Plan Review Details - Permit 09100525
Plan Review Stops For Permit 09100525
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-11-04 Cont ID  
Sent By mcarsill Date 2009-11-04 Time 08:06 Rev Time 0.00
Received By mcarsill Date 2009-11-04 Time 08:01 Sent To  
Notes
2009-11-04 08:06:31 
 1. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 EQUIPPED WITH KNOX LOCKING CAPS.
  
 2. THE ENTIRE STANDPIPE SYSTEM INCLUDING THE FIRE
 DEPARTMENT CONNECTION (FDC) SHALL BE PRESSURE TESTED AT
 200 PSIG FOR TWO HOURS.
  
 3. ALL STANDPIPE HOSE VALVES SHALL BE EQUIPPED WITH 2
 1/2 TO 1 1/2 REDUCERS.
  
 4. THE FIRE DEPARTMENT CONNECTION SHALL BE PROPERLY
 IDENTIFIED FOR WHICH DOCK IT SERVES.
  
 5. PORTABLE FIRE EXTINGUISHERS SHALL BE PROPERLY
 SERVICE TAGGED.
  
 6. ALL WORK IS SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
  
 APPROVED PROVISO:
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]