PROVIDE STRUCTURAL INSTALLATION DETAIL FOR ROOF CURB.
 ALSO PROVIDE RTU MANUFACTURER'S WIND RESISTANCE DATA
 PER FBC-M 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-14 Cont ID  
Sent By hmoser Date 2009-12-14 Time 09:33 Rev Time 0.00
Received By hmoser Date 2009-12-14 Time 08:59 Sent To  
Notes
2009-12-14 09:38:21MECHANICAL PLANS DENIED .
 PLEASE PROVIED A EQUIPMENT SCHEDULE WITH EQUIPMENT SIZE
 ON PLANS .
 PLEASE PROVIDE ENERGY CALCULATIONS WITH PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-02-18 Cont ID  
Sent By kstevens Date 2010-02-18 Time 14:31 Rev Time 0.00
Received By kstevens Date 2010-02-18 Time 14:31 Sent To  
Notes
2010-02-18 14:32:05NEW SHEET

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-21 Cont ID  
Sent By kstevens Date 2010-01-21 Time 17:11 Rev Time 0.00
Received By kstevens Date 2010-01-21 Time 17:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By kstevens Date 2009-11-30 Time 15:59 Rev Time 0.00
Received By kstevens Date 2009-11-30 Time 15:59 Sent To  
Notes
2009-11-30 16:04:25DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
  
 1. PLEASE INDICATE THE OCCUPANCY OF THE SPACE/UNIT PER
 SECTION 106.3.5.1.1(2) AND TABLE 403.1.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION PER SECTION
 104.1.
  
 3. A COMPLETE REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 MORE COMMENTS MAY BE FORTHCOMING WHEN THE ABOVE
 COMMENTS ARE ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-19 Cont ID  
Sent By jroach Date 2010-01-19 Time 18:39 Rev Time 0.00
Received By jroach Date 2010-01-19 Time 18:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By jroach Date 2009-11-24 Time 15:54 Rev Time 0.00
Received By jroach Date 2009-11-24 Time 15:54 Sent To  
Notes
2009-11-24 18:41:04ZONING PLAN REVIEW
  
 PERMIT NO.: 09110339
 ADDRESS: 429 BELVEDERE ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.: 561.832.1500
 SCOPE OF REVIEW: INTERIOR REMODEL TO EXISTING
 APARTMENT.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS EXTERIOR IMPROVEMENTS ARE PROPOSED (ADDITION OF
 AN A/C CONDENSING UNIT), TWO (2) COPIES OF A CURRENT
 AND ACCURATE SURVEY SHALL BE PROVIDED.
  
 2) AS EXTERIOR IMPROVEMENTS ARE PROPOSED (ADDITION OF
 AN A/C CONDENSING UNIT), TWO (2) COPIES OF A SITE PLAN
 SHALL BE PROVIDED INDICATING THE LOCATION OF THE NEW
 A/C UNIT. DIMENSIONS SHALL BE PROVIDED FROM THE NEW A/C
 UNIT TO ALL ADJACENT PROPERTY LINES.
  
 3) PURSUANT TO SECTION 94-444(B) OF THE CITY???S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), MECHANICAL
 (A/C) EQUIPMENT SHALL BE SCREENED. SCREENING SHALL
 CONSIST OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL.
 ADDITIONALLY, THE SCREENING SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO (2) FOOT INTERVALS.
 PLEASE NOTE: SEPARATE PERMITS WILL BE REQUIRED FOR
 EACH, FENCING AND LANDSCAPING.
  
 PLEASE NOTE THAT MATERIALS/PLANS PROVIDED AT TIME OF
 RESUBMITTAL MAY GENERATE ADDITIONAL COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved