Plan Review Details - Permit 09100440
Plan Review Stops For Permit 09100440
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-01-25 Cont ID  
Sent By jwitmer Date 2010-01-25 Time 09:38 Rev Time 0.66
Received By jwitmer Date 2010-01-25 Time 09:16 Sent To  
Notes
2010-01-25 09:38:56NEW A-2 12/23/09 I SPOKE WITH MARCELL TODAY ABOUT THE
 ISSUE OF TENANT SEPERATION IN REGARDS TO THE BEAUTY
 SALON AT MC KEEN TOWERS. MARCEL INDICATED THERE IS NO
 LEASE, THIS IS A SERVICE STRICTLY FOR THE RESIDENCE AND
 THE BEAUTY SALON PERSONNEL ARE EMPLOYEES OF THE MC KEEN
 TOWERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-23 Cont ID  
Sent By jwitmer Date 2009-12-23 Time 14:40 Rev Time 0.00
Received By jwitmer Date 2009-12-23 Time 14:40 Sent To  
Notes
2009-12-23 14:46:4512/23/09 I SPOKE WITH MARCELL TODAY ABOUT THE ISSUE OF
 TENANT SEPERATION IN REGARDS TO THE BEAUTY SALON AT MC
 KEEN TOWERS. MARCEL INDICATED THERE IS NO LEASE, THIS
 IS A SERVICE STRICTLY FOR THE RESIDENCE AND THE BEAUTY
 SALON PERSONNEL ARE EMPLOYEES OF THE MC KEEN TOWERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-22 Cont ID  
Sent By jwitmer Date 2009-12-22 Time 15:50 Rev Time 0.55
Received By jwitmer Date 2009-12-22 Time 15:50 Sent To  
Notes
2009-12-22 15:59:12BUILDING PLAN REVIEW
 PERMIT: 09100440
 ADD: 315 S FLAGLER
 CONT: J JAY ROTHE INC
 TEL: (561)389-4137
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 DEC.22/ 2009
  
 1-3) COMPLIED.
  
 4) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION ON THE
 NEW TENANT SEPERATION WALL/ CORRIDOR WALLS AND OR
 OPENING PROTECTIVES, PLEASE PROVIDE ADDITIONAL
 INFORMATION. FBC 708.1(7) & TABLE 715.4 OPENING
 PROTECTIVES. THIS ISSUE WAS DISCUSSED WITH THE BUILDING
 OFFICIAL DOUG WISE AND HE BELIEVES THE 1 HR RATED
 TENANT SEPERATION WALLS ARE REQUIRED UNLESS THE
 EXCEPTION OF 3,000 SQ FT OF B OCCUPANCY.
  
 5-7) COMPLIED.
  
 8) NEW COMMENT, THE NOTICE OF COMMENCEMENT WAS RECORDED
 9/16/09 AND WILL NEED TO BE RE-RECORDED PER FL S
 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 NOTE!!!CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 THREE
 OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION. THIS IS TO BE ASSESSED TO THE DESIGNER OF
 RECORD. PLEASE CONTACT ME IF ANY QUESTIONS ARISE FROM
 THE COMMENTS OF THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By jwitmer Date 2009-10-26 Time 14:30 Rev Time 1.50
Received By jwitmer Date 2009-10-26 Time 13:03 Sent To  
Notes
2009-10-26 14:12:56BUILDING PLAN REVIEW
 PERMIT: 09100440
 ADD: 315 S FLAGLER
 CONT: J JAY ROTHE INC
 TEL: (561)389-4137
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 OCT. 26/ 2009
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
 PLEASE INDICATE THIS INFORMATION ON THE PLANS.
  
 2) THE PLANS DO NOT PROVIDE ENOUGH INFORMATION FOR A
 THROUGH REVIEW, PLEASE PROVIDE THE MINIMUM BUILDING
 TYPE. TABLE 503 & TABLE 601. I BELIEVE THIS IS A
 HIGHRISE BUILDING OF 11 STORIES OR MORE BEING
 CONSIDERED A TYPE 1-A BUILDING.
  
 3) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION AS TO THE
 BUILDING USE OR OCCUPANCY, IT APPEARS TO BE A MIXED USE
 OCCUPANCY, IS THIS A NONSEPERATED OCCUPANCY IN
 COMPLIANCE WITH 508.3.2.1 OR SEPERATED OCCUPANCIES IN
 COMPLIANCE WITH 508.3.3.
  
 4) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION ON THE
 NEW TENANT SEPERATION WALL/ CORRIDOR WALLS AND OR
 OPENING PROTECTIVES, PLEASE PROVIDE ADDITIONAL
 INFORMATION. FBC 708.1(7) & TABLE 715.4 OPENING
 PROTECTIVES.
  
 5) SHEET A-3 DETAIL B INDICATES THE USE OF WOOD
 BLOCKING, PLEASE SEE SECTION 603.1 FOR ALLOWABLE
 MATERIALS.
  
 6) SHEET A-1 INDICATES THE DRINKING FOUNTAIN HAS BEEN
 RELOCATED PLEASE PROVIDE THE WIDTH OF THE CORRIDOR AS
 WELL AS THE AT WHAT HEIGHT THE FOUNTAIN IS TO BE
 INSTALLED, PROVIDE BOTH THE TOP AND BOTTOM OF THE WATER
 FOUNTAIN. 1017.2 MINIMUM CORRIDOR WIDTH, 11-4.4.1
 PROTRUDING OBJECTS, & 11-4.15.5 CLEARENCES.
  
 7) IT APPEARS THERE IS A TYPO ON ALL THE SHEETS BEING
 THE ADDRESS AT 15 S FLAGLER, PLEASE CORRECT TO 315 S
 FLAGLER AND SUITE NUMBER .
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-01-28 Cont ID  
Sent By btrobaug Date 2010-01-28 Time 10:51 Rev Time 0.00
Received By btrobaug Date 2010-01-28 Time 10:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 13:18 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 12:35 Sent To  
Notes
2009-12-22 13:18:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 PREVIOUS REVIEW.
  
 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED
 BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE
 READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE
 THE CONTROLLED LIGHTING
  
 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS
 INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR
 THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 NOTE : THE FIXTURE SCHEDULE ON SHEET E-1 DOES NOT
 CORRELATE WITH THE SCHEDULE ON SHEET A-2.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-29 Cont ID  
Sent By btrobaug Date 2009-10-29 Time 14:29 Rev Time 0.00
Received By btrobaug Date 2009-10-27 Time 15:18 Sent To  
Notes
2009-10-27 15:57:03 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} 401.4 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 2} 302.1 GENERAL. STRUCTURES OR PORTIONS OF STRUCTURES
 SHALL BE CLASSIFIED WITH RESPECT TO OCCUPANCY------,
 INDICATE SAME ON THE PLAN, ALSO INDICATE IF THIS IS A
 CHANGE OF OCCUPANCY PER CHAPTER 9 EXISTING BUILDING
 CODE FBC 2007.
  
 3} PANEL"A" IS LOCATED IN A STORAGE CLOSET WHICH MAY BE
 IN VIOLATION OF 110.26 FOR CLEARANCES IT STORED ITEMS
 ARE IN THE REQUIRED FREE SPACE, AND 240.24 (D) NOT IN
 VICINITY OF EASILY IGNITIBLE MATERIAL OVERCURRENT
 DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS, AND
 WOUD ALSO BE A VIOLATION IF CHEMICALS ARE STORED IN
 THIS SPACE. A SAFER LOCATION WOUD BE ON THE WALL
 OUTSIDE AND ADJACENT TO THE CLOSET
  
 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED
 BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE
 READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE
 THE CONTROLLED LIGHTING
  
 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS
 INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR
 THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 6} THE ADDRESS IN THE TITLE BLOCK, SHEET E-1IS
 INCORRECT. PLEASE INCLUDE THE ADDRESS AND SUITE/UNIT
 NUMBER OF THE PROJECT ON THE PLANS PER 106.1.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By mawillia Date 2009-12-21 Time 16:05 Rev Time 0.00
Received By mawillia Date 2009-12-21 Time 15:39 Sent To  
Notes
2009-12-21 16:05:33*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1, A-2, E-1, AND FS-1 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-11-17 Cont ID  
Sent By mawillia Date 2009-11-16 Time   Rev Time  
Received By mawillia Date 2009-11-16 Time   Sent To  
Notes
2009-11-16 19:11:42*****DENIED*****
  
 1. INDICATE THE TYPE OF OCCUPANCY AND THE OCCUPANT LOAD
 FOR THIS PROJECTED SITE.
  
 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3. IT IS INDICATED THAT THE TENANT SPACE IS/WILL BE
 LOCATED ON THE SECOND FLOOR. WILL A SUITE NUMBER BE
 ASSIGNED TO THIS TENANT SPACE FOR BETTER LOCATING THE
 PREMISE? IF SO, THE SUITE NUMBER SHALL BE INCLUDED IN
 THE ADDRESS.
  
 4. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 6. AS WAS DONE FOR THE NEW CEILINGS, SPECIFY THE
 INTERIOR FINISH MATERIAL FOR THE WALLS IN TERMS OF
 CLASS A, CLASS B, OR CLASS C.
  
 7. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-01-27 Cont ID  
Sent By lmartine Date 2010-01-19 Time 14:03 Rev Time 0.00
Received By lmartine Date 2010-01-19 Time 10:07 Sent To  
Notes
2010-01-21 10:15:46TO B-22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 15:41 Sent To  
Notes
2009-12-14 15:43:15B2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-17 Cont ID  
Sent By mawillia Date 2009-11-17 Time 10:04 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 10:40 Sent To  
Notes
2009-10-26 10:43:18SENT TO BOB #B8.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 10:40 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-04 Cont ID  
Sent By rregueir Date 2009-11-04 Time 10:43 Rev Time 0.00
Received By rregueir Date 2009-11-04 Time 10:33 Sent To  
Notes
2009-11-04 10:43:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN HAS TWO EXHAUST FAN SCHEDULES. ONE FOR A
 "NUTONE" 50 CFM FAN AND ONE FOR A "GREENHECK" 70 CFM
 FAN. THERE IS ONLY ONE EF-1 SHOWN ON THE PLANS. PLEASE
 COORDINATE FLOOR PLAN AND EQUIPMENT SCHEDULES IN
 ACCORDANCE WITH FBC-M 304.1 AND 304.11. SEE ALSO NEXT
 COMMENT REGARDIN REQUIRED EXHAUST RATES.
  
 2. PLAN SHOWS EITHER 50 OR 70 CFM OF EXHAUST FOR THE
 BEAUTY SALON. PER ASHRAE 62.1-2004 TABLE 6-4, THE
 REQUIRED EXHAUST RATE FOR THIS SPACE IS 0.12 CFM/SQ.
 FT. FOR A TOTAL OF 205 CFM. PROVIDE THE MINIMUM EXHAUST
 RATE AS REQUIRED PER THIS SECTION.
  
 3. THE VENTILATION RATE DOES NOT MEET THE MINIMUM
 VENTILATION RATE AS REQUIRED PER ASHRAE 62.1-2004 TABLE
 6-1. THE MINIMUM VENTILATION RATE FOR A HAIR AND NAIL
 SALON OF 342 SQ.FT. WOULD BE APPROX 220 CFM. SHOW HOW
 220 CFM OF OUTDOOR AIR IS TO BE PROVIDED TO THIS SPACE
 IN ACCORDANCE WITH THIS SECTION AND FBC-M 403.4.
  
 4. HAIR SALON IS GIVEN AN AIR CLASSIFICATION OF 2. WHAT
 IS THE AIR CLASSIFICATION OF THE SURROUNDING SPACES?
 DECLARE THIS CLASSIFICATION ON PLANS WITH JUSTIFICATION
 IN ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 5.17.4. AT
 THIS TIME IT IS NOT CLEAR WHETHER AIR CAN BE
 RECIRCULATED FROM THE HAIR SALON TO ADJACENT SPACES VIA
 RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-01-27 Cont ID  
Sent By kstevens Date 2010-01-27 Time 08:56 Rev Time 0.00
Received By kstevens Date 2010-01-27 Time 08:55 Sent To  
Notes
2010-01-27 08:57:35 
  
  
 PASSED/PROVISO:
  
 REVISION REQUIRED...
  
 SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S.
 SECTION 917.3.2.
  
 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF
 THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH
 A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE
 RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION
 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE
 RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR
 OTHER FIXTURES.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-12-22 Cont ID  
Sent By kstevens Date 2009-12-22 Time 08:44 Rev Time 0.00
Received By kstevens Date 2009-12-22 Time 08:44 Sent To  
Notes
2009-12-22 08:49:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLEASE DECLARE THE OCCUPANCY AS REQUIRED IN SECTION
 106.3.5.1.1(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 OCCUPANCY OR USE OF THE TENANT SPACE IS REQUIRED, NOT
 THE OCCUPANCY LOAD.
  
 2. OK
 3. OK
  
 4. SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S.
 SECTION 917.3.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER
 SECTION 917.3.2:
 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF
 THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH
 A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE
 RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION
 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE
 RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR
 OTHER FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-10-29 Cont ID  
Sent By kstevens Date 2009-10-29 Time 16:22 Rev Time 0.00
Received By kstevens Date 2009-10-29 Time 16:22 Sent To  
Notes
2009-10-29 17:02:08DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
  
 1. PLEASE DECLARE THE OCCUPANCY AS REQUIRED IN SECTION
 106.3.5.1.1(2).
  
 2. PLEASE DECLARE THE LEVEL OF ALTERATION. SECTIONS
 403, 404 & 405 OF THE EXISTING BUILDING CODE.
  
 3. THE ADDRESS IN THE TITLE BLOCK OF ALL SHEET EXCEPT
 THE COVER SHEET IS INCORRECT. PLEASE INDICATE THE
 CORRECT ADDRESS. SECTION 106.1.1.
  
 4. SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S.
 SECTION 917.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-11-03 Cont ID  
Sent By aaponte Date 2009-11-03 Time 10:59 Rev Time 0.00
Received By aaponte Date 2009-11-03 Time 10:58 Sent To  
Notes
2009-11-03 10:59:53INTERIOR RENOVATION ONLY. BEAUTY SALON FOR RESIDENTS
 USE ONLY. NO OUTSIDE PUBLIC.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved