Plan Review Details - Permit 09110262
Plan Review Stops For Permit 09110262
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-11-18 Cont ID  
Sent By jwitmer Date 2009-11-18 Time 10:36 Rev Time 1.00
Received By jwitmer Date 2009-11-18 Time 09:36 Sent To  
Notes
2009-11-18 11:02:08BUILDING PROVISO:1207.3 STRUCTURE-BORNE SOUND. PROVIDE
 DOCUMENTATION BEFORE INSPECTION.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-23 Cont ID  
Sent By btrobaug Date 2009-11-23 Time 09:31 Rev Time 0.00
Received By btrobaug Date 2009-11-23 Time 09:27 Sent To  
Notes
2009-11-23 09:33:03TOOK FROM KEN'S DESK, REVIEWED, PUT BACK IN B-9./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-12-01 Cont ID  
Sent By mawillia Date 2009-12-01 Time 12:43 Rev Time 0.00
Received By mawillia Date 2009-12-01 Time 12:38 Sent To  
Notes
2009-12-01 12:43:13*****APPROVED*****
  
 SINGLE PLAN SHEET 1 WAS STAMPED, INIITLAED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2009-11-17 Time 15:10 Sent To  
Notes
2009-11-17 15:10:31B-9

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-11-30 Cont ID  
Sent By kstevens Date 2009-11-30 Time 09:12 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 16:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-12-01 Cont ID  
Sent By aaponte Date 2009-12-01 Time 16:07 Rev Time 0.00
Received By aaponte Date 2009-12-01 Time 16:07 Sent To  
Notes
***NONE***