Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-25 Cont ID  
Sent By jwitmer Date 2010-01-25 Time 16:01 Rev Time 0.88
Received By jwitmer Date 2010-01-25 Time 15:56 Sent To  
Notes
2010-01-25 16:00:58BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 SHEET A1.4 DOOR# 58 IS MISSING THE 18 INCHES LATCH SIDE
 OF DOORWAY SEE 11-4.13.6
  
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-08 Cont ID  
Sent By jwitmer Date 2009-12-08 Time 10:21 Rev Time 2.00
Received By jwitmer Date 2009-12-08 Time 10:21 Sent To  
Notes
2009-12-08 11:07:25BUILDING PLAN REVIEW
 PERMIT: 09110277
 ADD: 534 DATURA ST
 CONT: ATLANTIC BAY PARTNERS INC
 TEL: (954)600-4646
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DECEMBER 08/ 2009
  
 1) A CLARIFICATION OF THE SCOPE OF WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT NEEDS TO BE ADDRESSED.
 THE PERMIT APPLICATION DESCRIPTION PROJECT IN DETAIL
 INDICATES COMMON AREAS ON THE FIRST FLOOR WHERE AS THE
 COVERSHEET OF THE PLANS UNDER PROJECT DESCRIPTION
 INDICATES COMMON AREAS FOR THE FIRST AND SECOND FLOOR.
 PLANS ONLY INDICATE THE FIRST FLOOR. 106.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE TO
 COMPLETE THIS REVIEW THOROUGHLY.
  
 2A) MINIMUM BUILDING TYPE PER TABLE 503 & TABLE 601.
  
 2B) IS THE BUILDING FULLY FIRE SPRINKLERED?
  
 2C) THE BUILDING IS A MIXED USE OCCUPANCY , IS THE
 DESIGN CRITERIA SEPARATED USE 508.3.1.3 FOR OCCUPANCIES
 OR NON-SEPARATED OCCUPANCIES 508.3.2?
  
 2D) PLANS WILL NEED TO INDICATE ONCE THE SPRINKLER
 ISSUE IS KNOWN, WALL AND CEILING FINISHES PER SECTION
 803.1 AND TABLE 803.5 FOR OCCUPANCIES, CORRIDORS ,ETC.
  
 2E) OCCUPANCY LOADS PER TABLE 1004.1.1.
  
 2F) 2007 W 2009 SUPPLEMENTS EXISTING BUILDING CODE-
 SECTION 401.4 A DESIGN PROFESSIONAL OR OWNER MUST ELECT
 ONE OR MORE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403,404 AND 405 OF THIS CODE.
  
 2G) FLOOR CEILING ASSEMBLIES WILL NEED TO INDICATE
 COMPLIANCE WITH TABLE 601 AND 803.9.1.2
 FIRE-RESISTANCE-RATED CONSTRUCTION. ACOUSTICAL CEILING
 SYSTEMS THAT ARE PART OF FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE INSTALLED IN THE SAME MANNER USED
 IN THE ASSEMBLY TESTED AND SHALL COMPLY WITH THE
 PROVISIONS OF CHAPTER 7.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-03-09 Cont ID  
Sent By dpalmer Date 2010-03-09 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2010-03-09 Time 10:28 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-01-28 Cont ID  
Sent By dpalmer Date 2010-01-28 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2010-01-28 Time 14:06 Sent To  
Notes
2010-01-28 14:06:57 
 ** DENIED SECOND REVIEW *
  
 ** THIS REVIEWER ATTEMPTED TO CONTACT ARCHITECT OF
 RECORD HOWEVER PHONE NUMBERS LISTED ON RESPONSE LETTER
 AND PLANS IS DISCONNECTED.
  
 1) NOTE: THE RESPONSE LETTER FOR SOME ITEMS DID NOT
 SEEM TO RESPOND TO THE ACTUAL COMMENT. THE SCOPE ON
 PREVIOUS PLANS WAS UNCLEAR AND WE NEEDED MORE
 INFORMATION FOR REVIEW. A PREVIOUS COMMENT WAS MADE
 ABOUT COMPLIANCE FOR CHAPTER 13. HOWEVER THE RESPONSE
 WAS THAT THE MECHANICAL SYSTEMS WERE NOT BEING ALTERED.
 PLEASE SEE CHAPTER 13 OF THE FLORIDA BUILDING CODE.
 CHAPTER 13 COVERS MANY ITEMS WHICH ARE NOT MECHANICAL
 SYSTEMS. RESPONSE MENTIONS MECHANICAL SYSTEMS HOWEVER
 SPECIFIC CODE SECTIONS FOR OTHER ITEMS LISTED BELOW
 WERE GIVEN ON PREVIOUS NOTES WHICH WERE NOT ABOUT
 MECHANICAL SYSTEMS.
 FOR EXAMPLE:
 PLEASE SEE 13-413 FOR REQUIREMENTS FOR ELECTRICAL
 POWER.
 PLEASE SEE 13-415.AB.5 FOR THE REQUIREMENTS FOR
 LIGHTING PERFORMANCE CALCULATIONS FOR NEW LIGHTING
 MEETING PRESCRIPTIVE REQUIREMENTS. IN BRIEF EVEN WHEN
 NOT MEETING THE DEFINITION OF A RENOVATION AS DEFINED
 IN SECTION 202, THE NEW BEING INSTALLED IS STILL
 REQUIRED TO MEET MINIMUM PRESCRIPTIVE REQUIREMENTS.
 13-400.0.B.4
 PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR
 LIGHTING CONTROLS WHERE REQUIRED. ANY SEPARATE SPACES,
 NEW CONTROLS INSTALLED OR SEPARATE SPACE CONTROLS ARE
 REQUIRED TO MEET MINIMUMS.
  
 FOR EXAMPLE: ANOTHER NOTE FROM PREVIOUS REVIEW WAS WITH
 RESPECT TO CHAPTER 11 REQUIREMENTS. THE RESPONSE NOTED
 REQUIREMENTS FOR ADA OF BATHROOMS, LAVATORIES ETC
 HOWEVER THERE ARE OTHER ITEMS IN CHAPTER 11 WHICH ARE
 REQUIRED FOR MINIMUM ADA COMPLIANCE WHICH ARE NOT ONLY
 BATHROOMS, DOORS ETC. THIS WAS GIVEN IN PREVIOUS REVIEW
 HOWEVER RESPONSE DID NOT RESPOND TO FA DEVICES FOR ADA.
 PLEASE PROVIDE INFORMATION ON ANY HORN, STROBE DEVICES,
 LOCATIONS AND HEIGHTS IN COMPLIANCE WITH 11-4.28,.1, .2
 AND .3.
 THIS FACILITY DOES HAVE A FIRE ALARM SYSTEM AND BASE
 DESIGN INTENT FOR MINIMUMS NEED TO BE SHOWN.
 WHERE ARE THE DEVICES, WILL NEW WORK AFFECTING THE
 DEVICES?
 BASED ON THE PLANS NEW WORK WILL AFFECT THE DEVICES.
  
  
 2) NOTE: SHOW LOCATIONS OF EXISTING OR NEW EMERGENCY
 LIGHTING MEETING NFPA-101 7.8, 7.9. FBC 1006.1, 1006.2
 AND 1006.3.
 PLACING A NOTE ON PLANS FOR THIS TO BE VERIFIED DOES
 NOT PROVIDE MINIMUM INFORMATION.
 EXIT LIGHTING PLACEMENT WILL BE UNDER FIRE MARSHAL
 REVIEW.
 NOTES ON PLANS MENTIONS EXIT LIGHTS TO BE CIRCUITED TO
 EXISTING EMERGENCY LIGHT CIRCUIT. PLEASE SEE NEC
 700.12F FOR ANY NEW OR EXISTING EMERGENCY LIGHTS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-03 Cont ID  
Sent By dpalmer Date 2009-12-03 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-12-03 Time 14:39 Sent To  
Notes
2009-12-03 14:39:59** DENIED**
  
 1) NOTE: THERE IS MINOR WORK WHICH WILL INVOLVE
 ELECTRICAL WORK HOWEVER NO ELECTRICAL DETAILS OR SCOPE
 SUBMITTED.
 PLANS INDICATE NEW CEILING IN SOME AREAS HOWEVER
 LIGHTING FIXTURE LAYOUT AND MINIMUM FOR COMPLIANCE NOT
 SHOWN OR SUBMITTED. PLEASE VERIFY SCOPE FOR THE
 FOLLOWING CURRENT CODES:
 2007 FBC W/2009 REVISIONS, SEE CHAPTER 13,
 13-415.AB.1.1,.1.2, 13-415.AB.5 FOR ENERGY COMPLIANCE
 AND CHAPTER 11, 11-4.28.1,.2 AND.3 FOR ADA.
 PLEASE SEE NFPA-101 2006 7.8.1.3, 7.9.1.2,.2.2 FOR
 MINIMUM REQUIRED FOR LIFE SAFETY FOR EGRESS.
 PLEASE SEE NFPA-70 700.12F FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-08 Cont ID  
Sent By mawillia Date 2010-02-08 Time 16:14 Rev Time 0.00
Received By mawillia Date 2010-02-08 Time 15:53 Sent To  
Notes
2010-02-08 15:56:17*****APPROVED****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A00 & A1.5 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By mawillia Date 2009-12-28 Time 10:39 Rev Time 0.00
Received By mawillia Date 2009-12-28 Time 10:16 Sent To  
Notes
2009-12-27 21:18:55*****DENIED****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. AS OF 12/31/2008, THE 2007 FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION
 AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. THE SCOPE OF WORK FOR THIS PROJECT IS DESCRIBED (ON
 SHEET A00) AS TO THE COMMON AREAS ON THE BOTH THE FIRST
 AND SECOND FLOOR. NO PLANS INDICATED FOR THE SECOND
 FLOOR.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 5. PROVIDE A LIFE SAFETY PLAN DEPICTING THE LOCATION OF
 EXIT LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND
 TRAVEL DISTANCES TO THE EXITS.
  
 6. HOW WILL THE PROJECTED SCOPE OF WORK HAVE AFFECT ON
 THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS? SEPARATE
 PLANS AND PERMITS WILL BE REQUIRED FOR ANY REMODEL TO
 THESE LIFE SAFETY SYSTEMS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-03 Cont ID  
Sent By rmcdouga Date 2010-03-03 Time 11:19 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2010-03-03 11:21:46TO D PALMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-14 Cont ID  
Sent By lmartine Date 2010-01-13 Time 17:02 Rev Time 0.00
Received By lmartine Date 2010-01-13 Time 17:01 Sent To  
Notes
2010-01-14 17:03:57C--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-28 Cont ID  
Sent By mawillia Date 2009-12-28 Time 10:16 Rev Time 0.00
Received By mawillia Date 2009-11-17 Time 15:19 Sent To  
Notes
2009-11-17 15:19:31C-37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-09 Cont ID  
Sent By dpalmer Date 2010-03-09 Time 10:28 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2010-01-26 Cont ID  
Sent By rregueir Date 2010-01-26 Time 17:03 Rev Time 0.00
Received By rregueir Date 2010-01-26 Time 16:57 Sent To  
Notes
2010-01-26 17:02:59PER ARCHITECTURAL NOTE ON PAGE A1.0, SEPARATE
 MECHANICAL PLANS AND PERMIT APPLICATION TO BE
 SUBMITTED. HOLD IS BEING PLACED ON THIS PERMIT TO
 ASSURE MECHANICAL WORK IS PERMITTED AND COMPLETE PRIOR
 TO OCCUPANCY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-19 Cont ID  
Sent By rregueir Date 2009-12-19 Time 12:53 Rev Time 0.00
Received By rregueir Date 2009-12-19 Time 12:53 Sent To  
Notes
2009-12-19 12:52:36REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PAGE A1.0 SHOWS DEMOLITION OF EXISTING HVAC DUCT AND
 REPLACEMENT WITH NEW. NO DETAILS OR PLANS WERE
 SUBMITTED FOR THIS SCOPE OF WORK. PROVIDE DETAILED
 PLANS SHOWING THE INSTALLATION OF ALL NEW HVAC SYSTEM
 COMPONENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-12-15 Cont ID  
Sent By kstevens Date 2009-12-15 Time 14:54 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 14:54 Sent To  
Notes
2009-12-15 14:55:15NO PLUMBING PLANS SUBMITTED OR REQUIRED. -- REMOVAL OF
 EXISTING PLUMBING FIXTURES AND REPLACING WITH NEW.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-11-19 Cont ID  
Sent By aaponte Date 2009-11-19 Time 15:51 Rev Time 0.00
Received By aaponte Date 2009-11-19 Time 15:51 Sent To  
Notes
***NONE***