Plan Review Details - Permit 09100416
Plan Review Stops For Permit 09100416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-11-05 Time 16:37 Rev Time 0.55
Received By jwitmer Date 2009-11-05 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By jwitmer Date 2009-10-26 Time 17:00 Rev Time 2.50
Received By jwitmer Date 2009-10-26 Time 14:38 Sent To  
Notes
2009-10-26 17:07:48BUILDING PLAN REVIEW
 PERMIT: 09100416
 ADD: 22420 MEDINA WAY
 CONT: D & A BUILDERS
 TEL: (561)662-6226
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT. 26/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 RESIDENTIAL WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
 PLEASE UPDATE PLANS.
  
 2) MISSING WIND DSIGN INFO:
 1603.1.4 WIND DESIGN DATA./ R301.2.1.3 -R301.2.1.5
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.PLEASE REVIEW SECTION
 R-3012.1.4(3) EXPOSURE "C" REQUIREMNTS.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLANS A-02 ARE LACKING THE WIND DESIGN PRESSURE FOR
 THE NEW WINDOW OPENING AS WELL AS NEW DOUBLE EXTERIOR
 DOOR LOCATED IN STUDY.
  
 4) THE NEW EXTERIOR DOUBLE DOOR OPENING AT THE STUDY
 ALSO IS MISSING PRODUCT APPROVALS REQUIRED BY RULE
 9B-72(31)( A) AND R-301.2.1.2.
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SHEET A-203 THE NEW MASTER BATHROOM AND WHIRLPOOL
 TUB IS LOCATED NEXT TO AN EXISTING WINDOW, THE NEW TUB
 HAS CREATED A HAZARDOUS LOCATION SEE R308.4(5).
  
 7) SHEET A-01 INDICATES REMODELING OF THE RESTROOM
 UNDER THE STAIRWELL, PLEASE PROVIDE COMPLIANCE WITH
 R311.2.2 UNDER STAIR PROTECTION. ENCLOSED ACCESSIBLE
 SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER STAIR
 SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE
 WITH 1/2-INCH (13 MM) GYPSUM BOARD.
  
 8) BUILDING PROVISO: THE NEW MASTER BEDROOM EGRESS
 WINDOW MUST MAINTAIN A CLEAR VENT SIZE OF 5.7 SQ FT, A
 245 WINDOW MAY MAKE OR MAY NOT MAKE THE CLEAR REQUIRED
 VENT SIZE DEPENDING ON THE SASH SIZE! R310.1.1
 R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.530 M2).
  
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
  
 R310.1.2 MINIMUM OPENING HEIGHT. THE MINIMUM NET CLEAR
 OPENING HEIGHT SHALL BE 24 INCHES (610 MM).
  
 R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR
 OPENING WIDTH SHALL BE 20 INCHES (508 MM).
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-11-05 Time 16:37 Rev Time 0.55
Received By jwitmer Date 2009-11-05 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By jwitmer Date 2009-11-03 Time 06:38 Rev Time 2.20
Received By jwitmer Date 2009-11-02 Time 09:52 Sent To  
Notes
2009-11-02 14:40:45RESIDENTIAL ELECTRICAL PLAN REVIEW
 PERMIT: 09100416/ 09100417
 ADD: 2420 MEDINA WAY
 CONT: D&A BUILDERS/ ELECTRICAL EXPRESS
 TEL: (561)662-6226
  
 1A) PLANS SUBMITTED AFTER OCT. 1/ 2009 SHALL BE
 DESIGNED TO THE 2008 NEC.
  
 1B) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
 FOR THIS REVIEW A LEVEL 2 ALTERATION WAS CONSIDERED
 EITHER DELETING OR EXTENDING SYTEMS.
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING KITCHEN
 COUNTERSPACE AS GFI/GFI PROTECTED AS REQUIRED PER
 210.8A-6 PLANS DO NOT INDICATE COMPLIANCE IF EXISTING
 INDICATE AS SUCH..
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. ON EACH LEVEL OF A
 MULTI-LEVEL DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING TO FLOORS ABOVE
 AND IN THE VICINITY OF BEDROOMS. PLEASE ALSO NOTE, SD'S
 ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND KITCHENS. ABOVE
 PER:FBC 905.2, NFPA-72 8-1.4
  
 4) ARC FAULT PROTECTION PROTECTION IS NOW REQUIRED IN
 RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH
 CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED
 BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER
 120 VOLTS 2110.12(B)
  
 5) MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON
 GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 6) 2008 NEC-NEW OCCUPIABLE BALCONIES AND PORCHES OVER
 20 SQ FT MUST NOW HAVE A RECEPTACLE OUTLET (GFCI
 PROTECTED) (210.52(E)(3).
  
 7) IN NEITHER THE BATHROOMS OR HALF BATHS DO THE PLANS
 INDICATE GFIC OUTLETS. BATHROOM GFIC OUTLET PLANS FAIL
 TO INDICATE COMPLIANCE WITH SECTION 210.11 (C)(3)
 BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S).
  
 8) PLEASE REVIEW THE MASTER BEDROOM CLOSET CEILING
 FIXTURE LOCATION AS WELL AS THE GUEST ROOM# 1 CLOSET
 CEILINF FIXTURE. SEE 410.16(C) (1-5) & 410.16.2
 DEFINITION.
  
 9) NOTE: PLEASE SEE MISSING RECEPTS FOR FRONT AND/OR
 REAR OF DWELLING. 210.52E/ EXISTING BUILDING CODE
 708.3.5 MINIMUM LIGHTING OUTLETS. AT LEAST ONE LIGHTING
 OUTLET SHALL BE PROVIDED WITH ELECTRIC POWER, TO
 ILLUMINATE OUTDOOR ENTRANCES AND EXITS.
  
 10) NOTE: PLEASE SEE MISSING RECEPT REQ'D FOR A/C
 EQUIPMENT. 210.63
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-11-05 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2009-11-04 Time 10:29 Sent To  
Notes
2009-11-05 16:38:25APPROVED SEE STAMP ON PLANS JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-05 Cont ID  
Sent By kstevens Date 2009-11-05 Time 10:44 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 10:44 Sent To  
Notes
2009-11-05 10:46:44SENT TO KSTEVENS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-03 Cont ID  
Sent By jwitmer Date 2009-11-03 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2009-10-22 Time 10:55 Sent To  
Notes
2009-10-22 11:05:44SENT TO R-6.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-11-02 Cont ID  
Sent By jwitmer Date 2009-11-02 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2009-11-02 Time 14:17 Sent To  
Notes
2009-11-02 14:18:26NO MECHANICAL INFORMATION SUPPLIED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-10-27 Cont ID  
Sent By kstevens Date 2009-10-27 Time 15:40 Rev Time 0.00
Received By kstevens Date 2009-10-27 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-10-30 Cont ID  
Sent By eschneid Date 2009-10-30 Time 17:25 Rev Time 0.25
Received By eschneid Date 2009-10-30 Time 17:25 Sent To  
Notes
2009-10-30 17:26:16NO EXTERIOR ENLARGEMENT, LESS THAN 50% VALUE.