Plan Review Details - Permit 09110018
Plan Review Stops For Permit 09110018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 13:33 Rev Time 0.00
Received By shill Date 2010-03-09 Time 13:33 Sent To  
Notes
2010-03-09 14:09:50PROVISO - ONLY ONE SET SUBMITTED FOR MANY DOCUMENTS
 (PRODUCT APPROVALS, SPEC SHEETS, LANDSCAPE PLAN, ETC.)
 - CONTRACTOR AGREED TO OBTAIN 2ND SET THROUGH OUR
 RECORDS DEPT PRIOR TO REQUIRED INSPECTIONS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-02-10 Cont ID  
Sent By shill Date 2010-02-10 Time 15:37 Rev Time 0.00
Received By shill Date 2010-02-10 Time 15:37 Sent To  
Notes
2010-02-10 15:39:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE HAVE A CONTRACTOR APPLY FOR PERMIT.
  
 2. IMPACT FEE ASSESSMENT REQUIRED (CHANGE OF USE, PER
 GWEN). PLEASE CONTACT PALM BEACH COUNTY FOR MORE
 INFORMATION, 561-233-5025.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-04 Cont ID  
Sent By shill Date 2009-11-04 Time 12:52 Rev Time 0.00
Received By shill Date 2009-11-03 Time 12:10 Sent To  
Notes
2009-11-04 12:56:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS PROJECT IS A CHANGE OF OCCUPANCY IN ADDITION TO
 A LEVEL 3 ALTERATION, FBC EB 202 (AUTO REPAIR IS S1,
 FBC311). PLEASE NOTE ON THE PLAN AND CHECK FOR
 COMPLIANCE WITH FBC EB CHAPTER 9.
  
 2. SEPARATE PERMIT REQUIRED FOR TANK REMOVAL AND
 REPLACEMENT.
  
 3. ENTRY DOOR IS TO MEET THE REQUIREMENT OF
 FBC11-4.13.11(2) (OPENING FORCE 8.5LBF).
  
 4. SEE FBC1004.1 AND DEFINITION OF FLOOR AREA, GROSS
 FBC 202. MAXIMUM AREA PER OCCUPANT AS PER TABLE
 1004.1.1 IS 30SF; BASED ON TOTAL SQUARE FEET AREA,
 OCCUPANT LOAD SHOULD BE 56 IF ENTIRE SPACE IS
 CLASSIFIED AS MERCANTILE, SINGLE OCCUPANCY.
  
 5. SEE COMMENT 5; IF OCCUPANT LOAD IS GREATER THAN 50,
 TWO INDEPENDENT EXITS REQUIRED FBC1015.
  
 6. A SHUTTER STORAGE AREA IS SHOWN. THIS IS ACCEPTABLE,
 BUT NOTE THAT ALL GLAZED PRODUCTS ARE IMPACT RATED
 (ADVISORY ONLY). EXIT DOORS ARE REQUIRED TO BE IMPACT
 FBC1003.6.
  
 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE A/C STANDS, FAC9B72. PLEASE HAVE THIS REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FBC*106.
  
 8. THIS REVIEW CAN BE PASSED WITH PROVISO (REVISION
 REQUIRED) UPON REQUEST OF ARCHITECT IF ALL OTHER TRADES
 PASS REVIEW. PLEASE CONTACT ME FOR FURTHER ASSISTANCE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-08 Cont ID  
Sent By btrobaug Date 2010-02-08 Time 11:35 Rev Time 0.00
Received By btrobaug Date 2010-02-08 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By btrobaug Date 2009-11-05 Time 07:31 Rev Time 0.00
Received By btrobaug Date 2009-11-05 Time 06:35 Sent To  
Notes
2009-11-05 07:32:24 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 ALL COMMENTS RELATE TO SHEET E-6
  
 1} REVISION REQUIRED FOR GEC PER 250.50, 250.52 &
 250.66. SHEET E-6 ONLY NEEDS REVISED.
  
 2} NOTE THAT THE TRANSFER SWITCH WILL BE MANUAL, SUBMIT
 MANUFACTURERS SPECIFICATIONS FOR SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-03 Cont ID  
Sent By mawillia Date 2010-02-03 Time 13:50 Rev Time 0.00
Received By mawillia Date 2010-02-03 Time 13:31 Sent To  
Notes
2010-02-03 13:49:59*****APPROVED*****
  
  
 PLAN SHEETS A2.1, A3.1, A5.1, AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By mawillia Date 2009-11-24 Time 11:39 Rev Time 0.00
Received By mawillia Date 2009-11-24 Time 10:59 Sent To  
Notes
2009-11-24 11:39:36*****PARTIAL APPROVAL*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER PLAN EXAMINERS' COMMENTS AS WELL AS THE FOLLOWING
 FIRE COMMENTS HAVE BEEN ADDRESSED:
  
