Plan Review Details - Permit 09100579
Plan Review Stops For Permit 09100579
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 08:34 Rev Time 0.77
Received By jwitmer Date 2009-11-09 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-11 Cont ID  
Sent By swurafti Date 2010-02-11 Time 10:11 Rev Time 0.00
Received By swurafti Date 2010-02-11 Time 10:11 Sent To  
Notes
2010-02-11 10:11:49OKAY TO ISSUE PER DPALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 08:05 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 08:05 Sent To  
Notes
2009-11-24 08:05:35** DENIED **
  
 1) NOTE: PLANS ARE SUBMITTED FOR PERMIT APPLICATION
 AFTER OCTOBER 1ST, 2009. THIS PLACES THE DESIGN TO BE
 UNDER THE 2008 NEC. SEVERAL CODE SECTIONS REFLECTED ON
 DESIGN DOCUMENTS ARE NOT FROM THE 2008 NEC OR THE 2005
 NEC.
 PLEASE ADJUST NOTES FOR CORRECT CODES.
 PLEASE ALSO KNOW THE CODE IN WHICH THE PROJECT IS
 DESIGNED SHALL BE LISTED ON PLANS.
  
 2) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK IS
 LOW. THE VALUE IS REQUIRED TO INCLUDE ALL LABOR,
 EQUIPMENT, EQUIPMENT SUPPLIED BY OWNER, MATERIALS,
 CONTRACTOR OVER HEAD, CONTRACTOR PROFIT, COST OF PLAN
 DESIGN ETC. EVEN IF ANY OF THESE ARE OWNER SUPPLIED.
 FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH.
 THE PROPOSED EQUIPMENT AS SHOWN ON PLANS ALONG WITH
 MATERIALS IS SUBSTANTIALLY HIGHER THAN THE COMPLETE
 APPLIED VALUE OF $10K.
 PLEASE ADJUST OR ONE WILL BE ASSESSED USING ADOPTED
 GUIDES.
  
 3) NOTE: THE PROPOSED TRANSFORMER SHOWN ON PLANS AT
 GARAGE IS IN THE WORKING CLEARANCE OF THE METER PER
 110.26.
  
 4) NOTE: PLEASE SHOWN ALL DISCONNECTING MEANS AT
 DETACHED BUILDING PER 225.31-225.39.
  
 5) NOTE: PLEASE INDICATE GROUNDING PER 250.32,250.50
 FOR DETACHED BUILDING.
  
 6) NOTE: RISER DOES NOT INDICATE ANY EQUIPMENT
 GROUNDING CONDUCTOR FROM GENERATOR PLUG. PLEASE SEE
 250.122 FOR SIZING.
  
 7) NOTE: PLEASE INDICATE GROUNDING OF SEPARATELY
 DERIVED SYSTEMS PER 250.30.250.20
  
 8) NOTE: PLEASE SEE 250.94 FOR INTERSYSTEM BONDING
 TERMINATION.
  
 9) NOTE: PLEASE SEE 250.50 AND OTHER GROUNDING SECTIONS
 NOTED ABOVE. THE RISER INDICATES 1-#8 FOR GROUNDING
 ELECTRODE CONDUCTOR HOWEVER NO ATTACHMENT LOCATION IS
 SHOWN.
 250.50,250.53,250.56, 54 ETC
  
 10) NOTE: GROUNDING ELECTRODE CONDUCTOR IS REQUIRED TO
 BE SIZED PER 250.66. THE #8 SHOWN IS TOO SMALL.
  
 11) NOTE: PLEASE INCLUDE VOLTAGE DROP CALCULATIONS PER
 FBC 13-413.AB.1
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-11-17 Cont ID  
Sent By mawillia Date 2009-11-17 Time 13:44 Rev Time 0.00
Received By mawillia Date 2009-11-17 Time 13:30 Sent To  
Notes
2009-11-17 13:45:57*****APPROVED*****
  
 SHEET T-1 STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 13:35 Rev Time 0.00
Received By btrobaug Date 2010-01-12 Time 13:35 Sent To E
Notes
2010-01-12 13:36:16TO DEWEY./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-08 Cont ID  
Sent By lmartine Date 2009-12-03 Time 11:55 Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 16:11 Sent To  
Notes
2009-11-02 16:18:22C--9

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-03 Cont ID  
Sent By astelly Date 2009-12-03 Time 13:55 Rev Time 0.00
Received By astelly Date 2009-12-03 Time 13:55 Sent To  
Notes
***NONE***