Plan Review Details - Permit 09100591
Plan Review Stops For Permit 09100591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-17 Cont ID  
Sent By jwitmer Date 2009-12-17 Time 10:45 Rev Time 0.77
Received By jwitmer Date 2009-12-17 Time 10:45 Sent To  
Notes
2009-12-17 10:46:05REVISON# 1 REVIWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-11-03 Cont ID  
Sent By jwitmer Date 2009-11-03 Time 17:58 Rev Time 3.25
Received By jwitmer Date 2009-11-03 Time 06:32 Sent To  
Notes
2009-11-03 17:58:31BUILDING PLAN REVIEW
 PERMIT: 09100591
 ADD: 1552 PALM BEACH LAKES BLVD
 CONT: NCY CONSTRUCTION INC
 TEL: (561)543-3457
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SHEET A-501 THE NORTH ELEVATION INDICATES THE RE-USE
 OF EXISTING ALUMINUM STOREFRONT FRAMES AND NEW 9/16"
 CLEAR IMPACT GLAZING BEING INSTALLED INTO THE FRAMES.
 PLEASE EITHER PROVIDE EITHER ENGINEERING AND OR
 RATIONAL ANALYSIS FOR THE INSTALLATION OF GLAZING INTO
 THE FRAME AND INSTALLATION OF WINDOW ASSEMBLY TO THE
 NEW OPENING WITHIN THE STRUCTURE.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) SHEET S1.0 WIND DESIGN CRITERIA, THE PLANS INDICATE
 A EXPOSURE CATEGORY TYPE "B" PLEASE REVIEW1609.4.3.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 THE C-TYPE TERRAIN WILL CAUSE THE PRESSURES TO BE
 HIGHER ON THE NEW OPENINGS WITH HIGHER POSITIVE AND
 NEGATIVE PRESSURES, PLEASE UPDATE PLANS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-12-22 Cont ID  
Sent By dpalmer Date 2009-12-22 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2009-12-22 Time 10:07 Sent To  
Notes
2009-12-22 10:08:13LOW VOLTAGE UNDER SEPARATE PERMITS.
 PLANS SHOW DATA/PHONE WHICH MAY BE REFERENCED FOR TURN
 AROUND PERMITS.
 OTHER LV PERMITS SUCH AS ANY ACCESS CONTROLS SHALL BE
 UNDER SEPARATE PLANS AND PERMITS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-21 Cont ID  
Sent By dpalmer Date 2009-12-21 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2009-12-21 Time 14:12 Sent To  
Notes
2009-12-21 14:13:02 
 ** DENIED/TEMPORARY**
  
 1) NOTE: EXPEDITED PLAN REVIEW FEES FROM PREVIOUS
 REVIEW WERE NOT PAID. THESE ARE REQUIRED TO BE PAID AT
 THE TIME THE PLANS WERE COMPLETED.
  
 2) NOTE: SECOND SET OF THE SUBMITTED PLANS FOR THE
 FOLLOWING SHEETS ARE NOT SIGNED, DATED OR SEALED AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025.
 ** CALLED ENGINEERING FIRM AND NEW SHEETS ARE NEEDED.
 E-001, E-201, E-203, E-401, E-501 AND P-501
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-23 Cont ID  
Sent By dpalmer Date 2009-11-23 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2009-11-23 Time 13:54 Sent To  
Notes
2009-11-23 13:54:51** DENIED **
  
 1) NOTE: PLANS ARE SUBMITTED FOR PERMIT APPLICATION
 AFTER OCTOBER 1ST, 2009. THIS PLACES THE DESIGN TO BE
 UNDER THE 2008 NEC. PLANS STATE ON SHEET LS101 STATE
 DESIGN UNDER 2005.
 ELECTRICAL SHEET E001 STATES THE CORRECT ELECTRICAL
 CODE HOWEVER NOT THE CORRECT LIFE SAFETY CODE. PLANS
 STATE 2003 HOWEVER PER FLORIDA ADMINISTRATIVE CODE
 69A-60.003,.004, 69A-3.012 AS OF DECEMBER 31ST, 2008
 THE ADOPTED NFPA-101 IS THE 2006 EDITION. PLEASE
 ADJUST.
 PLEASE SEE SHEET E-401 WHICH UNDER GENERAL NOTES #3
 STATES THE 2009 NEC. THERE IS NO 2009 NEC.
  
 2) NOTE: THE SUBMITTED FLA COM ENERGY CALCULATIONS ARE
 METHOD *A* FOR WHOLE BUILDING COMPLIANCE. THIS IS AN
 EXISTING BUILDING, PLEASE EXPLAIN USE OF METHOD *A*.
 PLEASE ALSO KNOW THAT NEW CONSTRUCTION AND USING METHOD
 *A* WOULD MEANT THAT EVERY COMPONENT OF THE BUILDING
 CONSTRUCTION INCLUDING ENERGY USE AND ITEMS WHICH
 AFFECT ENERGY USE MUST BE INCLUDED. THE INPUT DATA
 REPORT IS REQUIRED TO BE COMPLETE WITH ALL CONSTRUCTION
 ASPECTS OF THE BUILDING.
 13-101.1,13.101.1.3, 13-101.4.1, 13-400.0.A,
 13-400.0.B, 13-400.0.B.4
  
 PLEASE SEE SPECIFICALLY EXTERIOR LIGHTING WHICH IS
 COMPLETELY BLANK ON THE SUBMITTED CALCULATIONS AND
 INPUT DATA REPORT.
 THERE IS A SUBSTANTIAL AMOUNT OF PARKING LOT LIGHTING
 WHICH IS FED FROM THIS BUILDING ELECTRICAL SERVICE.
 PLEASE SEE SECTION 13-415.AB.2. SEE TABLE
 13-415.AB.2.2.
 PLEASE ALSO SEE OTHER COMPONENTS SUCH AS DOORS (SECTION
 13-403) WHICH ARE BLANK, ALONG WITH PIPING (SECTION
 13-411, 13-412 ETC.
 IF METHOD *A* IS GOING TO BE USED AS THIS WERE NEW
 CONSTRUCTION, ALL MUST BE COMPLETED.
 DISPLAY OR ACCENT LIGHTING IN THE IDR MAY NOT BE USED
 AS NONE OF THIS LIGHTING IN THIS OCCUPANCY MEETS THE
 EXEMPTIONS OF THE LIGHTING PERFORMANCE CALCULATION
 PROCEDURES. SPACES ARE 121, 191, 101B.
 ANOTHER AREA WOULD BE TWO OF THE EXISTING RESTROOMS.
 THEY CAN NOT BE EXISTING AND NOT BE PLACED INTO THE IDR
 AS SPACES FOR METHOD *A*.
 PLANS INDICATE WHAT APPEARS TO BE METHOD B SPACE BY
 SPACE. MAY NOT USE BOTH VERSIONS/METHODS. 13-415.AB.5
 THERE WERE SUBSTANTIAL CHANGES TO THE 2007 FBC W/ 2009
 SUPPLEMENTS. THERE ARE NO LONGER ALLOWANCES FOR THIS
 SPACE.
  
 3) NOTE: PLEASE EXPLAIN SOME OF THE LIGHTING CONTROLS.
 BASED ON THE SYMBOL LEGEND MANY OF THESE DEVICES ARE
 STANDARD SINGLE POLE OR THREE POLE DEVICES. MANY OF THE
 LIGHTS HAVE AREA OCCUPANCY SENSORS HOWEVER NOT ALL.
 FOR EXAMPLE: PLEASE SEE THE FRONT ENTRY AREA WHICH
 INDICATE A8 TYPE FIXTURES ON PANEL LP-1, CIRCUIT 13.
 THESE ARE SHOWN BEING CONTROL BY A SINGLE POLE SWITCH
 WITH NO AUTOMATED CONTROLS AS REQUIRED PER
 13-415.AB.1.1,.1.2, .1.3.
  
 4) NOTE: PLEASE INDICATE NEW OR EXISTING ROOF TOP GFI
 REQUIRED FOR A/C EQUIPMENT. 210.63, 210.8B3
  
 5) NOTE: HOW ARE THE LIGHTS IN STAIRS CONTROLLED?
 NOTED: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2
 FOR TYPES OF OCCUPANCY SENSORS REQUIRED WHEN USING FOR
 CONTROL OF EGRESS LIGHTING. THIS IS FOR ALL EGRESS
 PATHS NOT ONLY STAIRS.
 ( DEVICES SHALL FAIL SAFE *ON*) KEY NOTES ON PLANS
 ALREADY INDICATE THIS ON E201 HOWEVER IS NOTED FOR
 CLARITY AS CONTROLS FOR STAIR LIGHTING IS NOT SHOWN.
  
 6) NOTE: PLEASE INDICATE THE PHOTO-METRIC LEVELS FOR
 STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2.
 10FT CANDLES REQUIRED UNDER NORMAL AND 1FT CANDLE IS
 PERMITTED UNDER EMERGENCY FOR STAIRS. ALL OTHER LEVEL
 EGRESS WALKING SURFACES ARE 1FT CANDLE WHICH BASED ON
 PLANS AND LIGHTING SHOWN APPEARS TO BE MET.
  
 7) NOTE: PLANS INDICATE RELOCATION OF TIME CLOCK FOR
 EXTERIOR LIGHTING HOWEVER LIGHTING CONTROLS MUST MEET
 PRESCRIPTIVE FOR NEW INSTALLED. DOES TIME CLOCK MEET
 13-415.AB.1.4 FOR EXTERIOR CONTROLS?
  
 8) NOTE: PLEASE TAKE A LOOK AT THE LOAD CALCULATIONS ON
 SHEET E501. THE CODE SECTIONS LISTED ARE NOT FROM
 CURRENT 2008 NEC OR FROM THE 2005 NEC.
 ONE SECTION IS NOTED AS 220.21 WHICH IS NOT PART OF
 CODES LISTED. PLEASE ALSO SEE 220.14 AS NOTED.
 PLEASE ALSO SEE THAT THE LOAD CALCULATIONS ARE NOT
 LISTING ANY LIGHTING LOADS. HOW IS THIS POSSIBLE WHEN
 THE LP CONTAINS NUMEROUS LIGHTING CIRCUITS?
 THE LIGHTING COLUMN ACTUALLY INDICATES 0.00 LOAD WITH A
 DEMAND OF 125% AND DEMAND LOAD OF 0.00. PLEASE EXPLAIN
 AS THE LOAD OF 17.9 ON THE LP PANEL APPEARS TO BE UNDER
 THE RECEPTACLE COLUMN LOAD.. PLEASE SEE 220.42,220.12,
 230.42, 215.5 ETC.
  
 9) NOTE: PLEASE SEE NEC 517 PART II, BEGINNING WITH
 517.13 AND ADJUST PLANS. PLEASE SEE THE FOLLOWING WHICH
 IS EXTRACTED FORM THE NEC COMMENTARY UNDER 517.1.
 ***
 THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.**
  
  
 10) NOTE: PLEASE SEE 2008 NEC 210.8B5 AS *ALL*
 RECEPTACLES IN AREAS LISTED ARE REQUIRED TO BE GFI/GFI
 PROTECTED. THIS IS REQUIRED WHETHER OR NOT THEY ARE
 DEDICATED CIRCUITS SUCH AS THE REFRIGERATOR. THE 2005
 NEC HAD SUBSTANTIAL CHANGES TO 210.8 FOR RESIDENTIAL
 AND THE 2008 NEC HAS EXPANDED GFI PROTECTION.
  
 11) NOTE: PLEASE LIST AIC RATING FOR NEW SERVICE
 ENTRANCE RATED DISCONNECT. 110.9
  
 12) NOTE: PLEASE INDICATE THE FEEDERS AND CONDUITS FROM
 THE SERVICE MAIN TO THE MDP. THE RISER ONLY INDICATES
 SEC AHEAD OF THE MAIN.
 310.16, 240.4, ETC
 PLEASE BE SURE TO ALSO INCLUDE THE REQUIRED EQUIPMENT
 GROUNDING CONDUCTOR(S) SIZED PER 250.122.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-12-23 Cont ID  
Sent By mawillia Date 2009-12-23 Time 13:54 Rev Time 0.00
Received By mawillia Date 2009-12-23 Time 13:47 Sent To  
Notes
2009-12-23 13:54:46*****APPROVED*****
  
 THE ONE (OF TWO) SUBMITTED PLAN SHEET E-201 WHICH WAS
 NOT FIRE-STAMPED ON 12/21/2009 FIRE-STAMPED DUE TO NOT
 BEING SIGNED, DATED, AND SEALED WAS RECTIFIED.
 FIRE-STAMPED AND DATED AS 12/21/2009 FOR CONSISTENCY OF
 PLANS.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-12-21 Cont ID  
Sent By mawillia Date 2009-12-21 Time 15:20 Rev Time 0.00
Received By mawillia Date 2009-12-21 Time 14:54 Sent To  
Notes
2009-12-21 14:56:02*****PARTIAL APPROVAL*****
  
  
 PREVIOUSLY (11/17/09) FIRE-STAMPED PLAN SHEETS LS-100
 AND A-501 WERE STAMPED, INITIALED, AND DATED; HOWEVER,
 ONLY ONE OF THE SUBMITTED PLAN SET SHEET E-201 WAS
 FIRE-STAMPED AS THE OTHER WAS PLAN SET SHEET E-201 NOT
 SIGNED, DATED, AND SEALED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-11-17 Cont ID  
Sent By mawillia Date 2009-11-17 Time 15:13 Rev Time 0.00
Received By mawillia Date 2009-11-17 Time 14:50 Sent To  
Notes
2009-11-17 15:13:07*****APPROVED*****
  
  
 PLAN SHEETS LS-100, LS-101, A-501, A-800, AND E-201
 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-12-29 Cont ID  
Sent By btrobaug Date 2009-12-29 Time 09:44 Rev Time 0.00
Received By btrobaug Date 2009-12-29 Time 09:44 Sent To B
Notes
2009-12-29 09:45:39ROUTED TO JIM WITMER./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2009-12-09 Time 13:26 Sent To  
Notes
2009-12-09 13:28:48RESUB: BOX C-5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-23 Time   Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 13:33 Sent To  
Notes
2009-11-02 13:31:20C--4
 ***************EXPEDITED***************

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-12-29 Cont ID  
Sent By jwitmer Date 2009-12-29 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2009-12-29 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-21 Cont ID  
Sent By rregueir Date 2010-01-21 Time 16:12 Rev Time 0.00
Received By rregueir Date 2010-01-21 Time 16:09 Sent To  
Notes
2010-01-21 16:12:37REVISED MD-201, M-201, M-601 DELTA 1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 13:48 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 13:13 Sent To  
Notes
2009-11-06 13:48:16REVIEW #: 1ST **PROVISO**
 ACTION: PASSED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE TEST & BALANCE REPORT TO FIELD INSPECTOR AT
 FINAL INSPETION TO VERIFY VENTILATION RATES IN
 ACCORDANCE WITH FBC-M 403.3.4 AND ASHRAE 62.1-2004
 SECTION 7.2.2.
  
 2. PROVIDE PRODUCT APPROVAL DOCUMENTATION WITH
 INSTALLATION INSTRUCTIONS FOR THE PRE-ENGINEERED A/C
 STANDS TO FIELD INSPECTOR AT TIME OF INSPECTION PER
 FBC-B 106.3.3 AND FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By kstevens Date 2009-12-22 Time 13:53 Rev Time 0.00
Received By kstevens Date 2009-12-22 Time 13:53 Sent To  
Notes
2009-12-22 13:54:27 
  
  
 PASSED/PROVISO:
 SHT A-703 DETAIL 6, SHOW COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED, CABINET DOORS PROHIBITED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES.
 (REVISION REQUIRED) (SUBMIT ELEVATION FOR SINK)
  
 (NEW SHT P-501).
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By kstevens Date 2009-11-05 Time 07:20 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 07:20 Sent To  
Notes
2009-11-05 07:26:51 
  
  
 PASSED/PROVISO:
 SHT A-703 DETAIL 6, SHOW COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED, CABINET DOORS PROHIBITED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES.
 (REVISION REQUIRED) (SUBMIT ELEVATION FOR SINK)
  
 SHT P-501 ELECTRIC WATER HEATER 2 + 3 DETAIL REFERENCES
 DETAIL 4/P6.02. SHEET P6.02 HAS NOT BEEN SUBMITTED IN
 PLANS. REVISION REQUIRED CHANGING DETAIL ON SHT P-501
 OR SHEET P6.02 SHALL BE SUBMITTED AS A REVISION SHOWING
 DETAIL REFERENCED. SECTIONS 504.6 & 504.7.2.
  
  
  
  
  
 .

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-23 Cont ID  
Sent By jroach Date 2009-12-23 Time 13:25 Rev Time 0.00
Received By jroach Date 2009-12-23 Time 13:25 Sent To  
Notes
2009-12-23 13:25:17ZONING PLAN REVIEW
  
 PERMIT NO.: 09100591
 ADDRESS: 1552 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: PETER GILSTAD
 TELEPHONE NO.: 655.2423
 SCOPE OF REVIEW: INTERIOR REMODEL AND ADDITION OF UPPER
 LEVEL OFFICE SPACE.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 THESE PLANS ARE APPROVED AS AN AT-RISK PERMIT! PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (CO),
 NECESSARY AMENDMENTS TO THE COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO, AND APPROVED
 THROUGH, THE PLANNING & ZONING DEPARTMENT REGARDING THE
 ADDITIONAL SQUARE FOOTAGE (AND ADDITIONAL TRAFFIC
 IMPACT) ADDED ON THE UPPER LEVEL. FAILURE TO OBTAIN
 SUCH APPROVALS MAY NECESSITATE THE REMOVAL OF THE UPPER
 LEVEL.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-10 Cont ID  
Sent By jroach Date 2009-11-10 Time 14:49 Rev Time 0.00
Received By jroach Date 2009-11-10 Time 14:49 Sent To  
Notes
2009-11-10 14:49:58ZONING PLAN REVIEW
  
 PERMIT NO.: 09100591
 ADDRESS: 1552 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: CHRISTOPHER BACHE
 TELEPHONE NO.: 561.753.6050
 SCOPE OF REVIEW: ALTERATIONS TO EXISTING BUILDING FOR
 CONVERSION TO MEDICAL OFFICE.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO SECTION 94-207(E) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), A MINOR
 AMENDMENT TO THE HOME DEPOT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO, AND APPROVED
 BY, THE PLANNING & ZONING DEPARTMENT PRIOR TO ISSUANCE
 OF A BUILDING PERMIT. THE AMENDMENT IS REQUIRED AS
 ALTERATIONS ARE BEING MADE TO THE PREVIOUSLY-APPROVED
 ELEVATIONS AND ADDITIONAL SQUARE FOOTAGE IS BEING ADDED
 TO THE BUILDING.
  
 2) A SITE PLAN SHALL BE PROVIDED WITH A CURRENT AND
 ACCURATE DATA TABLE REFLECTING THE ADDITIONAL SQUARE
 FOOTAGE, IMPACT ON PARKING, ETC.
  
 3) THE SMALL SITE PLAN ON SHEET A-201 INDICATES
 LOCATION OF AN "EXISTING/NEW TRANSFORMER." PLEASE
 CLARIFY AS TO WHETHER OR NOT AN ADDITIONAL TRANSFORMER
 IS BEING PLACED HERE. IF NEW, HOW WILL THIS AFFECT
 EXISTING LANDSCAPING, ETC...AND THIS WOULD NEED TO BE
 INCLUDED IN THE MINOR AMENDMENT ALONG WITH ANY REVISED
 LANDSCAPE PLANS.
  
 4) STAFF HAS SIGNIFICANT CONCERNS REGARDING THE
 PROPOSED WINDOW INSTALLATION ON THE SOUTH SIDE OF THE
 BUILDING. WHAT IS BEING PROPOSED IS NOT COMPATIBLE WITH
 THE EXISTING ARCHITECTURE. THE NEW WINDOWS SHOULD
 CORRESPOND WITH THE SIZE AND LOCATION OF THE EXISTING
 FAUX-OPENINGS AND AWNINGS.
  
 5) PLEASE IDENTIFY THE IMPACT ON THE LANDSCAPING AS A
 RESULT OF THE PROPOSED DOORWAY AND SIDEWALK ON THE EAST
 SIDE OF THE BUILDING. THIS REVISION SHALL BE INCLUDED
 IN THE MINOR AMENDMENT.
  
 6) FYI...NEW SIGNAGE WILL BE REQUIRED TO COMPLY WITH
 THE CURRENT SIGN REGULATIONS FOR THE HOME DEPOT CPD.
 THE SIZE OF PREVIOUS SIGNAGE DOES NOT GUARANTEE
 COMPLIANCE WITH THESE REGULATIONS.
  
 7) WILL ANY GENERATORS BE ADDED TO THE BUILDING? IF SO,
 PLEASE BE SURE TO INDICATE THE LOCATION AS IT MAY
 AFFECT THE SITE/LANDSCAPE PLANS. BE SURE TO INCLUDE IN
 THE MINOR AMENDMENT. GENERATORS SHALL BE SCREENED IN
 COMPLIANCE WITH THE CITY'S ZLDRS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  