Plan Review Details - Permit 09110257
Plan Review Stops For Permit 09110257
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-24 Cont ID  
Sent By lmartine Date 2009-11-23 Time 10:24 Rev Time 0.00
Received By lmartine Date 2009-11-23 Time 10:24 Sent To  
Notes
2009-11-24 10:25:07**********************EXPEDITED************************
 GAVE TO KENNY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-10 Cont ID  
Sent By lmartine Date 2009-11-10 Time 16:27 Rev Time 0.00
Received By lmartine Date 2009-11-10 Time 16:27 Sent To  
Notes
2009-11-10 16:28:21*********************EXPEDITED*******************
 GAVE TO KENNY

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-11-24 Cont ID  
Sent By dwise Date 2009-11-24 Time 16:05 Rev Time 0.00
Received By dwise Date 2009-11-24 Time 16:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-16 Cont ID  
Sent By kstevens Date 2009-11-16 Time 17:26 Rev Time 0.00
Received By kstevens Date 2009-11-16 Time 09:17 Sent To  
Notes
2009-11-16 17:37:37DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 MECHANICAL
 NFPA-99C 2002
  
 1. SUBMIT PLANS SHOWING COMPLIANCE WITH SECTIONS
 5.3.3.3.1 & 5.3.3.3.3.2.
  
 2. SUBMIT INFORMATION ON THE TOTAL VOLUME OF MED-GAS
 CONNECTED IN THE STORAGE ROOM PER SECTIONS 5.3.3.6.1 &
 5.3.3.3.6.3. ALSO SEE FBC-2007 MECHANICAL SECTION
 502.9.1.
  
 3. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 5.3.3.5.3 WITH ALL SUBSECTIONS.
  
 4. THE LIQUIDS DRAINED FROM A LEVEL-3 VACUUM SOURCE
 SHALL BE DIRECTLY CONNECTED TO A SANITARY DRAINAGE
 SYSTEM THROUGH A TRAPPED AND VENTED DRAIN. SECTION
 5.3.3.6.3.1. PLEASE SHOW ON PLANS.
  
 5. PER SECTION 713.6 OF THE FBC-2007 PLUMBING THE
 EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM (FLUID
 SECTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR
 ABOVE THE ROOF. PLEASE INDICATE ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved