Plan Review Details - Permit 09110104
Plan Review Stops For Permit 09110104
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2011-01-31 Cont ID  
Sent By jwitmer Date 2011-01-31 Time 12:22 Rev Time 0.77
Received By jwitmer Date 2011-01-31 Time 12:22 Sent To  
Notes
2011-01-31 12:27:27BUILDING PLAN REVIEW
 PERMIT: 09110104
 ADD: 1320 N TAMARIND AVE
 CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION
 CORP. CGC1508383/ CCC1328731
 TEL: (561)509-4000
 DEC.27/2010
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLANS RESUBMITTED WITH WINDOW WITHIN 10 FEET OF THE
 EXTERIOR STAIR NEED TO BE 1 HOUR FIRE RATED . PRODUCT
 APPROVAL FOR THE FIRE RATING WAS SUBMITTED BUT NO
 PRODUCT REPORTS WERE SUBMITTED FOR THE REQUIRED STORM
 SHUTTER. FIRE RATED GLASS WINDOWS DO NOT MEET THE LARGE
 MISSILE TESTING REQUIREMING THE WINDOW TO BE STORM
 SHUTTERED IN THE CASE OF A HIGH WIND EVENT. PROVIDE
 BEFORE INSPECTION
 2007/ 2009 FBC-B 1023.6 EXTERIOR RAMPS AND STAIRWAY
 PROTECTION. EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE
 SEPARATED FROM THE INTERIOR OF THE BUILDING AS REQUIRED
 IN SECTION 1020.1. OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES.
 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE
 OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 715.
 2007/2009 FBC-B TABLE 715.4.
  
 2)THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA
 07-822.10:
 2A) DOES NOT HAVE ANY OF THE SUB-SYSTEMS HIGHLIGHTED AS
 TO WHICH SYSTEM WILL BE INSTALLED.
 2B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL
 BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS
 AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 &
 3.
 RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A
 FLORIDA P.E. OR REGISTERED ARCHITECT.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-12-27 Cont ID  
Sent By jwitmer Date 2010-12-27 Time 11:27 Rev Time 0.55
Received By jwitmer Date 2010-12-27 Time 11:27 Sent To  
Notes
2010-12-27 11:28:11BUILDING PLAN REVIEW
 PERMIT: 09110104
 ADD: 1320 N TAMARIND AVE
 CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION
 CORP. CGC1508383/ CCC1328731
 TEL: (561)509-4000
 DEC.27/2010
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLANS RESUBMITTED WITH NOTATIONS FOR WINDOW TYPE D
 TO BE FIRE RATED . PRODUCT APPROVAL FOR THE FIRE RATING
 WAS SUBMITTED BUT NO PRODUCT REPORTS WERE SUBMITTED FOR
 THE REQUIRED STORM SHUTTER. FIRE RATED GLASS WINDOWS DO
 NOT MEET THE LARGE MISSILE TESTING REQUIREMING THE
 WINDOW TO BE STORM SHUTTERED IN THE CASE OF A HIGH WIND
 EVENT. PROVIDE BEFORE INSPECTION
  
 2)THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA
 07-822.10:
 2A) DOES NOT HAVE ANY OF TTTHE SUB-SYSTEMS HIGHLIGHTED
 AS TO WHICH SYSTEM WILL BE INSTALLED.
 2B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL
 BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS
 AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 &
 3.
 RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A
 FLORIDA P.E. OR REGISTERED ARCHITECT.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-11-01 Cont ID  
Sent By jwitmer Date 2010-11-01 Time 11:37 Rev Time 1.55
Received By jwitmer Date 2010-11-01 Time 11:37 Sent To  
Notes
2010-11-01 11:50:59BUILDING PLAN REVIEW
 PERMIT: 09110104
 ADD: 1320 N TAMARIND AVE
 CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION
 CORP. CGC1508383/ CCC1328731
 TEL: (561)509-4000
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLANS RESUBMITTED WITH NOTATIONS FOR WINDOW TYPE D
 TO BE FIRE RATED . PRODUCT APPROVAL FOR THE FIRE RATING
 WAS SUBMITTED BUT NO PRODUCT REPORTS WERE SUBMITTED FOR
 THE REQUIRED STORM SHUTTER. FIRE RATED GLASS WINDOWS DO
 NOT MEET THE LARGE MISSILE TESTING REQUIREMING THE
 WINDOW TO BE STORM SHUTTERED IN THE CASE OF A HIGH WIND
 EVENT. PROVIDE BEFORE INSPECTION
  
 2)THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA
 07-822.10:
 2A) DOES NOT HAVE ANY OF TTTHE SUB-SYSTEMS HIGHLIGHTED
 AS TO WHICH SYSTEM WILL BE INSTALLED.
 2B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL
 BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS
 AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 &
 3.
 RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A
 FLORIDA P.E. OR REGISTERED ARCHITECT.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-03-15 Cont ID  
Sent By jwitmer Date 2010-03-15 Time 13:38 Rev Time 3.33
Received By jwitmer Date 2010-03-15 Time 13:12 Sent To  
Notes
2010-03-15 17:07:21BUILDING PLAN REVIEW
 PERMIT: 09110104
 ADD: 1320 N TAMARIND AVE
 CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION
 CORP
 TEL: (561)509-4000
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 5 DETAIL A INDICATES A ROOF FRAMING SECTION
 WITH NEW 2X8 RAFTERS @ 12 INCHES ON CENTER, PLANS FAIL
 TO PROVIDE THE SPECIES OF WOOD AND GRADE OF WOOD,
 PLEASE PROVIDE
 FOR COMPLIANCE WITH TABLE 2308.10.3.1.
  
 2) SHEET 5 DETAIL A ALSO INDICATES A WOOD BEAM (2) 2X8S
 THE PLANS ARE NOT CLEAR IF A SINGLE 2X8 IS BEING ADDED
 TO AN EXISTING 2X8 BEAM OR IF THE (2) 2X8S MAKE UP THE
 TOTAL BEAM.
 106.1.2 ADDITIONAL INFORMATION REQUIRED. IT APPEARS
 THAT AGAIN NOT ENOUGH INFORMATION HAS BEEN PROVIDED.
 SPECIES OF WOOD, GRADE OF WOOD, FB VALUE, AND THE SPAN
 ON THE OTHER SIDE OF THE NEW WOOD BEAM, IT APPEARS
 THERE ARE EXISTING 2X6S @ 24 INCHES ON CENTER. IT
 APPEARS THIS BEAM IS LIGHT. PLEASE PROVIDE THE BEAM
 CALCULATIONS FOR A SIMPLE SPAN CONFIGURATION.WOOD
 STRUCTURAL DESIGN DATA 1992 REVISIONS WOOD BEAMS SAFE
 LOAD TABLES SPANS OF 15'-0". 2308.4.2 STRUCTURAL
 ELEMENTS OR NOT DESSCRIBED WITHIN.
  
 3) SHEET 5 DETAIL A INDICATE A BUILT UP WOOD BEAM BUT
 DO NOT PROVIDE AS TO WHAT CONNECTIONS, UPLIFT, LATERAL
 AND GRAVITY LOADS WILL BE ACTING ON THIS BEAM NOR THE
 TIE DOWN SYSTEM,
 MWFRS MAIN WIND FORCE RESISTING SYSTEM. WHAT TRANSFERS
 THE GRAVITY LOADS INTO TTHE STRUCTURE AND TIE TO THE
 FOUNDATION BELOW. FBC-B 1609.1.1.
  
 4A) SHEET 1 IS NOT CLEAR AS TO THE HORIZONTAL OCCUPANCY
 SEPERATION THAT IS REQUIRED BETWEEN THE
 BUSINESSOCCUPANCY AND R2 ON THE SECOND FLOOR. TWO HOUR
 HORIZONTAL OCCUPNCY SEPERATION WILL BE REQUIRED PLEASE
 REVIEW SECTION FBC-B 711.3 FIRE- RESISTANCE RATING. THE
 FIRE-RESISTANCE RATING OF FLOOR AND ROOF ASSEMBLIES
 SHALL NOT BE LESS THAN THAT REQUIRED BY THE BUILDING
 TYPE OF CONSTRUCTION. WHERE THE FLOOR ASSEMBLY
 SEPARATES MIXED OCCUPANCIES, THE ASSEMBLY SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED
 BY SECTION 508.3.3 BASED ON THE OCCUPANCIES BEING
 SEPARATED. TABLE 508.3.3 BUSINESS/ R2, UNSPRINKLERED:
 2HOURS. PLEASE PROVIDE UL OR OTHER LISTED ASSEMBLY.
  
 4B) THE TENANT SEPERATION WALL THAT SEPERATES TENANT 1
 AND TENANT 2 APPEARS TO BE A BEARING WALL, 2ND FLOOR
 FLOOR JOIST, AND WILL ALSO BE REQUIRED TO BE A 2 HOUR
 WALL SINCE IT SUPPORTS THE 2 HR RATED FLOOR CEILING
 ASSEMBLY. PLEASE PROVIDE A UL LISTED ASSEMBLY OR
 EQUIVALENT.
  
 5) PLEASE ALSO REVIEW REQUIRED SEPERATION FOR EACH OF
 THE R2 TENANCIES. 711.3 FIRE-RESISTANCE RATING. FLOOR
 ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDING OR SLEEPING UNITS IN OCCUPANCIES IN GROUP R-1,
 HOTEL OCCUPANCIES, R-2 AND I-1; AND FLOOR ASSEMBLIES
 SEPARATING INDIVIDUAL TENANT SPACES IN THE SAME
 BUILDING IN ALL OTHER OCCUPANCIES SHALL BE A MINIMUM OF
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 6) PLEASE REVIEW DRAFT STOPPING REQUIREMENTS:BUILDING
 PROVISO: IF THE CONTRACTORS DO NOT REMOVE CEILING
 ASSEMBLIES AND OR FLOOR /CEILING ASSEMBLIES THEN THE
 DRAFT STOPPING REQUIREMENTS WILL NOT BE REQUIRED.
 5-11-2010 J. W.
 717.3.2 GROUPS R-1, R-2, R-3 AND R-4. DRAFTSTOPPING
 SHALL BE PROVIDED IN FLOOR/CEILING SPACES IN GROUP R-1
 BUILDINGS, IN GROUP R-2 BUILDINGS WITH THREE OR MORE
 DWELLING UNITS, IN GROUP R-3 BUILDINGS WITH TWO
 DWELLING UNITS AND IN GROUP R-4 BUILDINGS.
 DRAFTSTOPPING SHALL BE LOCATED ABOVE AND IN LINE WITH
 THE DWELLING UNIT AND SLEEPING UNIT SEPARATIONS.
  
 717.4 DRAFTSTOPPING IN ATTICS. IN COMBUSTIBLE
 CONSTRUCTION, DRAFTSTOPPING SHALL BE INSTALLED TO
 SUBDIVIDE ATTIC SPACES AND CONCEALED ROOF SPACES IN THE
 LOCATIONS PRESCRIBED IN SECTIONS 717.4.2 AND 717.4.3.
 VENTILATION OF CONCEALED ROOF SPACES SHALL BE
 MAINTAINED IN ACCORDANCE WITH SECTION 1203.2.
  
 717.4.2 GROUPS R-1 AND R-2. DRAFTSTOPPING SHALL BE
 PROVIDED IN ATTICS, MANSARDS, OVERHANGS OR OTHER
 CONCEALED ROOF SPACES OF GROUP R-2 BUILDINGS WITH THREE
 OR MORE DWELLING UNITS AND IN ALL GROUP R-1 BUILDINGS.
 DRAFTSTOPPING SHALL BE INSTALLED ABOVE, AND IN LINE
 WITH, SLEEPING UNIT AND DWELLING UNIT SEPARATION WALLS
 THAT DO NOT EXTEND TO THE UNDERSIDE OF THE ROOF
 SHEATHING ABOVE.
 EXCEPTIONS:
 1. WHERE CORRIDOR WALLS PROVIDE A SLEEPING UNIT OR
 DWELLING UNIT SEPARATION, DRAFTSTOPPING SHALL ONLY BE
 REQUIRED ABOVE ONE OF THE CORRIDOR WALLS.
 2. DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1.
 3. IN OCCUPANCIES IN GROUP R-2 THAT DO NOT EXCEED FOUR
 STORIES IN HEIGHT, THE ATTIC SPACE SHALL BE SUBDIVIDED
 BY DRAFTSTOPS INTO AREAS NOT EXCEEDING 3,000 SQUARE
 FEET (279 M2) OR ABOVE EVERY TWO DWELLING UNITS,
 WHICHEVER IS SMALLER.
 4. DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.2, PROVIDED THAT
 AUTOMATIC SPRINKLERS ARE ALSO INSTALLED IN THE
 COMBUSTIBLE CONCEALED SPACES.
  
 7A) SUBMITTED IS A PRODUCT APPROVAL NOA 07-0214.05 FOR
 SERIES 100 STORM SAFE SINGLE HUNG WINDOW, THE PLANS DO
 NOT INDICATE THE 2ND FLOOR WINDOWS ARE TO BE REPLACED
 ONLY THE FIRSST FLOOR WINDOWS. IF THTE SECOND FLOOR
 WINDOWS ARE TO BE REPLACED PLEASE PROVIDE BY EITHER
 CIRLING THE UNIT TO BE INSTALLED, WINDOW HEIGHT AND
 WIDTH ON THE PRODUCT APPROVAL OR PROVIDE INFORMATION ON
 THE PLANS. PROVIDE THE OVERALL WINDOW DIMENSIONS TO BE
 INSTALLED, THE CLEAR VENT SIZE MUST BE 5.7 SQ FT.
  
 7B) THE SUBMITTED NOA 07-0214.05 HAS BEEN PREVIOUSLY
 STAMPED WITH A DIFFERENT PERMIT NUMBER PLEASE PROVIDE
 NEW SETS. RECORD RETENTION WILL NOT BE ABLE TO COPY AND
 BE LEGIBLE FOR RECORD RETENSION.
  
 8) THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA
 07-822.10:
 8A) DOES NOT HAVE ANY OF TTTHE SUB-SYSTEMS HIGHLIGHTED
 AS TO WHICH SYSTEM WILL BE INSTALLED.
 8B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL
 BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS
 AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 &
 3.
 RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A
 FLORIDA P.E. OR REGISTERED ARCHITECT.
 8C) PLEASE NOTE SHEET ROOFING DETAIL INDICATES THE NEW
 ROOF DECKING TO BE 15/32 CDX PLYWOOD WHERE AS THE
 SUBMITTED NOA REQUIRES A MINIMUM OF 19/32 CDX PLYWOOD.
  
 9) SHEET# 4 SOUTH ELEVATION PLEASE REVIEW 1023.6
 EXCEPTION# 1 3/4 HR OPENING PROTECTION FOR WINDOWS
 LOCATED WITHIN 10'-0" OF EXTERIOR STAIRS.
  
 10) EXISTING BUILDING CODE 705.5.1 CORRIDOR DOORS.
 CORRIDOR DOORS IN THE WORK AREA SHALL NOT BE
 CONSTRUCTED OF HOLLOW CORE WOOD AND SHALL NOT CONTAIN
 LOUVERS. ALL DWELLING UNIT OR SLEEPING UNIT CORRIDOR
 DOORS IN WORK AREAS IN BUILDINGS OF GROUPS R-1, R-2,
 AND I-1 SHALL BE AT LEAST 13/8-INCH (35 MM) SOLID CORE
 WOOD OR APPROVED EQUIVALENT AND SHALL NOT HAVE ANY
 GLASS PANELS, OTHER THAN APPROVED WIRED GLASS OR OTHER
 APPROVED GLAZING MATERIAL IN METAL FRAMES. ALL DWELLING
 UNIT OR SLEEPING UNIT CORRIDOR DOORS IN WORK AREAS IN
 BUILDINGS OF GROUPS R-1, R-2, AND I-1 SHALL BE EQUIPPED
 WITH APPROVED DOOR CLOSERS. ALL REPLACEMENT DOORS SHALL
 BE 13/4-INCH (45 MM) SOLID BONDED WOOD CORE OR APPROVED
 EQUIVALENT, UNLESS THE EXISTING FRAME WILL ACCOMMODATE
 ONLY A 13/8-INCH (35 MM) DOOR.
  
 11) THE PLANS ARE NOT CLEAR AS TO WHAT EXTENT THE 2ND
 FLOOR IS TO BE REMODELED, WILL THE DRRYWALL BE REMOVED
 FROM ALL WALLS, PLANS CURRENTLY DO NOT INDICATE ANY
 TYPE OF WALL OR CEILING INSULATION?
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-10 Cont ID  
Sent By tmoore Date 2009-11-10 Time 14:42 Rev Time 0.00
Received By tmoore Date 2009-11-10 Time 14:37 Sent To I
Notes
2009-11-10 14:42:36UPSTAIRS APARTMENT HAD LOCALIZED BUT SEVERE FIRE
 DAMAGE. SMOKE DAMAGE TO THE REST OF THE SECOND FLOOR.
 FIRE HAS DAMAGED THE ROOF FRAMING MEMBERS, ROOF
 SHEATHING, AND SOME INTERIOR FRAMING. ENGINEERED
 REPAIRS WILL BE REQUIRED.
 VALUE MUST INCREASE AS WELL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-02-03 Cont ID  
Sent By jleahy Date 2011-02-03 Time 08:16 Rev Time 0.00
Received By jleahy Date 2011-02-03 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-10-15 Cont ID  
Sent By jleahy Date 2010-10-15 Time 09:25 Rev Time 0.00
Received By jleahy Date 2010-10-15 Time 09:25 Sent To  
Notes
2010-10-15 09:26:14SEE COMMENTS FROM FIRST REVIEW JL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By jleahy Date 2010-03-24 Time 08:49 Rev Time 0.00
Received By jleahy Date 2010-03-24 Time 08:49 Sent To  
Notes
2010-03-24 08:52:171 NEED LIGHTING DENSITY CALCULATION BEFORE FINAL
 INSPECTION.
  
 2 NEED TO SHOW LIGHTING CONTROL ON DRAWING FOR FIRST
 FLOOR OCCUPANCIES BEFORE FINAL INSPECTION.
  
 JAKE

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2011-06-23 Cont ID  
Sent By ddaniels Date 2011-06-23 Time 12:08 Rev Time 0.00
Received By ddaniels Date 2011-06-23 Time 12:08 Sent To  
Notes
2011-06-23 12:11:4006/23/11 PLANS REVIEWED BY FIRE **APPROVED**
  
 1. PLANS ORIGINALLY ADDRESSED ROOMING HOUSE NOW
 ADDRESSED AS APARTMENTS.
  
 DERRICK DANIELS, INTERIM BATTALION CHIEF
 FIRE PLANS REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2011-02-01 Cont ID  
Sent By ddaniels Date 2011-02-01 Time 14:51 Rev Time 0.00
Received By ddaniels Date 2011-02-01 Time 14:40 Sent To  
Notes
2011-02-01 14:55:312/1/11 PLANS REVIEWED BY FIRE
 NFPA 101 CHAPTER 26, LODGING OR ROOMING HOUSES,
 SPECIFICALL 26.33.6.1 "ALL LODGING OR ROOMING HOUSES,
 OTHER THAN THOSE MEETING 26.3.6.2 SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 26.3.6.3.
  
 PERMIT IS DENIED PENDING THIS PROVISO
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-12-01 Cont ID  
Sent By mcarsill Date 2010-12-01 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2010-12-01 Time 13:01 Sent To  
Notes
2010-12-01 13:58:511320 NORTH TAMARIND AVENUE
 REPAIR FIRE DAMAGE IN FIRST FLOOR AND SECOND FLOOR
 PERMIT NUMBER 09110104
  
  
 1. THIS OFFICE HAS REVIEWED THE REVISED PLANS AND HAVE
 ACKNOWLEDGED THE REVISIONS TO THE DRAWINGS REGARDING
 THE PREVIOUS FIRE CODE COMMENTS.
  
 2. THE UPSTAIRS PORTION OF THE BUILDING SHALL COMPLY
 WITH NFPA 101 CHAPTER 26, LODGING OR ROOMING HOUSES.
 SINCE THE FIRE IT IS BELIEVED THAT THE ROOMING HOUSE
 PORTION HAS BEEN CLOSED. ACCORDING TO THE PREVAILING
 FIRE CODE, THE REQUIREMENTS OF CHAPTER 26 "SHALL APPLY
 TO NEW BUILDINGS OR MODIFIED BUILDINGS ACCORDING TO THE
 PROVISIONS OF 1.3.1 OF THIS CODE". SECTION 1.3.1
 INDICATES " THE CODE SHALL APPLY TO BOTH NEW
 CONSTRUCTION AND EXISTING BUILDINGS AND EXISTING
 STRUCTURES.
  
 3. NFPA 101 CHAPTER 26, LODGING OR ROOMING HOUSES
 SPECIFICALLY 26.3.6.1 "ALL NEW LODGING OR ROOMING
 HOUSES, OTHER THAN THOSE MEETING 26.3.6.2 SHALL BE
 PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 26.3.6.3. SINCE THE ROOMING
 HOUSE WAS CLOSED FOR A LONG PERIOD OF TIME, THAT
 PORTION IS BEING CONSIDERED NEW. IT DOES NOT APPEAR
 THAT THE BUILDING MEETS THE EXCEPTION FOR NO SPRINKLERS
 AND THEREFORE THE BUILDING WILL NEED TO BE FIRE
 SPRINKLER PROTECTED WITH A MINIMUM OF AT LEAST A 13R
 FIRE SPRINKLER SYSTEM. SEPARATE PLANS AND PERMITS ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
  
 THE PERMIT IS APPROVED PROVISO WITH THE UNDERSTANDING
 THAT THE ROOMING HOUSE PORTION BE FIRE SPRINKLER
 PROTECTED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-24 Time   Rev Time 0.00
Received By mawillia Date 2010-03-24 Time   Sent To  
Notes
2010-03-25 00:11:21*****DENIED*****
  
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 02. ON SHEET 4, POST THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS NORTH
 TAMARIND AVENUE. AS PER WEST PALM BEACH CODE, BUILDING
 ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND
 NO LESS THAN 1" IN WIDTH/STROKE. THE BUSINESS SUITE
 NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH/STROKE.
  
 03. NO FIRE EXTINGUISHER SHOWN IN THE # 1 BUSINESS
 SUITE.
  
 04. NO DOOR DESIGNATION/NUMBER FOR THE DOOR
 ENTERING/EXITING THE SECOND FLOOR LIVING ROOM.
 *******************************************************
 *******************************************************
 *******************************************************
 THE REFERENCE FOR THE FOLLOWING COMMENTS ARE BASED ON
 CHAPTER 26 (LODGING OR ROOMING HOUSES) OF NFPA 101 -
 LIFE SAFETY CODE - 2006 EDITION
 *******************************************************
 *******************************************************
 *******************************************************
 05. SLEEPING ROOM DOORS WHICH WHICH OPEN INTO EXIT
 ACCESS CORRIDOR SHALL BE FIRE RATED, SELF CLOSING, AND
 LATCHES UPON RELEASE. AMEND TO REFLECT AS THUS IN THE
 DOOR SCHEDULE.
  
 06. ON SHEET 2, SECOND FLOOR, NO MANUAL FIRE ALARM PULL
 STATIONS SHOWN IN THE NATURAL EXIT ACCESS PATH NEAR
 EACH REQUIRED EXIT FROM AN AREA.
  
 07. ON SHEET 2, SECOND FLOOR, NO VISIBLE SIGNALS FOR
 THE HEARING IMPAIRED. THESE DEVICES SHALL NOT BE
 REQUIRED WHERE THE PROPRIETOR (OR PROPRIETOR'S AGENT)
 RESIDES IN THE BUILDING AND THERE ARE FIVE OR FEWER
 ROOMS FOR RENT.
  
 08. EXISTING STAIRS SHALL BE PERMITTED TO REMAIN IN
 USE, PROVIDED THAT THEY MEET THE REQUIREMENTS FOR
 EXISTING STAIRS SHOWN IN TABLE 7.2.2.2.1.19(B) OF NFPA
 101 - LIFE SAFETY CODE - 2006 EDITION.
  
 09. STAIRS SHALL HAVE GUARDRAILS ON BOTH SIDES.
  
 10. WHAT IS THE DISTANCE AND/OR FIRE RATING OPENING
 PROTECTION FOR THE WINDOWS, AS SHOWN ON SHEET #4,
 LOCATED NEAR THE EXTERIOR STAIRS ON THE SOUTH
 ELEVATION.
  
 11. BASED ON INFORMATION GAINED FROM PLANNING AND
 ZONING DEPARTMENT, A FIRE SPRINKLER SYSTEM MAY BE
 REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATINGWHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
 OR
 BATTALION CHIEF MIKE CARSILLO
 FIRE MARSHAL - FIRE PREVENTION BUREAU
 561-804-4709

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2011-01-28 Cont ID  
Sent By fmittner Date 2011-01-28 Time 11:42 Rev Time 0.00
Received By fmittner Date 2011-01-28 Time 11:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2010-12-20 Cont ID  
Sent By fmittner Date 2010-12-20 Time 11:48 Rev Time 0.00
Received By fmittner Date 2010-12-20 Time 11:48 Sent To  
Notes
2010-12-20 11:51:27INTERIOR CHANGES RESULTED IN EXTERIOR CHANGE OF WINDOW
 OPENINGS. FHM FAILED. SPOKE TO BOB KOAPOLLA 12-20-10 -
 NEED TO KEEP ORIGINAL WINDOW OPENINGS, SINCE PROJECT
 HAS CHANGED BACK TO DUPLEX MIKE CARSILLO X4709 OK W
 ADDING WINDOW BACK IN BY STAIR. WAITING ON REVISIONS TO
 EXTERIOR BACK TO ORIGINAL OPENING SIZES. PUT PLANS BACK
 IN C-23 12-20-10.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-11-04 Cont ID  
Sent By mmiller Date 2009-11-04 Time 13:45 Rev Time 0.00
Received By mmiller Date 2009-11-04 Time 13:45 Sent To  
Notes
2009-11-04 13:45:37OK PER JILLIAN PAPA MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-01-21 Cont ID  
Sent By lmartine Date 2011-01-19 Time 14:21 Rev Time 0.00
Received By lmartine Date 2011-01-19 Time 14:45 Sent To  
Notes
2011-01-19 14:46:41C4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-12-08 Cont ID  
Sent By lmartine Date 2010-12-08 Time 16:38 Rev Time 0.00
Received By lmartine Date 2010-12-08 Time 16:38 Sent To  
Notes
2010-12-08 16:39:16C--23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-10-14 Cont ID  
Sent By lmartine Date 2010-10-14 Time 15:32 Rev Time 0.00
Received By lmartine Date 2010-10-14 Time 15:32 Sent To  
Notes
2010-10-14 15:49:04C--23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-28 Cont ID  
Sent By lmartine Date 2010-03-24 Time 12:47 Rev Time 0.00
Received By lmartine Date 2010-03-03 Time 10:47 Sent To  
Notes
2010-03-03 11:01:52TO C 27

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-01-31 Cont ID  
Sent By lwagner Date 2011-01-31 Time 11:59 Rev Time 0.00
Received By lwagner Date 2011-01-31 Time 11:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-12-22 Cont ID  
Sent By lwagner Date 2010-12-22 Time 14:02 Rev Time 0.00
Received By lwagner Date 2010-12-22 Time 13:32 Sent To  
Notes
2010-12-22 14:00:59FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. SANITARY RISER DIAGRAM SHOWS WATER CLOSETS ON THE
 2ND FLOOR WITH HORIZONTAL DRY VENTS.
 PLUMBING 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES (152 MM)
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED.
  
 2. SANITARY RISER DIAGRAM SHOWS A KITCHEN SINK WET
 VENTING A TUB.
 PLUMBING 909.1 HORIZONTAL WET VENT PERMITTED. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 3. BY MOVING THE LOCATION OF THE 2ND FLOOR BATHROOMS, A
 WATER DISTRIBUTION DRAWING AND WATER HEATER DETAIL WILL
 BE REQUIRED.
 FBC 106.3.5.1.3 (3) & (5) PLUMBING

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-03-24 Cont ID  
Sent By lwagner Date 2010-03-24 Time 15:17 Rev Time 0.00
Received By lwagner Date 2010-03-24 Time 14:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2011-01-28 Cont ID  
Sent By fmittner Date 2011-01-28 Time 11:43 Rev Time 0.00
Received By fmittner Date 2011-01-28 Time 11:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2010-12-17 Cont ID  
Sent By astelly Date 2010-12-10 Time 15:33 Rev Time 0.00
Received By astelly Date 2010-12-10 Time 15:33 Sent To HIST
Notes
2010-12-17 15:35:09AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 WINDOWS CANNOT BE CHANGED WITHOUT APPROVAL FROM THE
 HISTORIC PRESERVATION DIVISION.

Review Stop Z ZONING
Rev No 2 Status F Date 2010-10-19 Cont ID  
Sent By astelly Date 2010-10-19 Time 13:16 Rev Time 0.00
Received By astelly Date 2010-10-19 Time 13:16 Sent To  
Notes
2010-10-26 14:27:46AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 REPEAT COMMENT:
 PLEASE SUBMIT A SURVEY / SITE PLAN FOR THE PROPERTY
 UNDER REVIEW. YOUR SUBMISSION MAY GENERATE ADDITIONAL
 COMMENTS.
 ACCORDING TO THE CONSTRUCTION SERVICES DEPARTMENT AND
 REPAIR ESTIMATES SUBMITTED TO THE PLANNING DEPPARTMENT,
 THE PROPOSED SCOPE OF WORK SEEMS TO BE UNDER-VALUED.
 SINCE THE VALUE OF THE WORK EXCEEDS 50% OF THE PROPERTY
 VALUE, A LANDSCAPE PLAN WILL BE REQUIRED AND THE
 PROPERTY WILL HAVE TO BE BROUGHT INTO COMPLIANCE WITH
 THE LANDSCAPE CODE.
  
 ADDITIONAL COMMENT:
 THE FLOOR PLANS INDICATE THAT A ROOMING HOUSE IS BEING
 PLANNED FOR THE SECOND FLOOR OF THE STRUCTURE. PURSUANT
 TO SEC. 94-513(B)(2)B, THE ZONING CODE DOES NOT ALLOW
 NONCONFORMING USES WITH ADVERSE IMPACTS, SUCH AS A
 ROOMING HOUSE, TO BE RESTORED WITHOUT A CLASS B SPECIAL
 USE PERMIT IN THIS ZONING DISTRICT. THE PROPOERTY OWNER
 SHOULD EITHER APPLY FOR A CLASS B PERMIT OR CONVERT THE
 ROOMING HOUSE TO UP TO TWO (2) APARTMENTS.
  
 THE PROPERTY OWNER HAS BEEN INFORMED OF THIS FINDING.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-11 Cont ID  
Sent By astelly Date 2010-03-11 Time 15:09 Rev Time 0.00
Received By astelly Date 2010-03-11 Time 15:09 Sent To  
Notes
2010-03-11 15:16:44AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE SUBMIT A SURVEY / SITE PLAN FOR THE PROPERTY
 UNDER REVIEW. YOUR SUBMISSION MAY GENERATE ADDITIONAL
 COMMENTS.
 ACCORDING TO THE CONSTRUCTION SERVICES DEPARTMENT, THE
 PROPOSED SCOPE OF WORK SEEMS TO BE UNDER-VALUED. IF THE
 VALUE OF THE WORK EXCEEDS 50% OF THE PROPERTY VALUE, A
 LANDSCAPE PLAN WILL BE REQUIRED AND THE PROPERTY WILL
 HAVE TO BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE
 CODE.