Plan Review Details - Permit 09100337
Plan Review Stops For Permit 09100337
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-10 Cont ID  
Sent By shill Date 2009-12-10 Time 09:42 Rev Time 0.00
Received By shill Date 2009-12-10 Time 09:42 Sent To  
Notes
2009-12-10 09:43:14***PROVISO****
 ISSUED AT CONTRACTOR'S RISK
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 REVISE PLANS TO INCLUDE THE FOLLOWING INFORMATION:
  
 1. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED
 IMPROVEMENT IN RELATION TO THE PROPERTY LINE, FBC R301.
 A COPY OF A SURVEY WAS SUBMITTED. PLEASE SHOW LOCATION
 OF PROPOSED IMPROVEMENT AND INCLUDE "SUN DECK" WITH
 DIMENSIONS (OVERALL SIZE AND DISTANCE TO PROPERTY
 LINES).
  
 2. DECLARE WIND DESIGN CRITERIA FBC R 301; DECLARE WIND
 SPEED FBC R301.2.1 (MINIMUM 140MPH), EXPOSURE CATEGORY
 (APPEARS TO BE EXPOSURE C). ALSO PROVIDE BUILDING
 HEIGHT SO THAT COMPONENTS & CLADDING DESIGN PRESSURES
 CAN BE DETERMINED.
  
 3. INFORMATION REGARDING THE ROOF WAS NOT PROVIDED. IF
 THIS IS AN EXISTING ROOF, PLEASE NOTE ON PLANS.
  
 4. PROVIDE ELEVATION DESIGNATIONS (N,S,E OR W). PROVIDE
 COMPASS NORTH ON THE SITE PLAN. FBC*106, FBC301.
  
 5. HOW WILL THE BLOCK INFILL TIE IN STRUCTURALLY TO THE
 EXISTING? SEE FBC R301.1, ALL PARTS SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS.
  
 6. HOW HAVE YOU DETERMINED THAT THE FOOTER SIZE IS
 ADEQUATE?
  
 7. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT (IF FEES ARE DUE)
 IS TO BE ATTACHED TO THE APPLICATION.
  
 8. WILL THIS AREA BE AIR CONDITIONED? ENERGY CALCS MAY
 BE REQUIRED FBC R11.
  
 9. PLEASE REVISE THE PLAN TO SHOW THAT THE MASTER
 BEDROOM EMERGENCY EGRESS IS NOT AFFECTED BY THE
 PROPOSED IMPROVEMENT, FBC R310 (YOU MAY DO THIS BY
 NOTING LOCATION OF MASTER BEDROOM EMERGENCY EGRESS ON
 THE PLAN).
  
 10. PHOTOGRAPHS WERE INCLUDED IN THE PLANS. SEE
 FBC*106, PLANS ARE TO BE ARCHITECTURAL QUALITY, TO
 SCALE. PHOTOGRAPHS SHOULD NOT BE USED TO SHOW CODE
 COMPLIANCE. PLEASE INCORPORATE ANY REQUIRED INFORMATION
 INTO THE PLAN.
  
 11.PORTIONS OF TWO DIFFERENT DOOR PRODUCT APPROVALS
 WERE PROVIDED. OTHER SHEETS STAPLED WITH THE ANCHOR
 EVALUATION REPORT WERE SPEC SHEETS FOR WINDOWS, DOORS,
 WINDOW INSTALLATION INFORMATION. PLEASE INCLUDE THE
 FLORIDA STATE PRODUCT APPROVAL COVER SHEET (SHOWS CODE
 VERSION, STATUS). FAC0B72. PLEASE PRINT THE COVER
 SHEET, EVALUATION REPORT, INSTALLATION INSTRUCTIONS FOR
 THE PRODUCT YOU WISH TO INSTALL. (PARTS OF FL8838,
 FL5262 INCLUDED, PLEASE SELECT ONE AND PRINT REQUIRED
 DOCUMENTS.)
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By shill Date 2009-12-02 Time 09:32 Rev Time 0.00
Received By shill Date 2009-12-02 Time 09:32 Sent To  
Notes
2009-12-02 10:46:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED
 IMPROVEMENT IN RELATION TO THE PROPERTY LINE, FBC R301.
 A COPY OF A SURVEY WAS SUBMITTED. PLEASE SHOW LOCATION
 OF PROPOSED IMPROVEMENT AND INCLUDE "SUN DECK" WITH
 DIMENSIONS (OVERALL SIZE AND DISTANCE TO PROPERTY
 LINES).
  
 2. DECLARE WIND DESIGN CRITERIA FBC R 301; DECLARE WIND
 SPEED FBC R301.2.1 (MINIMUM 140MPH), EXPOSURE CATEGORY
 (APPEARS TO BE EXPOSURE C). ALSO PROVIDE BUILDING
 HEIGHT SO THAT COMPONENTS & CLADDING DESIGN PRESSURES
 CAN BE DETERMINED.
  
 3. INFORMATION REGARDING THE ROOF WAS NOT PROVIDED. IF
 THIS IS AN EXISTING ROOF, PLEASE NOTE ON PLANS.
  
 4. PROVIDE ELEVATION DESIGNATIONS (N,S,E OR W). PROVIDE
 COMPASS NORTH ON THE SITE PLAN. FBC*106, FBC301.
  
 5. HOW WILL THE BLOCK INFILL TIE IN STRUCTURALLY TO THE
 EXISTING? SEE FBC R301.1, ALL PARTS SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS.
  
 6. HOW HAVE YOU DETERMINED THAT THE FOOTER SIZE IS
 ADEQUATE?
  
 7. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. THE
 PLANS MUST BE STAMPED AND THE RECEIPT (IF FEES ARE DUE)
 IS TO BE ATTACHED TO THE APPLICATION.
  
 8. WILL THIS AREA BE AIR CONDITIONED? ENERGY CALCS MAY
 BE REQUIRED FBC R11.
  
 9. PLEASE REVISE THE PLAN TO SHOW THAT THE MASTER
 BEDROOM EMERGENCY EGRESS IS NOT AFFECTED BY THE
 PROPOSED IMPROVEMENT, FBC R310 (YOU MAY DO THIS BY
 NOTING LOCATION OF MASTER BEDROOM EMERGENCY EGRESS ON
 THE PLAN).
  
 10. PHOTOGRAPHS WERE INCLUDED IN THE PLANS. SEE
 FBC*106, PLANS ARE TO BE ARCHITECTURAL QUALITY, TO
 SCALE. PHOTOGRAPHS SHOULD NOT BE USED TO SHOW CODE
 COMPLIANCE. PLEASE INCORPORATE ANY REQUIRED INFORMATION
 INTO THE PLAN.
  
 11.PORTIONS OF TWO DIFFERENT DOOR PRODUCT APPROVALS
 WERE PROVIDED. OTHER SHEETS STAPLED WITH THE ANCHOR
 EVALUATION REPORT WERE SPEC SHEETS FOR WINDOWS, DOORS,
 WINDOW INSTALLATION INFORMATION. PLEASE INCLUDE THE
 FLORIDA STATE PRODUCT APPROVAL COVER SHEET (SHOWS CODE
 VERSION, STATUS). FAC0B72. PLEASE PRINT THE COVER
 SHEET, EVALUATION REPORT, INSTALLATION INSTRUCTIONS FOR
 THE PRODUCT YOU WISH TO INSTALL. (PARTS OF FL8838,
 FL5262 INCLUDED, PLEASE SELECT ONE AND PRINT REQUIRED
 DOCUMENTS.)
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 14:50 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 14:42 Sent To  
Notes
2009-11-03 14:48:14 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 210.52(A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
 (1) SPACING RECEPTACLES SHALL BE INSTALLED SO THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET.
  
 2} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED. PLANS INDICATING THE SCOPE OF WORK MUST BE
 SUBMITTED WITH THE APPLICATION. 106.1 FBC AS AMENDED.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-02 Cont ID  
Sent By shill Date 2009-12-02 Time 10:46 Rev Time 0.00
Received By shill Date 2009-10-20 Time 16:54 Sent To  
Notes
2009-10-20 16:55:00R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By shill Date 2009-12-10 Time 09:43 Rev Time 0.00
Received By shill Date 2009-12-10 Time 09:43 Sent To  
Notes
2009-12-10 09:43:40IMPACT FEE ASSESSMENT FROM COUNTY REQUIRED PRIOR TO
 PERMIT ISSUANCE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By astelly Date 2009-11-24 Time 17:07 Rev Time 0.00
Received By astelly Date 2009-11-24 Time 17:11 Sent To M
Notes
2009-11-24 17:10:59AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SITE PLANS AND FLOOR PLAN WHICH SHOW
 THE SCOPE OF WORK.