| 2009-12-01 16:11:08 | ** DENIED ** |
| | |
| | 1) NOTE: PLANS STATE 2007 FBC ON COVER SHEET, HOWEVER |
| | BASED ON REVISED 2007 FBC WHICH NOW HAS TWO REVISED |
| | SUPPLEMENTS, CODES FOR DESIGN SHOULD BE SPECIFIC ON |
| | PLANS. |
| | THE 2008 NFPA-70 WAS ADOPTED ON OCTOBER 1ST,2009. |
| | PLEASE ADJUST DESIGNS FOR NEW REVISED CODES. |
| | 2006 NFPA-101 |
| | 2002 NFPA-72 |
| | 2006 NFPA-1 ( TO BE NOTED BY FIRE REVIEW |
| | 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY |
| | FIRE REVIEW) |
| | |
| | PER |
| | FAC 69A-60..03,.004, 69A-13.012 |
| | |
| | 2) NOTE: PLANS SUBMITTED CONTAIN TWO SETS OF ELECTRICAL |
| | PLANS IN ONE OF THE SETS AND ONE SET IN THE OTHER. WE |
| | ONLY NEED TWO TOTAL SETS. |
| | ** PLEASE ALSO KNOW THE ELECTRICAL PLANS DO NOT CONTAIN |
| | A SYMBOL LEGEND THEREFORE SOME COMMENTS BELOW ARE |
| | DERIVED BECAUSE ELECTRICAL DEVICES ARE NOT CLEAR. SEE |
| | NOTE # 5. |
| | |
| | 3) NOTE: MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE |
| | CHAPTER 13 HAS NOT BEEN MET. THE SUBMITTED FORM C FROM |
| | THE 2004 FBC MAY NOT BE USED. |
| | THE 2004 FLORIDA BUILDING CODE HAS NOT BEEN ADOPTED IN |
| | THE STATE OF FLORIDA SINCE MARCH 1ST, 2009. PLEASE KNOW |
| | AT THAT TIME THERE WAS 2009 SUPPLEMENTS TO THE 2007 |
| | FBC. PLEASE ALSO KNOW THAT AS OF OCTOBER 1ST, 2009 THE |
| | FBC WAS ONCE AGAIN REVISED WITH SEVERAL ITEMS IN |
| | CHAPTER 13. PLEASE SEE PERFORMANCE METHODS FROM THE |
| | 2007 FBC W/2009 SUPPLEMENTS. |
| | |
| | PLEASE SEE 13-101.1.3, 13-101.4.1, 13-400.0.B, |
| | 13-400.0.B.4, 13-400.2. |
| | |
| | PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING |
| | PERFORMANCE CALCULATIONS REQUIRED. PLEASE KEEP IN MIND |
| | IF USING A FORM FROM THE FLORIDA BUILDING CODE FOR |
| | SPACE BY SPACE, THEN ONE FORM IS REQUIRED FOR EACH |
| | SPACE. IF USING FLA-COM THEN PLEASE BE SURE TO COMPLETE |
| | THE INPUT DATA REPORT WHICH IS PART OF THE FLA COM |
| | PROGRAM. |
| | |
| | PLEASE SEE 13-415.AB.2 FOR ANY EXTERIOR ALLOWANCES. |
| | |
| | 4) NOTE: THE FORM C WAS SIGNED, BUT NOT SEALED BY THE |
| | RESPONSIBLE DESIGNER OF RECORD. PLEASE BE SURE WHEN |
| | SUBMITTING NEW ENERGY COMPLIANCE FORMS THAT THE |
| | SIGNATURE, DATE AND SEALS AS REQUIRED PER FBC 13-103.1, |
| | FAC 61G15-23.002, FS 471.025 |
| | |
| | 5) NOTE: PLEASE SUBMIT AND SHOW MORE INFORMATION |
| | SHOWING COMPLIANCE WITH FBC 13-415.AB.1.1,.1.2,.1.3 AND |
| | .1.4. |
| | PLANS INDICATE WHAT APPEARS TO BE A LIGHTING CONTROL |
| | SYSTEM WHICH IS OK, HOWEVER BASED ON SECTIONS GIVEN THE |
| | SEPARATE SPACES ON PLANS DO NOT COMPLY. SEPARATE SPACES |
| | ON PLANS SHOW WHAT WOULD BE STANDARD SINGLE POLE |
| | SWITCHES. IF THIS IS THE CASE THEY MUST MEET |
| | 13-415.AB.1.1 AND .1.2 FOR SEPARATE SPACE UNDER |
| | AUTOMATED CONTROLS AND OVER RIDES OF SYSTEM. THERE ARE |
| | OTHER CODE ACCEPTABLE OPTIONS AND THESE MAY BE GONE |
| | OVER BY CONTACTING THIS REVIEWER. |
| | PLEASE BE SURE TO SHOW COMPLIANCE AND TIMES FOR MAXIMUM |
| | OVER RIDES OF THE AUTOMATED LIGHTING CONTROLS. REVISE |
| | LIGHTING CONTROLS AS REQUIRED. |
| | |
| | 6) NOTE: PLEASE SEE SECTION 13-415.AB.1.4 FOR EXTERIOR |
| | LIGHTING. THE CODE ALLOWS TWO METHODS OF CONTROLS. |
| | PLEASE INDICATE WHICH ONE WILL BE DONE IF NOT EXISTING. |
| | SEE COMMENT NUMBER 7 AS THIS WILL BE RELEVANT TO THIS |
| | COMMENT. |
| | |
| | 7) NOTE: PLEASE INDICATE MINIMUM LIGHTING FOR EGRESS |
| | PATHS TO THE PUBLIC RIGHT OF WAY UNDER NORMAL AND |
| | EMERGENCY CONDITIONS. PLEASE SEE NFPA-101 |
| | 7.8.1.3,7.9.1.1,.1.2. |
| | IF LIGHTING IS EXISTING, PLEASE SHOW. PLEASE ALSO SEE |
| | MINIMUM CODE REQUIRED FOR STAIRS AND OTHER EXIT PATHS |
| | TO RIGHT OF WAY UNDER SOME SORT OF EMERGENCY BACK UP |
| | POWER MEETING NFPA-70 700.12 AND NFPA-101 SECTIONS. |
| | IF THERE IS EXISTING EMERGENCY EGRESS LIGHTING MEETING |
| | MINIMUM LEVELS UNDER NORMAL AND EMERGENCY (POWER |
| | OUTAGE) CONDITIONS, PLEASE SHOW. |
| | IF THERE IS NO EXISTING LIGHTING MEETING MINIMUMS FOR |
| | LIFE SAFETY PLEASE SHOW NEW AND CIRCUIT PER 700.12F. |
| | (SEE COMMENT #8) |
| | PLEASE ALSO SEE COMMENT #6 ABOVE WITH RESPECT TO |
| | LIGHTING CONTROLS FOR EXTERIOR LIGHTS. |
| | |
| | 8) NOTE: CIRCUITING OF EMERGENCY LIGHTING AND EXIT |
| | LIGHTS SHALL BE CIRCUITED PER 700.12F. PLANS CONTAIN A |
| | NOTE#2 WHICH MENTIONS TO WIRED TO UN-SWITCHED LEG OF |
| | D-20. |
| | THIS IS NOT PERMITTED AS D-20 ON REVISED PANEL D IS |
| | ACTUALLY IDENTIFIED AS A RECEPTACLE CIRCUIT. PLEASE SEE |
| | CODE SECTION GIVEN WHICH REQUIRES EMERGENCY AND EXIT |
| | LIGHTS TO BE CIRCUITED TO THE HOT SIDE OF THE LOCAL |
| | LIGHTING BRANCH CIRCUIT IN ANY ONE AREA. BASED ON THE |
| | PLANS MANY AREAS DO NOT MEET THE EXCEPTION IN 700.12F. |
| | PLEASE REVISE ALL CIRCUITING. |
| | |
| | 9) NOTE: IT IS CONFUSING HOW THE SUBMITTED EXISTING |
| | PANEL *D* INDICATE MOST OF THE EXISTING CIRCUITS AS |
| | *SPARE* THEN THE REVISED PANEL SCHEDULE *D* INDICATES |
| | MANY OF THOSE SAME CIRCUITS SHOWN AS * EXISTING SPARE* |
| | NOW AS *EXISTING RECEPTACLES* ETC. PLEASE SPECIFIC |
| | CIRCUITS REVISED PANEL D11-19 AND D8-20. HOW CAN THESE |
| | BE EXISTING CIRCUITS WHEN EXISTING PANEL SCHEDULE SHOWS |
| | ALL OF THESE SAME SPACES AS *SPARE* SPACES? |
| | 408.4 |
| | |
| | 10) NOTE: PLEASE SEE SHEET E-2 SECOND FLOOR DETAIL. |
| | THERE ARE SQUARE/RECTANGLE BOXES ON THE WEST WALL |
| | OUTSIDE AREAS 1-002 AND 1-202. WHAT ARE THESE? |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | 408.4,310.16, 240.4 ETC GIVEN AS GENERAL SECTIONS FOR |
| | WIRING, OVERCURRENT PROTECTION AND PANEL SCHEDULES AS |
| | THESE ARE NOT CLEAR AT THIS TIME. |
| | |
| | 11) NOTE: PLEASE VERIFY MAXIMUM OCP FOR CONDENSING |
| | UNITS. THIS CAN BE A PROVISO ITEM TO BE REVISED IF NOT |
| | KNOWN AT THIS TIME. |
| | |
| | 12) NOTE: PLEASE INDICATE HORN, STROBE LEVELS FOR FIRE |
| | ALARM DEVICES PER FBC 11-4.28.1,.2 AND.3. PLANS SHOULD |
| | ALSO INDICATE MINIMUM HEIGHTS AND LOCATIONS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |