| Plan Review Stops For Permit 09110336 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-02-04 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-02-04 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2010-02-04 10:36:32 | ONLY NEEDED CONTRACTOR ON APPLICATION. OK PER JW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2010-01-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-01-21 |
Time |
07:56 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2010-01-21 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2010-01-21 07:57:50 | PLANS ARE CODE COMPLIANT, TEMPORARY FAILED UNTIL | | | CONTRACTOR IS SIGNED ON AND LICENSURE IS VERIFIED AND | | | PLANS ARE DATE STAMPED . |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-12-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-08 |
Time |
12:20 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2009-12-08 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2009-12-08 12:21:50 | PLANS ARE CODE COMPLIANT, TEMPORARY FAILED UNTIL | | | CONTRACTOR IS SIGNED ON AND LICENSURE IS VERIFIED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-02-04 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-02-04 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2010-02-04 10:36:46 | * PROVISO ** | | | | | | 1) NOTE: NEED TO SUBMIT COPY OF SIGNED CONTRACT | | | INCLUDING VALUE FOR ALL LABOR, MATERIALS, EQUIPMENT, | | | SET UP AND DESIGN FEES. | | | APPLIED VALUE IS LOW. THERE WILL A HOLD ON INSPECTIONS | | | UNTIL COMPLETED VALUE IS VERIFIED. | | | FBC 108.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2010-01-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-01-20 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-01-20 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2010-01-20 11:58:13 | ** DENIED * | | | | | | 1) NOTE: PERMIT APPLICATION HAS NOT YET BEEN MADE BY A | | | LICENSED CONTRACTOR. SEPARATE ELECTRICAL/LOW VOLTAGE | | | PERMITS WILL BE REQUIRED HOWEVER PRIMARY PERMIT NEEDS | | | TO HAVE LICENSED CONTRACTOR FOR APPLIED WORK BEFORE | | | REVIEW CAN BE PASSED. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-12-09 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-12-09 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2009-12-09 13:58:19 | | | | ** DENIED ** | | | | | | ** REVIEW UNDER 2008 NEC. | | | | | | 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW | | | WORK AS SHOWN ON PLANS. THE VALUE FOR THE COMPLETE | | | SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3 REQUIRES THE | | | VALUE TO INCLUDE ALL LABOR, EQUIPMENT, MATERIALS, | | | DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER | | | SUPPLIED. | | | | | | 2) NOTE: PLEASE KNOW THE FOLLOWING CODE WHICH IS | | | RELEVANT TO THE DESIGN SHOULD BE ON PLANS. | | | 2008 NFPA-70 (PLANS DO NOT INDICATE ANY SPECIFIC | | | EDITION ON COVER SHEET) | | | 2006 NFPA-101 (PLANS INDICATE THE 2003. FAC | | | 69A-60.003,.004 ADOPTED THE 2006 ON DECEMBER 31ST, | | | 2008. | | | 2007 FLORIDA FIRE PREVENTION CODE (PLANS INDICATE THE | | | 2004 EDITION. | | | | | | 3) NOTE: NOT APPLIED FOR PERMIT BY A LICENSED | | | CONTRACTOR FOR SCOPE OF WORK. LICENSURE INFORMATION | | | WILL NEED TO BE VERIFIED WHEN CONTRACTOR HAS BEEN | | | DETERMINED. | | | | | | 4) NOTE: PLEASE INDICATE ANY ROUTING OF CONDUITS DOWN | | | THROUGH THE BUILDING. PLEASE BE SURE TO SEE CHAPTER 10 | | | OF THE FBC AS CONDUITS ARE NOT PERMITTED IN EGRESS | | | STAIRS. | | | | | | | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-02-04 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-02-04 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2010-02-04 10:37:31 | ONLY NEEDED CONTRACTOR ON APPLICATION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2010-01-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-01-26 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-01-26 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2010-01-26 15:01:39 | ****PARTIAL APPROVAL***** | | | | | | PLAN APPEARS TO BE CODE COMPLIANT, HOWEVER, TO REMAIN | | | IN A FAILED STATUS UNTIL A CONTRACTOR IS SIGNED ON AND | | | LICENSURE IS VERIFIED; PLAN SHEET E-2 STAMPED, | | | INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-12-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-12-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-12-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2009-12-13 17:22:31 | *****PARTIAL APPROVAL***** | | | | | | PLAN APPEARS TO BE CODE COMPLIANT; THE APPROPIATE | | | SHEETS TO BE FIRE-STAMPED WHEN THE FOLLOWING HAVE BEEN | | | SATISFIED: | | | | | | 1. A CONTRACTOR IS SIGNED ON AND LICENSURE IS VERIFIED. | | | | | | 2. ON SHEET T-1, AMEND TO REFLECT THE CURRENT CODES IN | | | USE AS SUCH: FLORIDA FIRE PREVENTION CODE 2007 AND NFPA | | | 101, LIFE SAFETY CODE, 2006 EDITIONS. | | | | | | 3. ON THE APPROPIATE PLAN SHEET, REFERENCE 7.1.3.2.1 | | | (6) OF NFPA 101 AS IT PERTAINS TO THE LIMITING OF | | | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-01-11 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-01-11 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-12-17 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-11-17 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2009-12-17 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-12-16 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-12-16 |
Time |
10:27 |
Sent To |
I |
|
| Notes |
|
|