| 2009-11-16 17:37:37 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 MECHANICAL |
| | NFPA-99C 2002 |
| | |
| | 1. SUBMIT PLANS SHOWING COMPLIANCE WITH SECTIONS |
| | 5.3.3.3.1 & 5.3.3.3.3.2. |
| | |
| | 2. SUBMIT INFORMATION ON THE TOTAL VOLUME OF MED-GAS |
| | CONNECTED IN THE STORAGE ROOM PER SECTIONS 5.3.3.6.1 & |
| | 5.3.3.3.6.3. ALSO SEE FBC-2007 MECHANICAL SECTION |
| | 502.9.1. |
| | |
| | 3. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 5.3.3.5.3 WITH ALL SUBSECTIONS. |
| | |
| | 4. THE LIQUIDS DRAINED FROM A LEVEL-3 VACUUM SOURCE |
| | SHALL BE DIRECTLY CONNECTED TO A SANITARY DRAINAGE |
| | SYSTEM THROUGH A TRAPPED AND VENTED DRAIN. SECTION |
| | 5.3.3.6.3.1. PLEASE SHOW ON PLANS. |
| | |
| | 5. PER SECTION 713.6 OF THE FBC-2007 PLUMBING THE |
| | EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM (FLUID |
| | SECTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR |
| | ABOVE THE ROOF. PLEASE INDICATE ON PLANS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |