| Plan Review Stops For Permit 09100440 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2010-01-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-01-25 |
Time |
09:38 |
Rev Time |
0.66 |
| Received By |
jwitmer |
Date |
2010-01-25 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2010-01-25 09:38:56 | NEW A-2 12/23/09 I SPOKE WITH MARCELL TODAY ABOUT THE | | | ISSUE OF TENANT SEPERATION IN REGARDS TO THE BEAUTY | | | SALON AT MC KEEN TOWERS. MARCEL INDICATED THERE IS NO | | | LEASE, THIS IS A SERVICE STRICTLY FOR THE RESIDENCE AND | | | THE BEAUTY SALON PERSONNEL ARE EMPLOYEES OF THE MC KEEN | | | TOWERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-12-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-23 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-12-23 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2009-12-23 14:46:45 | 12/23/09 I SPOKE WITH MARCELL TODAY ABOUT THE ISSUE OF | | | TENANT SEPERATION IN REGARDS TO THE BEAUTY SALON AT MC | | | KEEN TOWERS. MARCEL INDICATED THERE IS NO LEASE, THIS | | | IS A SERVICE STRICTLY FOR THE RESIDENCE AND THE BEAUTY | | | SALON PERSONNEL ARE EMPLOYEES OF THE MC KEEN TOWERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-22 |
Time |
15:50 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2009-12-22 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2009-12-22 15:59:12 | BUILDING PLAN REVIEW | | | PERMIT: 09100440 | | | ADD: 315 S FLAGLER | | | CONT: J JAY ROTHE INC | | | TEL: (561)389-4137 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | DEC.22/ 2009 | | | | | | 1-3) COMPLIED. | | | | | | 4) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION ON THE | | | NEW TENANT SEPERATION WALL/ CORRIDOR WALLS AND OR | | | OPENING PROTECTIVES, PLEASE PROVIDE ADDITIONAL | | | INFORMATION. FBC 708.1(7) & TABLE 715.4 OPENING | | | PROTECTIVES. THIS ISSUE WAS DISCUSSED WITH THE BUILDING | | | OFFICIAL DOUG WISE AND HE BELIEVES THE 1 HR RATED | | | TENANT SEPERATION WALLS ARE REQUIRED UNLESS THE | | | EXCEPTION OF 3,000 SQ FT OF B OCCUPANCY. | | | | | | 5-7) COMPLIED. | | | | | | 8) NEW COMMENT, THE NOTICE OF COMMENCEMENT WAS RECORDED | | | 9/16/09 AND WILL NEED TO BE RE-RECORDED PER FL S | | | 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. | | | | | | NOTE!!!CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES | | | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR | | | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED | | | THREE | | | OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE | | | VIOLATION. THIS IS TO BE ASSESSED TO THE DESIGNER OF | | | RECORD. PLEASE CONTACT ME IF ANY QUESTIONS ARISE FROM | | | THE COMMENTS OF THIS REVIEW. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-10-26 |
Time |
14:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2009-10-26 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2009-10-26 14:12:56 | BUILDING PLAN REVIEW | | | PERMIT: 09100440 | | | ADD: 315 S FLAGLER | | | CONT: J JAY ROTHE INC | | | TEL: (561)389-4137 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | OCT. 26/ 2009 | | | | | | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC | | | BUILDING WITH 2009 SUPPLEMENTS. | | | | | | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING | | | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO | | | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS | | | PERMIT. | | | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 403, 404 AND 405 OF THIS CODE. | | | PLEASE INDICATE THIS INFORMATION ON THE PLANS. | | | | | | 2) THE PLANS DO NOT PROVIDE ENOUGH INFORMATION FOR A | | | THROUGH REVIEW, PLEASE PROVIDE THE MINIMUM BUILDING | | | TYPE. TABLE 503 & TABLE 601. I BELIEVE THIS IS A | | | HIGHRISE BUILDING OF 11 STORIES OR MORE BEING | | | CONSIDERED A TYPE 1-A BUILDING. | | | | | | 3) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION AS TO THE | | | BUILDING USE OR OCCUPANCY, IT APPEARS TO BE A MIXED USE | | | OCCUPANCY, IS THIS A NONSEPERATED OCCUPANCY IN | | | COMPLIANCE WITH 508.3.2.1 OR SEPERATED OCCUPANCIES IN | | | COMPLIANCE WITH 508.3.3. | | | | | | 4) SHEET A-1 DOES NOT PROVIDE ANY INFORMATION ON THE | | | NEW TENANT SEPERATION WALL/ CORRIDOR WALLS AND OR | | | OPENING PROTECTIVES, PLEASE PROVIDE ADDITIONAL | | | INFORMATION. FBC 708.1(7) & TABLE 715.4 OPENING | | | PROTECTIVES. | | | | | | 5) SHEET A-3 DETAIL B INDICATES THE USE OF WOOD | | | BLOCKING, PLEASE SEE SECTION 603.1 FOR ALLOWABLE | | | MATERIALS. | | | | | | 6) SHEET A-1 INDICATES THE DRINKING FOUNTAIN HAS BEEN | | | RELOCATED PLEASE PROVIDE THE WIDTH OF THE CORRIDOR AS | | | WELL AS THE AT WHAT HEIGHT THE FOUNTAIN IS TO BE | | | INSTALLED, PROVIDE BOTH THE TOP AND BOTTOM OF THE WATER | | | FOUNTAIN. 1017.2 MINIMUM CORRIDOR WIDTH, 11-4.4.1 | | | PROTRUDING OBJECTS, & 11-4.15.5 CLEARENCES. | | | | | | 7) IT APPEARS THERE IS A TYPO ON ALL THE SHEETS BEING | | | THE ADDRESS AT 15 S FLAGLER, PLEASE CORRECT TO 315 S | | | FLAGLER AND SUITE NUMBER . | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES | | | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER | | | NOTICE. | | | | | | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM | | | - 5:00 PM. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2010-01-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-01-28 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-01-28 |
Time |
10:43 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-12-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-12-22 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-12-22 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2009-12-22 13:18:15 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE | | | PREVIOUS REVIEW. | | | | | | 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED | | | BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE | | | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL | | | LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE | | | READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE | | | THE CONTROLLED LIGHTING | | | | | | 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE | | | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A | | | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD | | | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR | | | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING | | | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN | | | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING | | | POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH | | | SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS | | | INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR | | | THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. | | | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE | | | WITH THE ONES IN THE CALCULATIONS. | | | | | | NOTE : THE FIXTURE SCHEDULE ON SHEET E-1 DOES NOT | | | CORRELATE WITH THE SCHEDULE ON SHEET A-2. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-10-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-10-29 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-10-27 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2009-10-27 15:57:03 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING | | | | | | 1} 401.4 FBC EXISTING BUILDING CODE. THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE | | | PLAN. | | | | | | 2} 302.1 GENERAL. STRUCTURES OR PORTIONS OF STRUCTURES | | | SHALL BE CLASSIFIED WITH RESPECT TO OCCUPANCY------, | | | INDICATE SAME ON THE PLAN, ALSO INDICATE IF THIS IS A | | | CHANGE OF OCCUPANCY PER CHAPTER 9 EXISTING BUILDING | | | CODE FBC 2007. | | | | | | 3} PANEL"A" IS LOCATED IN A STORAGE CLOSET WHICH MAY BE | | | IN VIOLATION OF 110.26 FOR CLEARANCES IT STORED ITEMS | | | ARE IN THE REQUIRED FREE SPACE, AND 240.24 (D) NOT IN | | | VICINITY OF EASILY IGNITIBLE MATERIAL OVERCURRENT | | | DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY | | | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS, AND | | | WOUD ALSO BE A VIOLATION IF CHEMICALS ARE STORED IN | | | THIS SPACE. A SAFER LOCATION WOUD BE ON THE WALL | | | OUTSIDE AND ADJACENT TO THE CLOSET | | | | | | 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED | | | BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE | | | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL | | | LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE | | | READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE | | | THE CONTROLLED LIGHTING | | | | | | 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE | | | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A | | | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD | | | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR | | | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING | | | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN | | | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING | | | POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH | | | SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS | | | INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR | | | THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. | | | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE | | | WITH THE ONES IN THE CALCULATIONS. | | | | | | 6} THE ADDRESS IN THE TITLE BLOCK, SHEET E-1IS | | | INCORRECT. PLEASE INCLUDE THE ADDRESS AND SUITE/UNIT | | | NUMBER OF THE PROJECT ON THE PLANS PER 106.1.1 FBC AS | | | AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-12-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-12-21 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-12-21 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2009-12-21 16:05:33 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | | ADDRESSED; PLAN SHEETS A-1, A-2, E-1, AND FS-1 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-11-16 |
Time |
|
Rev Time |
|
| Received By |
mawillia |
Date |
2009-11-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2009-11-16 19:11:42 | *****DENIED***** | | | | | | 1. INDICATE THE TYPE OF OCCUPANCY AND THE OCCUPANT LOAD | | | FOR THIS PROJECTED SITE. | | | | | | 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 3. IT IS INDICATED THAT THE TENANT SPACE IS/WILL BE | | | LOCATED ON THE SECOND FLOOR. WILL A SUITE NUMBER BE | | | ASSIGNED TO THIS TENANT SPACE FOR BETTER LOCATING THE | | | PREMISE? IF SO, THE SUITE NUMBER SHALL BE INCLUDED IN | | | THE ADDRESS. | | | | | | 4. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 5. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 6. AS WAS DONE FOR THE NEW CEILINGS, SPECIFY THE | | | INTERIOR FINISH MATERIAL FOR THE WALLS IN TERMS OF | | | CLASS A, CLASS B, OR CLASS C. | | | | | | 7. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL | | | DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-01-27 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-01-19 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-01-19 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2010-01-21 10:15:46 | TO B-22 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-12-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-12-14 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-12-14 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-11-17 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-26 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2009-10-26 10:43:18 | SENT TO BOB #B8. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-12-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-12-21 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-12-21 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-11-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-11-04 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-11-04 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2009-11-04 10:43:42 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLAN HAS TWO EXHAUST FAN SCHEDULES. ONE FOR A | | | "NUTONE" 50 CFM FAN AND ONE FOR A "GREENHECK" 70 CFM | | | FAN. THERE IS ONLY ONE EF-1 SHOWN ON THE PLANS. PLEASE | | | COORDINATE FLOOR PLAN AND EQUIPMENT SCHEDULES IN | | | ACCORDANCE WITH FBC-M 304.1 AND 304.11. SEE ALSO NEXT | | | COMMENT REGARDIN REQUIRED EXHAUST RATES. | | | | | | 2. PLAN SHOWS EITHER 50 OR 70 CFM OF EXHAUST FOR THE | | | BEAUTY SALON. PER ASHRAE 62.1-2004 TABLE 6-4, THE | | | REQUIRED EXHAUST RATE FOR THIS SPACE IS 0.12 CFM/SQ. | | | FT. FOR A TOTAL OF 205 CFM. PROVIDE THE MINIMUM EXHAUST | | | RATE AS REQUIRED PER THIS SECTION. | | | | | | 3. THE VENTILATION RATE DOES NOT MEET THE MINIMUM | | | VENTILATION RATE AS REQUIRED PER ASHRAE 62.1-2004 TABLE | | | 6-1. THE MINIMUM VENTILATION RATE FOR A HAIR AND NAIL | | | SALON OF 342 SQ.FT. WOULD BE APPROX 220 CFM. SHOW HOW | | | 220 CFM OF OUTDOOR AIR IS TO BE PROVIDED TO THIS SPACE | | | IN ACCORDANCE WITH THIS SECTION AND FBC-M 403.4. | | | | | | 4. HAIR SALON IS GIVEN AN AIR CLASSIFICATION OF 2. WHAT | | | IS THE AIR CLASSIFICATION OF THE SURROUNDING SPACES? | | | DECLARE THIS CLASSIFICATION ON PLANS WITH JUSTIFICATION | | | IN ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 5.17.4. AT | | | THIS TIME IT IS NOT CLEAR WHETHER AIR CAN BE | | | RECIRCULATED FROM THE HAIR SALON TO ADJACENT SPACES VIA | | | RETURN AIR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2010-01-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2010-01-27 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2010-01-27 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2010-01-27 08:57:35 | | | | | | | | | | PASSED/PROVISO: | | | | | | REVISION REQUIRED... | | | | | | SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S. | | | SECTION 917.3.2. | | | | | | 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS | | | LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF | | | THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH | | | A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR | | | STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE | | | RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | | DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE | | | DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE | | | RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION | | | 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE | | | RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR | | | OTHER FIXTURES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-12-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-12-22 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-12-22 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2009-12-22 08:49:35 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 EXISTING BUILDING | | | FBC-2007 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. PLEASE DECLARE THE OCCUPANCY AS REQUIRED IN SECTION | | | 106.3.5.1.1(2). | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE | | | OCCUPANCY OR USE OF THE TENANT SPACE IS REQUIRED, NOT | | | THE OCCUPANCY LOAD. | | | | | | 2. OK | | | 3. OK | | | | | | 4. SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S. | | | SECTION 917.3.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER | | | SECTION 917.3.2: | | | 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS | | | LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF | | | THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH | | | A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR | | | STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE | | | RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | | DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE | | | DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE | | | RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION | | | 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE | | | RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR | | | OTHER FIXTURES. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-29 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-10-29 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2009-10-29 17:02:08 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 EXISTING BUILDING | | | FBC-2007 CHAPTER 1 | | | | | | 1. PLEASE DECLARE THE OCCUPANCY AS REQUIRED IN SECTION | | | 106.3.5.1.1(2). | | | | | | 2. PLEASE DECLARE THE LEVEL OF ALTERATION. SECTIONS | | | 403, 404 & 405 OF THE EXISTING BUILDING CODE. | | | | | | 3. THE ADDRESS IN THE TITLE BLOCK OF ALL SHEET EXCEPT | | | THE COVER SHEET IS INCORRECT. PLEASE INDICATE THE | | | CORRECT ADDRESS. SECTION 106.1.1. | | | | | | 4. SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S. | | | SECTION 917.3.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-11-03 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2009-11-03 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2009-11-03 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2009-11-03 10:59:53 | INTERIOR RENOVATION ONLY. BEAUTY SALON FOR RESIDENTS | | | USE ONLY. NO OUTSIDE PUBLIC. |
|
|