Plan Review Details - Permit 09110301
Plan Review Stops For Permit 09110301
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-05 Cont ID  
Sent By jwitmer Date 2010-01-05 Time 11:40 Rev Time 1.33
Received By jwitmer Date 2010-01-04 Time 15:35 Sent To  
Notes
2010-01-05 11:59:44BUILDING PLAN REVIEW
 PERMIT: 09110301
 ADD: 300 NORTHPOINT PARKWAY
 CONT: ITASCA
 TEL: (954)714-6998
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: REVIEWED
 JAN. 05/2010
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) SHEET A100 DOOR# 6 IS A NEW DOOR AND FRAME REQUIRING
 PRODUCT APPROVALS ( FL ADMINISTRATIVE CODE RULE
 9B-72.31(A). CONTRACTOR TO PROVIDE BEFORE FRAMING
 INSPECTION.
  
 2) SHEET A130 TABLE 1019.2, THE TRAVEL DISTANCE FOR THE
 S-2 WAREHOUSE WILL REQUIRE THE 2ND EXIT. THE DOOR
 BETWEEN THE PHARMACY SHIPPING AND WAREHOUSE IS THE 2ND
 REQUIRED MEANS OF EGRESS FROM THE WAREHOUSE. 1014.2
 ALLOWS FOR EGRESS THROUGH INTERVENING SPACES AS LONG AS
 THE DOORS ARE NOT LOCKED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-14 Cont ID  
Sent By jwitmer Date 2009-12-14 Time 11:39 Rev Time 1.50
Received By jwitmer Date 2009-12-14 Time 10:13 Sent To  
Notes
2009-12-14 11:40:25BUILDING PLAN REVIEW
 PERMIT: 09110301
 ADD: 300 NORTHPOINT PARKWAY
 CONT: ITASCA
 TEL: (954)714-6998
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE HEADING OF ADDRESS
 INDICATES THE JOBSITE LOCATION AS 300 NORTHPOINT
 PARKWAY, PLEASE ADD THE SUITE NUMBER TO THE
 APPLICATION.
  
 2) THE COVERSHEET SUBMITTED ONLY INDICATES LEVEL OF
 ALTERATION NOT THE EDITION OF THE CODE UNDER WHICH THE
 DESIGN WAS CREATED. PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO
 THE 2007 FBC BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE. THE COVERSHEET
 INDICATES LEVEL OF ALTERATION II SECTION 304, THIS
 SECTION UNDER THE 2007 FBC EXISTING BUILDING IS FOR
 GLASS REPLACEMENT, LEVEL II SCOPING IS FOUND IN FBC
 EXISTING BLDG 404.1. PLEASE UPDATE PLANS.
  
 3) SHEET A100 NOTE C7 & C12 BOTH INDICATE THE USE OF
 GLASS WALL SYSTEM, PLEASE INDICATE TYPE OF GLASS TO BE
 USED WITHIN THE GLASS WALL SYSTEM, NO NOTES ON GLAZED
 SYSTEM AT DOOR SCHEDULE SHEET A300. HAZARDOUS LOCATION
 2406.3.3.
  
 4) SHEET A100 DOOR NUMBER (6) NOTES INDICATE THIS DOOR
 IS TO BE REPLACED, PLEASE PROVIDE PRODUCT APPROVALS
 REVIEWED BY THE DESIGN TEAM. FL S RULE 9B-72.31( A) &
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) SINCE THE EXTERIOR DOOR# 6 IS BEING REPLACED PLEASE
 PROVIDE WIND CRITERIA DESIGN INFORMATION.
 1609.6.2 WIND DESIGN PROCEDURES
 5.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 5.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 6) SHEET A100. PLEASE CLARIFY WHAT APPEARS TO BE A RAMP
 ON THE EXTERIOR SIDE OF DOOR# 6.
 IF THIS IS A RAMP THERE IS NO TOP NOR BOTTOM LANDING,
 PLEASE REVIEW SECTION 11-4.8.4.(2) LANDINGS. ALL
 LANDINGS ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, &
 THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF
 STRAIGHT & LEVEL CLEARANCE.
  
 7) PLEASE LABEL THE EXISTING DOOR FROM THE WAREHOUSE TO
 PHARMACY SHIPPING, THIS DOOR CAN NOT BE LOCKED SINCE IT
 IS PART OF THE EGRESS PATH TO THE EXTERIOR. 1014.2 DOES
 ALLOW FOR EGRESS THROUGH INTERVENING SPACES AS LONG AS
 THE DOORS ARE NOT LOCKED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-01-12 Cont ID  
Sent By dpalmer Date 2010-01-12 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2010-01-12 Time 08:52 Sent To PC
Notes
2010-01-12 08:54:19PROVISO
  
 PLEASE REVISE PLANS FOR NOTE #1 BELOW BEFORE FINAL. ALL
 OTHER REVISIONS ARE TO BE REVISED, SUBMITTED FOR REVIEW
 AND ON JOB-SITE BEFORE ROUGH.
 ** ALL LOW VOLTAGE IS UNDER SEPARATE PERMITS. THESE
 PLANS MAY BE REFERENCED FOR DATA/PHONE ONLY FOR TURN
 AROUND PERMITS.
  
 1) NOTE: ALL PANEL SCHEDULES WILL BE UPDATED TO BE
 SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 408.4.
 PLACING * LIGHTING OR RECEPTACLES* IN GENERAL IN NOT
 ACCEPTABLE FOR PANEL SCHEDULES ON RECORD PLANS. ALL
 OTHER CHANGES ARE TO BE REVISED AND SUBMITTED BEFORE
 ROUGH INSPECTIONS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-01-04 Cont ID  
Sent By dpalmer Date 2010-01-04 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2010-01-04 Time 10:47 Sent To  
Notes
2010-01-04 10:47:14** TEMPORARY DENIED *
  
 ** THE NOTE #1 BELOW NEEDS TO BE ADDRESSED AT THIS
 TIME. THE NOTE #2 WILL BE PART OF THE PROVISO AS
 REFERENCED ON THE INITIAL REVIEW.
  
  
 1) NOTE: THE SECOND COPY OF THE SUBMITTED FLA COM
 CALCULATIONS IS IN FACT A PHOTO-COPY OF SIGNED AND SEAL
 DOCUMENTS. PLEASE SUBMIT SECOND SET OF ORIGINAL SIGNED,
 DATED AND SEALED CALCULATIONS.
 FAC 61G15-23.002, FS 471.025
  
 2) NOTE: ALL PANEL SCHEDULES WILL BE UPDATED TO BE
 SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 408.4.
 PLACING * LIGHTING OR RECEPTACLES* IN GENERAL IN NOT
 ACCEPTABLE FOR PANEL SCHEDULES ON RECORD PLANS. ALL
 OTHER CHANGES ARE TO BE REVISED AND SUBMITTED BEFORE
 ROUGH INSPECTIONS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-13 Cont ID  
Sent By mawillia Date 2009-12-08 Time   Rev Time 0.00
Received By dpalmer Date 2009-12-08 Time 10:16 Sent To  
Notes
2010-01-11 10:17:09 
 ** DENIED **
  
 ** SOME ITEMS BELOW COULD HAVE BEEN REDLINED HOWEVER
 NOT ALL. PLEASE ADDRESS COMMENTS AT THIS TIME.
  
 1) NOTE: *PLEASE ADJUST CODES AS FOLLOWS FOR THIS
 REVIEWER AS APPLICABLE. SOME OTHER CODES MAY BE NOTED
 BY OTHER TRADES.
 PLANS INDICATE 2004 FBC ON SOME OF THE ARCHITECTURAL
 SHEETS AS WELL AS OLDER NFPA-1 AND NFPA-101 EDITIONS.
 SEE A100, A130 ETC.
 ELECTRICAL SHEETS INDICATE THE 2005 NFPA-70.
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE
 ADJUSTED ON SHEETS
  
 THE 2008 NFPA-70: ADOPTED ON OCTOBER 1ST, 2009. PLEASE
 ADJUST DESIGNS FOR NEW REVISED CODES.
 2006 NFPA-101: ADOPTED 12/31/08 BY FAC 69A-60.004
 2002 NFPA-72: ADOPTED 12/31/08 FAC 69A-3.012
 2006 NFPA-1: ADOPTED 12/31/08 FAC 69A-60.003( TO BE
 NOTED BY FIRE REVIEW
 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY
 FIRE REVIEW) PLANS STATE 2006 FFPC.
  
  
 2) NOTE: PLEASE CLARIFY THE OCCUPANCY OF THIS BUILDING
 OUT PER FBC CHAPTER 3. THE PLANS APPEAR TO INDICATE
 BUSINESS HOWEVER THE COVER SHEET ALSO INDICATES A
 MEDICAL STORE. IS THIS MERCANTILE OR BUSINESS OFFICES?
 THIS WILL AFFECT THE LIGHTING ALLOWANCES.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR REVIEW. NONE SUBMITTED FOR MINIMUM
 CODE COMPLIANCE.
 13-415.AB.5, 13-400.0.B.4, 13-400.2
  
 4) NOTE: PLEASE SEE 408.4 IN THE NEC. THE PANEL
 SCHEDULE WILL BE REQUIRED TO BE UPDATED WITH ALL
 CIRCUITS. PLANS WILL ALSO BE REQUIRED TO HAVE ALL
 CIRCUITS LABELED AND COORDINATED WITH PANEL SCHEDULES.
 THE USE OR WORDING OF *LIGHTING* OR *RECEPTACLES* IS
 NOT ACCEPTABLE. THE FOLLOWING IS EXTRACTED DIRECTLY
 FROM THE NEC HANDBOOK.
 **
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 ** AS THIS IS AN EXISTING SITUATION A PROVISO CAN BE
 SET UP TO SUBMIT COMPLETE REVISED PANEL SCHEDULES AND
 CIRCUITING ON PLANS FOR ALL EXISTING AND NEW BEFORE
 FINAL.
 ALL NEW IS REQUIRED TO BE COORDINATED AT THIS TIME FOR
 ALL NEW RECEPTACLES, LIGHTING AND EQUIPMENT.
 ALL REVIEW OF LOADING ON CIRCUITS WILL BE DONE ONCE
 PLANS HAVE BEEN REVISED AND COORDINATED WITH PANEL
 SCHEDULES.
  
 5) NOTE: ALL LOW VOLTAGE IS UNDER SEPARATE PERMITS. ANY
 ACCESS CONTROL SYSTEM WILL ALSO BE UNDER SEPARATE
 PERMIT WITH SUBMISSION OF SEPARATE PLANS FOR DETAILS OF
 ACCESS CONTROLS MEETING NFPA-101 CHAPTER 7.
  
 6) NOTE: NEW OR EXISTING SIGN CIRCUIT REQUIRED PER
 600.5.
  
 7) NOTE: RISER INDICATES FEEDERS TO TRANSFORMER FROM
 PANEL H1A, HOWEVER THE PANEL IS NOTED AS H1SA.
 (MISPRINT)
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2009-12-13 17:47:22*****FIRE REVIEW, DENIED*****
  
 1. THE SUITE NUMBER SHALL BE INCLUDED IN THE PROJECT
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2. AS OF DECEMBER 31, 2008, THE 2007 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM
 FIRE CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE,
 2006 EDITION SHALL BE REFERENCED. AMEND THE CODE
 SECTIONS LISTED ON THE AFFECTED SHEETS TO REFLECT THE
 EDITIONS CURRENTLY ADOPTED.
  
 3. ON SHEET FS2.1, PROVIDE A LAYOUT OF THE FIRE
 SPRINKLER HEADS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By mawillia Date 2010-01-11 Time 11:21 Rev Time 0.00
Received By mawillia Date 2010-01-11 Time 10:56 Sent To  
Notes
2010-01-11 11:14:58*****APPROVED*****
  
  
 PLAN SHEETS A-130, A-300, E2.1, FA0.1, FA2.1, FS0.1,
 AND FS2.1 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-08 Cont ID  
Sent By mawillia Date 2009-12-11 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2009-12-11 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-29 Cont ID  
Sent By lmartine Date 2009-12-29 Time 16:35 Rev Time 0.00
Received By lmartine Date 2009-12-29 Time 16:34 Sent To  
Notes
2009-12-29 16:39:28****************EXPEDITED******************
2009-12-29 16:37:23C--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-29 Cont ID  
Sent By lmartine Date 2009-12-15 Time 16:32 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 09:27 Sent To  
Notes
2009-11-18 09:27:43C 11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-01-12 Cont ID  
Sent By dpalmer Date 2010-01-12 Time 08:54 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2010-01-12 08:54:58INTERIOR WORK AND WORK DOES NTO AFFECT OCCUPANCY
 CHANGE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-15 Cont ID  
Sent By hmoser Date 2009-12-15 Time 14:45 Rev Time 0.00
Received By hmoser Date 2009-12-15 Time 13:36 Sent To  
Notes
2009-12-15 14:48:53PLEASE REFER TO BUILDING NOTES ON 2004 AND 2007 CODES
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-12-15 Cont ID  
Sent By kstevens Date 2009-12-15 Time 15:52 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-11-25 Cont ID  
Sent By eschneid Date 2009-11-25 Time 16:55 Rev Time 0.20
Received By eschneid Date 2009-11-25 Time 16:55 Sent To  
Notes
2009-11-25 16:56:19NO EXTERIOR CHANGES REQUIRING ZONING APPROVAL.
  
 VALUE OF PERMITS WITHIN LAST 12 MONTHS IS LESS THAN 50%
 VALUE OF STRUCTURE.