Plan Review Details - Permit 09110178
Plan Review Stops For Permit 09110178
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-04-25 Cont ID  
Sent By jgomez Date 2011-04-25 Time 14:56 Rev Time 0.00
Received By jgomez Date 2011-04-25 Time 14:56 Sent To PC
Notes
2011-04-25 14:57:24SKYLIGHT PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2011-01-14 Cont ID  
Sent By jgomez Date 2011-01-14 Time 11:19 Rev Time 0.00
Received By jgomez Date 2011-01-14 Time 11:19 Sent To PC
Notes
2011-01-14 11:54:48SKYLIGHT SUBMITTAL:
  
 1- PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-02-23 Cont ID  
Sent By jgomez Date 2010-02-23 Time 16:57 Rev Time 0.00
Received By jgomez Date 2010-02-23 Time 13:16 Sent To  
Notes
2010-02-23 16:59:17BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- FILE FOR SINGLE HUNG WINDOW NOA 05-0810.04 WAS
 CLOSED BY MIAMI-DADE. PROVIDE CURRENT PRODUCT APPROVAL
 AND ARCHITECT TO REVIEW AND APPROVE IN WRITING PRIOR TO
 SUBMITTAL.
  
 2- NOA 07-0626.10 SUBMITTED FOR GLASS BLOCK IS FOR
 SMALL MISSILE IMPACT PROTECTION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR LARGE MISSILE IMPACT PROTECTION
 AND ARCHITECT TO REVIEW AND APPROVE IN WRITING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-01-14 Cont ID  
Sent By jgomez Date 2010-01-14 Time 14:04 Rev Time 0.00
Received By jgomez Date 2010-01-14 Time 14:15 Sent To  
Notes
2010-01-14 14:12:29RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 2- SHEET A-1: A) OPENING HEIGHT SHOWN ON THE ELEVATIONS
 FOR BEDROOM EGRESS WINDOWS DON'T CORRESPOND TO THE SIZE
 OF WINDOW SHOWN UNDERNEATH THE WINDOW. SH26 WINDOW
 DOESN'T HAVE 4'-3" HEIGHT. REVISE AS REQUIRED AND
 COORDINATE WITH ITEM #3(A) BELOW.
  
 B) SHOW EGRESS WINDOW FOR EXISTING BEDROOM. COORDINATE
 WITH ITEM #3(B) BELOW.
  
 3- SHEET A-2: A) SH24 WINDOWS SPECIFIED FOR THE
 BEDROOMS DON'T COMPLY WITH THE MINIMUM OPENING HEIGHT
 REQUIRED FOR EGRESS. NEED TO COMPLY WITH SEC. R310.1.2
 OF 2007 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED
 (REPEAT COMMENT, NOT ADDRESSED AT ALL).
  
 B) EXISTING BEDROOM THAT IS ADJACENT TO NEW BEDROOM
 ADDITION HAVE NOT MEANS OF EGRESS. NEED TO PROVIDE
 MEANS OF EGRESS AS REQUIRED BY SEC. R310 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 4- SHEET S-1: A) SPECIFY HOW LONG (HOW MUCH EMBEDMENT)
 IS REQUIRED FOR THE ANCHOR BOLTS AT THE BOTTOM PLATE OF
 ALUMINUM COLUMNS TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 B) COORDINATE CONNECTORS SPECIFIED ON ROOF FRAMING PLAN
 AND SECTIONS AA AND BB ON SHEET D-1. CONNECTORS
 SPECIFIED DON'T MATCH AND MAKE SURE CORRECT CONNECTORS
 ARE USED. EX: WOOD TO WOOD CONNECTORS AND WOOD TO
 MASONRY CONNECTORS (REPEAT COMMENT).
  
 C) CLARIFY CONNECTORS SPECIFIED ON THE NEW BEDROOM/TV
 ROOM ADDITION ROOF FRAMING PLAN AREA. A2 CONNECTOR IS
 SHOWN TO ATTACH WOOD TRUSS TO WOOD TRUSS GIRDER. REVISE
 AS REQUIRED (REPEAT COMMENT).
  
 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) WINDOW MULLIONS AS SHOWN ON ELEVATIONS (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 B) GLASS BLOCK AS SHOWN ON ELEVATIONS (REPEAT COMMENT.
 NOT ADDRESSED AT ALL).
  
 C) SLIDING GLASS DOORS (REPEAT COMMENT. NOT ADDRESSED
 AT ALL).
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 E) ROOF SHINGLES (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 F) FLAT ROOF (FOR NEW 1/2:12 PITCH ROOF). AND CLEARLY
 MARK ON THE PRODUCT APPROVAL THE FOLLOWING INFORMATION:
 * WHICH APPROVED ASSEMBLY IS GOING TO BE USED AND WHICH
 BASE SHEET FASTENING OPTION IS GOING TO BE USED. IF
 SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7,
 THEN RAS 117 CALCULATIONS ARE REQUIRED FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS. CHECK GENERAL
 LIMITATION #7 ON LAST PAGE OF PRODUCT APPROVAL TO SEE
 IF RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED.
 **NOTE: SELECTED ASSEMBLY LIMITED BY GENERAL LIMITATION
 #9 CAN'T BE USED IN THIS BUILDING BECAUSE IT DOESN'T
 MEET THE DESIGN PRESSURES (REPEAT COMMENT. NOT
 ADDRESSED AT ALL).
  
 G) SPECIFY WHICH UNDERLAYMENT FROM NOA 07-1025.10
 SUBMITTED IS GOING TO BE USED TO VERIFY COMPLIANCE WITH
 THE PRODUCT APPROVAL LIMITATIONS ON SHEET 4 OF 6.
 ***NOTE: TU PLUS IS DESIGNED FOR TILE UNDERLAYMENT NO
 SHINGLES (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 7- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2007 FLORIDA RESIDENTIAL CODE TO VERIFY THE 2500PSF
 SOIL BEARING CAPACITY REQUIRED BY THE ARCHITECT ON
 SHEET D-1 (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 8- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 9- REVISE THE ENERGY CALCULATIONS: A) NEED TO PROVIDE
 WINDOWS SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC
 FACTOR SHOWN ON ITEM #7 OR USE THE DEFAULT FACTORS
 SHOWN ON TABLE B2.1.1 OF CHAPTER 11 OF 2007 FLORIDA
 RESIDENTIAL CODE (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 B) PERSON DOING THE CALCULATIONS TO REVIEW PLANS FOR
 COOLING AND HEATING INFORMATION (ITEMS #11, #12 AND
 #13). INFORMATION TO MATCH PLANS (REPEAT COMMENT).
  
 C) IF TAKING THE CEILING FAN CREDIT, THEN NEED TO
 SPECIFY CEILING FAN SIZES TO VERIFY COMPLIANCE WITH
 TABLE C4.2.1.1 OF 2007 FLORIDA RESIDENTIAL CODE,
 CHAPTER 11.
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF THE FORM
 INCLUDING THE BUILDER'S NAME (REPEAT COMMENT).
  
 E) ROOF INFORMATION ON SHEET 2 OF 5 NEED TO BE REVISED.
 NEED TO ADD THE TYPE OF ROOF ON THE FLAT ROOF (REPEAT
 COMMENT, NOT ADDRESSED AT ALL). AND, THERE IS NOT
 BARREL TYPE ROOFING. SEE PLANS AND REVISE AS REQUIRED.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $860.30
 FOR UPDATED PERMIT VALUATION AND RADON FEES.
  
 11- NEED TO PROVIDE CARBON MONOXIDE ALARM AS REQUIRED
 BY SEC. R313.4 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 12- NEW ADDITION NEED TO HAVE EGRESS DOOR TO COMPLY
 WITH SEC. R311.4 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By jgomez Date 2009-11-30 Time 14:56 Rev Time 0.00
Received By jgomez Date 2009-11-30 Time 14:53 Sent To  
Notes
2009-11-30 15:23:34RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 2- SHEET A-1:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF THE 2009 REVISIONS
 TO THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NO "B". REVISE WIND EXPOSURE AT
 THE BOTTOM CENTER OF THE SHEET. ALSO, REVISE THE
 CALCULATED DESIGN PRESSURES OF THE DOORS AND WINDOWS
 SHOWN ON THE EXTERIOR ELEVATIONS.
  
 B) REVISE TITLE BLOCK. PROVIDE CORRECT NAME FOR THE
 OWNER OF THE RESIDENCE. THIS IS NOT THE HENLEY
 RESIDENCE. THIS APPLIES TO ALL SHEETS.
  
 3- SHEET A-2: SH24 WINDOWS SPECIFIED FOR THE BEDROOMS
 DON'T COMPLY WITH THE MINIMUM OPENING HEIGHT REQUIRED
 FOR EGRESS. NEED TO COMPLY WITH SEC. R310.1.2 OF 2007
 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED.
  
 4- SHEET S-1:
 A) FOUNDATION PLAN DOESN'T SPECIFY SIZE AND
 SPECIFICATION FOR FOOTING AT THE REAR PORCH.
  
 B) FOOTING DETAIL "E" DOESN'T MATCH FOUNDATION FLOOR
 PLAN. REVISE AS REQUIRED.
  
 C) PROVIDE COMPLETE INFORMATION FOR NEW ALUMINUM
 COLUMNS. SPECIFY COLUMN THICKNESS, CONNECTORS AT TOP
 AND BOTTOM AND FOOTING SPECIFICATIONS.
  
 D) COORDINATE CONNECTORS SPECIFIED ON ROOF FRAMING PLAN
 AND SECTIONS AA AND BB ON SHEET D-1. CONNECTORS
 SPECIFIED DON'T MATCH AND MAKE SURE CORRECT CONNECTORS
 ARE USED. EX: WOOD TO WOOD CONNECTORS AND WOOD TO
 MASONRY CONNECTORS.
  
 E) CLARIFY CONNECTORS SPECIFIED ON THE NEW BEDROOM/TV
 ROOM ADDITION ROOF FRAMING PLAN AREA. A2 CONNECTOR IS
 SHOWN TO ATTACH WOOD TRUSS TO WOOD TRUSS GIRDER. REVISE
 AS REQUIRED.
  
 F) RAKED GABLE END OVERHANG ABOVE NEW BEDROOM/TV ROOM
 DOESN'T MATCH RAKED GABLE END OVERHANG DETAIL SHOWN ON
 SHEET D-1. REVISE AS REQUIRED. REVISE OUTLOOKERS AND
 CONNECTORS TO MATCH.
  
 5- SHEET D-1: REVISE ROOF SHEATHING NAIL TYPE AND
 SPACING SPECIFICATIONS ON TYPICAL EXTERIOR WALL SECTION
 AND SHEATHING NAILING SCHEDULE TO COMPLY WITH SEC.
 R803.2.3.1 OF 2007 FLORIDA RESIDENTIAL CODE. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AND SPACING ON ROOF
 ZONE #3 IS 4"O.C. MIN.
  
 6- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) WINDOW MULLIONS AS SHOWN ON ELEVATIONS.
  
 B) GLASS BLOCK AS SHOWN ON ELEVATIONS.
  
 C) SLIDING GLASS DOORS.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ROOF SHINGLES.
  
 F) FLAT ROOF (FOR NEW 1/2:12 PITCH ROOF). AND CLEARLY
 MARK ON THE PRODUCT APPROVAL THE FOLLOWING INFORMATION:
 * WHICH APPROVED ASSEMBLY IS GOING TO BE USED AND WHICH
 BASE SHEET FASTENING OPTION IS GOING TO BE USED. IF
 SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7,
 THEN RAS 117 CALCULATIONS ARE REQUIRED FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS. CHECK GENERAL
 LIMITATION #7 ON LAST PAGE OF PRODUCT APPROVAL TO SEE
 IF RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED.
 **NOTE: SELECTED ASSEMBLY LIMITED BY GENERAL LIMITATION
 #9 CAN'T BE USED IN THIS BUILDING BECAUSE IT DOESN'T
 MEET THE DESIGN PRESSRUES.
  
 G) SPECIFY WHICH UNDERLAYMENT FROM NOA 07-1025.10
 SUBMITTED IS GOING TO BE USED TO VERIFY COMPLIANCE WITH
 THE PRODUCT APPROVAL LIMITATIONS ON SHEET 4 OF 6.
 ***NOTE: TU PLUS IS DESIGNED FOR TILE UNDERLAYMENT NO
 SHINGLES.
  
 7 ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2007 FLORIDA RESIDENTIAL CODE TO VERIFY THE 2500PSF
 SOIL BEARING CAPACITY REQUIRED BY THE ARCHITECT ON
 SHEET D-1.
  
 9- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 10- REVISE THE ENERGY CALCULATIONS:
 A) CALCULATIONS ARE NO DONE FOR WORST CASE SCENARIO
 (SEE ITEM #5) AND THEY DON'T MATCH BUILDING ACTUAL
 ORIENTATION EITHER. SEE PLANS FOR CORRECT BUILDING
 ORIENTATION OR DO CALCULATIONS PER WORST CASE SCENARIO.
  
 B) NEED TO PROVIDE WINDOWS SPECIFICATIONS SHOWING THE
 U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7 OR USE THE
 DEFAULT FACTORS SHOWN ON TABLE B2.1.1 OF CHAPTER 11 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 C) CLARIFY HOW OBTAINING THE R VALUE OF 0.3 ON THE SLAB
 SHOWN ON ITEM #8. R VALUE CAN ONLY BE GIVEN IF
 INSTALLING INSULATION.
  
 D) PERSON DOING THE CALCULATIONS TO REVIEW PLANS FOR
 COOLING AND HEATING INFORMATION (ITEMS #11, #12 AND
 #13). INFORMATION TO MATCH PLANS. PLANS SHOW AHU NO
 WINDOW UNITS.
  
 E) PROVIDE INFORMATION SHOWING HOW COMPLYING WITH THE
 CREDITS TAKEN ON ITEM #15. SEE SEC. B4.1.4 OF 2007
 FLORIDA RESIDENTIAL CODE FOR WHOLE HOUSE FAN
 REQUIREMENTS. ALSO, PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE PSTAT CREDIT.
  
 F) OWNER INFORMATION IS INCORRECT. ALSO, COMPLETE ALL
 THE INFORMATION ON TOP OF THE FORM INCLUDING THE
 BUILDER'S NAME.
  
 G) REVISE CLIMATE INFORMATION ON PAGE 2 OF 5. SEE SEC.
 N1100.4 OF 2007 FLORIDA RESIDENTIAL CODE. REVISE ALL
 THE INFORMATION AS REQUIRED.
  
 H) ROOF INFORMATION ON SHEET 2 OF 5 NEED TO BE REVISED
 ALSO. NEED TO ADD THE TYPE OF ROOF ON THE FLAT ROOF
 ALSO. SEE PLANS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $860.30
 FOR UPDATED PERMIT VALUATION AND RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-02-24 Cont ID  
Sent By btrobaug Date 2010-02-24 Time 09:41 Rev Time 0.00
Received By btrobaug Date 2010-02-24 Time 09:41 Sent To B
Notes
2010-02-24 09:41:41TO JULIO./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-19 Cont ID  
Sent By btrobaug Date 2010-01-19 Time 12:45 Rev Time 0.00
Received By btrobaug Date 2010-01-19 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-01 Cont ID  
Sent By btrobaug Date 2009-12-01 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2009-12-01 Time 12:25 Sent To  
Notes
2009-12-01 13:01:27THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} DEPENDING ON THE METER LOCATION, A DISCONNECT MAY BE
 REQUIRED PER 230.70, 225.32. INDICATE LOCATION ON PLAN
 PER 230.72(A)(1) INDICATE IF THE ELECTRICAL SERVICE
 SHOWN ON THE PLAN IS NEW OR EXISTING.
  
 2} INDICATE THE CONDUCTOR SIZES FROM THE METER TO THE
 PANEL ON THE RISER DIAGRAM.
  
 3} THE RECEPTACLES THAT ARE TO BE REMOVED IN THE
 EXISTING LIVING ROOM AND FAMILY ROOM MUST BE
 REINSTALLED AND COMPLY WITH 210.52(A) (1).
  
 4} R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN.
 LOCATE SAME ON PLANS.
  
 5} THE ELECTRICAL SPECS, NOTE #1 REFERENCES THE 2005
 NEC. THE 2008 NEC WAS ADOPTED 10/1/09, PLEASE CHANGE
 ALL NOTES TO REFLECT THIS CHANGE.
  
 THE OWNER NAME IN THE TITLE BLOCK DOES NOT CORRELATE
 WITH THE NAME ON THE APPLICATION, CORRECT SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2011-04-25 Cont ID  
Sent By jgomez Date 2011-04-25 Time 14:56 Rev Time 0.00
Received By jgomez Date 2011-04-21 Time 15:32 Sent To  
Notes
2011-04-21 15:32:30GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2011-01-14 Cont ID  
Sent By jgomez Date 2011-01-14 Time 11:18 Rev Time 0.00
Received By jgomez Date 2011-01-14 Time 11:18 Sent To  
Notes
2011-01-14 11:18:56SKYLIGHT PRODUCT APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-02-24 Cont ID  
Sent By jgomez Date 2010-02-24 Time 14:59 Rev Time 0.00
Received By jgomez Date 2010-02-24 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-02-09 Cont ID  
Sent By lmartine Date 2010-02-09 Time 17:00 Rev Time 0.00
Received By lmartine Date 2010-02-09 Time 16:59 Sent To  
Notes
2010-02-09 17:00:29IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2010-01-12 Time 16:28 Sent To  
Notes
2010-01-12 16:38:33R 2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-12-02 Time 16:27 Rev Time 0.00
Received By btrobaug Date 2009-11-05 Time 09:56 Sent To  
Notes
2009-11-16 10:21:25R--2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2010-02-24 Cont ID  
Sent By jgomez Date 2010-02-24 Time 15:09 Rev Time 0.00
Received By jgomez Date 2010-02-24 Time 15:08 Sent To  
Notes
2010-02-24 15:09:23NO FEES DUE. PLANS ARE STAMPED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2010-01-14 Cont ID  
Sent By jgomez Date 2010-01-14 Time 10:03 Rev Time 0.00
Received By jgomez Date 2010-01-14 Time 10:03 Sent To  
Notes
2010-01-14 10:05:11BRING PLANS TO PALM BEACH COUNTY ( 2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. (REPEAT
 COMMENT).

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By jgomez Date 2009-11-30 Time 14:53 Rev Time 0.00
Received By jgomez Date 2009-11-30 Time 14:53 Sent To  
Notes
2009-11-30 14:56:20BRING PLANS TO PALM BEACH COUNTY ( 2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-02-08 Cont ID  
Sent By rkussner Date 2010-02-08 Time 12:06 Rev Time 0.00
Received By rkussner Date 2010-02-08 Time 12:06 Sent To  
Notes
2010-02-08 12:10:53***LANDSCAPE REVIEW PASSED***
  
 PLEASE SEE PERMIT #09-120385 FOR LANDSCAPE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-11-17 Cont ID  
Sent By rkussner Date 2009-11-17 Time 14:46 Rev Time 0.00
Received By rkussner Date 2009-11-17 Time 14:46 Sent To  
Notes
2009-11-17 15:07:18***LANDSCAPE REVIEW FAILED**(*
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-441 (C)(2), BECAUSE THE
 RENOVATIONS EXCEED 50 PERCENT OF THE VALUE OF THE
 STRUCTURE, THE ENTIRE LANDSCAPE SHALL BE BROUGHT UP TO
 MINIMUM STANDARDS. PLEASE SUBMIT TWO (2) COPIES OF A
 COMPLETE LANDSCAPE PLAN AND THE TABULATION NECESSARY
 FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 2. SUBMIT A LANDSCAPE APPLICATION AND A COST ESTIMATE
 THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS
 AND LABOR, BROKEN DOWN INTO UNIT COST.
  
 3. PURSUANT TO SECTION 94-448 (D)(2), THE LANDSCAPE
 PLAN SHALL CONTAIN THE ITEMS LISTED IN THIS SECTION.
  
 4. ALL EXISTING PLANT MATERIAL TO REMAIN SHALL BE
 IDENTIFIED ON THE LANDSCAPE PLAN.
  
 5. PURSUANT TO SECTION 94-445 (4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. AN IRRIGATION
 PERMIT IS REQUIRED FOR A NEW SYSTEM OR MODIFICATIONS TO
 AN EXISTING SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-02-24 Cont ID  
Sent By hmoser Date 2010-02-24 Time 10:38 Rev Time 0.00
Received By hmoser Date 2010-02-24 Time 10:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-27 Cont ID  
Sent By hmoser Date 2010-01-27 Time 08:59 Rev Time 0.00
Received By hmoser Date 2010-01-27 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By hmoser Date 2009-12-02 Time 09:58 Rev Time 0.00
Received By hmoser Date 2009-12-02 Time 09:48 Sent To  
Notes
2009-12-02 10:00:18NO MECHANICAL PLANS IN PACKAGE .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-02-24 Cont ID  
Sent By kstevens Date 2010-02-24 Time 08:34 Rev Time 0.00
Received By kstevens Date 2010-02-24 Time 08:34 Sent To  
Notes
2010-02-24 08:35:25RESTAMP OF APPROVED PLANS, NEW SHEET.

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-20 Cont ID  
Sent By kstevens Date 2010-01-20 Time 15:53 Rev Time 0.00
Received By kstevens Date 2010-01-20 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By kstevens Date 2009-11-30 Time 08:48 Rev Time 0.00
Received By kstevens Date 2009-11-30 Time 08:48 Sent To  
Notes
2009-11-30 09:02:39DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT S-1 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS TWO
 NEW BATHROOMS AND A SINK IN THE T.V. ROOM WHEREAS THE
 RISER DIAGRAM ONLY SHOWS ONE BATHROOM AND DOES NOT SHOW
 THE SINK IN THE T.V. ROOM. SECTION 106.3.5.4(9).
  
 2. "INFORMATIONAL" THE SINK IN THE T.V. ROOM SHALL NOT
 DRAIN THROUGH THE WET VENT FOR THE BATHROOM GROUP.
 SECTION 909.1. ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE HORIZONTAL WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 3. "INFORMATIONAL" IN THE INSTALLATION OR REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5. WHEN THE EXISTING KITCHEN
 AND EXISTING BATHROOM ARE BEING REMOVED, ABANDONED
 SANITARY LINES SHALL BE CAPPED OFF WITHIN 2 FEET OF
 ACTIVE LINES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2010-02-12 Cont ID  
Sent By astelly Date 2010-02-12 Time 16:54 Rev Time 0.00
Received By astelly Date 2010-02-12 Time 16:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-01-30 Cont ID  
Sent By astelly Date 2010-01-30 Time 10:17 Rev Time 0.00
Received By astelly Date 2010-01-30 Time 10:17 Sent To  
Notes
2010-01-30 10:19:26AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 REPEAT COMMENT: PLEASE PROVIDE A SITE PLAN SHOWING
 LOCATION OF PROPOSED ADDITION.
 SETBACKS FROM PROPERTY LINES MUST BE INCLUDED

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By astelly Date 2009-11-24 Time 17:14 Rev Time 0.00
Received By astelly Date 2009-11-24 Time 17:14 Sent To E
Notes
2009-11-24 17:17:10AMY F. STELLY
 PLANNING AND ZONNING
 561-822-1442
  
 PLEASE PROVIDE A SITE PLAN AND SURVEY SHOWING SCOPE OF
 PROPOSED WORK.