 1. SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A OR CLASS B; NEW INTERIOR
 FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 2. COMMERCIAL COOKING EQUIPMENT, IF INSTALLED/UTILIZED,
 SHALL BE IN ACCORDANCE WITH NFPA 96 - 2004 EDITION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-01-25 Cont ID  
Sent By kstevens Date 2010-01-25 Time 08:50 Rev Time 0.00
Received By kstevens Date 2010-01-25 Time 08:50 Sent To  
Notes
2010-01-25 08:50:51 
  
  
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED FOR OVEN AT THE
 TIME OF APPLICATION FOR THE GAS PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-11-06 Cont ID  
Sent By kstevens Date 2009-11-06 Time 10:19 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 17:55 Sent To  
Notes
2009-11-06 10:20:10PASSED PENDING MANUF. SPEC. SHEETS FOR THE OVEN AND THE
 TANKLESS W/H.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-05-25 Cont ID  
Sent By vmolina Date 2010-05-25 Time 11:50 Rev Time 0.00
Received By vmolina Date 2010-05-25 Time 11:50 Sent To  
Notes
2010-05-25 11:50:40GAVE TO BTR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-10 Cont ID  
Sent By shill Date 2010-02-10 Time 15:39 Rev Time 0.00
Received By shill Date 2010-01-13 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-24 Time 11:45 Rev Time 0.00
Received By lmartine Date 2009-11-02 Time 13:34 Sent To  
Notes
2009-11-02 13:34:46C--8
 *****************EXPEDITED****************

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2010-03-10 Cont ID  
Sent By shill Date 2010-03-10 Time 14:39 Rev Time 0.00
Received By shill Date 2010-03-10 Time 14:38 Sent To  
Notes
2010-03-10 14:40:19RECEIPT # 2010-0308-132
 TRACKING # MU-2010-002656-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 13:36 Rev Time 0.00
Received By shill Date 2010-03-09 Time 13:36 Sent To  
Notes
2010-03-09 13:36:36IMPACT FEE RECEIPT REQUIRED - S/W CONTRACTOR; HE AGREED
 TO EMAIL THE RECEIPT
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-02-10 Cont ID  
Sent By shill Date 2010-02-10 Time 15:39 Rev Time 0.00
Received By shill Date 2010-02-10 Time 15:39 Sent To  
Notes
2010-02-10 15:39:53IMPACT FEE ASSESSMENT REQUIRED, CHANGE OF USE
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-01-20 Cont ID  
Sent By rkussner Date 2010-01-20 Time 16:19 Rev Time 0.00
Received By rkussner Date 2010-01-20 Time 16:19 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By rkussner Date 2009-11-03 Time 09:48 Rev Time 0.00
Received By rkussner Date 2009-11-03 Time 09:48 Sent To  
Notes
2009-11-03 09:54:01***LANDSCAPE REVIEW FAILED***
  
 THIS IS AN OLDER VERSION OF THE APPROVED PLAN. PLEASE
 SUBMIT 2 COPIES OF THE MOST RECENT PLAN (REVISION DATE
 4/22/09).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-26 Cont ID  
Sent By rregueir Date 2010-01-26 Time 16:53 Rev Time 0.00
Received By rregueir Date 2010-01-26 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-23 Cont ID  
Sent By rregueir Date 2009-11-23 Time 09:05 Rev Time 0.00
Received By rregueir Date 2009-11-23 Time 08:38 Sent To  
Notes
2009-11-23 09:05:27REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MOTORIZED DAMPER WITH SHUTOFF DAMPER CONTROLS IS
 REQUIRED ON THE OUTSIDE AIR INTAHE IN ACCORDANCE WITH
 FBC-B 13-409.AB.3.3.
  
 2. A TYPE 2 HOOD IS REQUIRED OVER THE OVEN IN
 ACCORDANCE WITH FBC-M 507.2.2. THIS HOOD SHOULD MAY BE
 COVERED UNDER A SEPARATE PERMIT IN CONJUNCTION WITH THE
 TYPE 1 HOOD.
  
 3. PRODUCT APPROVAL IS REQUIRED FOR ROOFTOP
 PRE-ENGINEERED A/C STAND IN ACCORDANCE WITH FBC-B
 106.3.3 AND FAC RULE 9B-72. IF THE PROPOSED STAND IS
 FOR WALK-IN REMOTE CONDENSERS, THE PRODUCT APPROVAL MAY
 BE SUBMITTED WITH THE SEPARATE PERMIT APPLICATION FOR
 THE WALK-IN COOLERS.
  
 NOTE: NEW ROOFTOP CONDENSERS SHALL MEET THE
 REQUIREMENTS FOR GUARDS IF WITHIN 10' OF THE ROOF EDGE
 PER FBC-M 304.10 AND FOR SERVICE ACCESS IN ACCORDANCE
 WITH FBC-M 306.5.
  
 ENERGY CALCULATIONS:
  
 4. A LARGE PORTION OF THIS BUILDING IS BEING CONVERTED
 FROM UNCONDITIONED TO CONDITIONED SPACE. PER ENERGY
 CODE DEFINITIONS, AN INCREASE IN CONDITIONED FLOOR AREA
 IS CONSIDERED AN ADDITION AND SHALL MEET THE
 REQUIREMENTS FOR NEW CONSTRUCTION IN ACCORDANCE WITH
 FBC-B 13-101.1.2. ADDITIONS TO EXISTING BUILDINGS SHALL
 FOLLOW THE SAME METHOD A CALCULATION PROCEDURE AS NEW
 CONSTRUCTION IN ACCORDANCE WITH FBC-B 13-400.2.A.1. ALL
 BUILDING ENVELOPE COMPONENTS FOR THE AREA OF THE
 ADDITION SHALL BE INCLUDED IN THE ENERGY CALCULATIONS.
  
 5. THE METHOD B FORM SUBMITTED SHOWS THE EQUIPMENT SIZE
 AS 12,300 BTU/H. THIS DOES NOT CORRESPOND WITH THE
 EQUIPMENT SHOWN ON THE PLANS OR THE COOLING LOAD
 CALCULATIONS. ALSO, ALL BUILDING ENVELOPE COMPONENTS
 ARE SHOWSN AS "EXISTING." WHILE THE PLANS SHOW MANY NEW
 ENVELOPE COMPONENTS BEING INSTALLED OR RETROFITTED. THE
 PLANS AND SPECIFICATIONS, INCLUDING THE ENERGY CODE
 CALCULATIONS, SHALL SHOW, IN SUFFICIENT DETAIL, ALL
 PERTINENT DATA AND FEATURES OF THE BUILDING AND THE
 EQUIPMENT AND SYSTEMS IN ACCORDANCE WITH FBC-B
 13-103.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-25 Cont ID  
Sent By kstevens Date 2010-01-25 Time 08:51 Rev Time 0.00
Received By kstevens Date 2010-01-25 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-06 Cont ID  
Sent By kstevens Date 2009-11-06 Time 10:11 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 17:54 Sent To  
Notes
2009-11-06 10:19:21DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 CITY WPB MUNICIPAL CODES
 FBC-2007 CHAPTER 11
  
 1. SHT A2.1 FLOOR PLAN SHOWS THE TOILET ROOM DOOR
 SWINGING INTO THE CLEAR FLOOR SPACE OF THE DRINKING
 FOUNTAIN. PER SECTION 11-4.22.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR @ (561) 822-2271, FAX (561) 822-2279 OR
 E-MAIL [email protected]. ARTICLE III SECTION 90-124(7),
 AND SECTIONS 1003.1 & 1003.3.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-22 Cont ID  
Sent By kdfreema Date 2010-01-22 Time 11:44 Rev Time 0.00
Received By kdfreema Date 2010-01-22 Time 11:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By kdfreema Date 2009-11-03 Time 14:40 Rev Time 0.00
Received By kdfreema Date 2009-11-03 Time 14:40 Sent To  
Notes
2009-11-03 15:03:02***FAILED***
  
 1. THE ZONING BOARD OF APPEALS PROVIDED A CONDITION
 THAT THE CITY'S CRIME PREVENTION UNIT REVIEW AND
 APPROVE THE PROPOSED PLANS PRIOR TO SUBMITTAL. EVIDENCE
 THAT THIS TOOK PLACE WAS NOT PROVIDED. PLEASE CONTACT
 KELLY CARSILLO AT 822-1620 TO SCHEDULE A MEETING TO
 REVIEW THE PLANS IF YOU HAVE NOT ALREADY DONE SO.
  
 2. PLEASE STATE HOW THE REQUIREMENTS OF THE CONVENIENCE
 BUSINESS SECURITY ACT (ATTACHED) ARE MET. NOTE THAT
 THIS PROPERTY EXPERIENCED A BURGLARY ON 8/7/09 AND IS
 THEREFORE SUBJECT TO THE ADDITIONAL SECURITY MEASURES
 FOUND WITHIN THE ACT.
  
 PLEASE ADDRESS ALL COMMENTS IN WRITING.
  
 CONTACT KELLY FREEMAN, GIS PLANNER AT 561-822-1458 WITH
 QUESTIONS.