Plan Review Details - Permit 09100323
Plan Review Stops For Permit 09100323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 18:40 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By jwitmer Date 2009-10-20 Time 07:38 Rev Time 2.00
Received By jwitmer Date 2009-10-20 Time 07:03 Sent To  
Notes
2009-10-20 07:55:38BUILDING PLAN REVIEW
 PERMIT: 09100323
 ADD: 401 NORTHWOOD RD
 CONT: G. FLEWELLING CONSTRUCTION
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT. 20/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 1B) ADDITIONAL INFORMATION REQUIRED106.1.2, IS THIS A
 CHANGE IN OCCUPANCY?
  
 2) SHEET A-1;
  
 2A) PLANS DO NOT INDICATE WHAT WALLS ARE EXISTING AND
 WHAT WALLS ARE NEW. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. IT APPEARS THERE IS A SHARED EXIT ACCESS
 CORRIDOR SHARED BY A MINIMUM OF TWO TENANTS,( 2007
 EXIST BLDG CODE 705.2 EXCEPTION 2) THE NEW OPENING FROM
 THIS TENANT SPACE DOES NOT INDICATE IF THE CORRIDOR
 CONTINUES TO A THIRD TENANT. IF SO PLEASE REVIEW
 SECTION 1005 .2 OF THE FBC. DOOR ENCROACHMENT.
  
 2B) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 OBJECT (2'-0"X 5'-6") DIRECT IN FRONT OF THE RESTROOMS
 IT APPEARS TO BE BLOCKING THE EGRESS PATH. 11-4.3.3
 THTE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE ROUTE IS
 36".11-5.3.
  
 2C) PLEASE PROVIDE COMLIANCE WITH :11-5.1 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18).
  
 2D) SHEET A-1 DOES NOT PROVIDE A DETAIL FOR THE FRONT
 ENTRY PROVIDING EGRESS FOR HANDICAPPED PATRONS.
 11-4.1.6 (2) (A)(I) AN ACCESSIBLE ENTRANCE.
  
 2E) THE NEW EXIT ACCESS DOOR LEADING INTO THE COORIDOR
 IS INDICATED AS A "C" RATED DOOR, PLEASE REVIEW OPENING
 PROTECTIVES TABLE 715.4, OPENING PROTECTION IS IN HOURS
 AND MINUTES.
  
 3) SHEET M-1 INDICATES THE A/C CONDENSORS AND COOLER
 CONDENSOR TO BE LOCATED ON THE ROOF:
  
 3A) PRE-MANUFACTURED A/C STANDS: 06.3 PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL, RULE 9B-72(C)(G). PLEASE PROVIDE PRODUCT
 APPROVALS (2 COPIES) FOR A/C STAND.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3C) ALL ROOFTOP EQUIPMEN NEEDS TO INDICATE COMPLIANCE
 WITH, 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. THIS IS THE EQUIPMENT EXTERIOR SHELL AS
 WELL AS THE TIE DOWN TO THE A/C STAND AS WELL AS THE
 HOOD EXHAUST DUCT AND EXHAUST FAN.
  
 3D) THE INTAKE DUC , WALL LOUVER WILL ALSO NEED TO
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR WIND, RULE
 9B-72#1)(C).
  
 4) NOTE ENERGY CALCULATION METHOD "A" NOT REQUIRED BY
 BUILDING , NOT REVIEWED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-16 Cont ID  
Sent By btrobaug Date 2009-11-16 Time 12:32 Rev Time 0.00
Received By btrobaug Date 2009-11-16 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By btrobaug Date 2009-10-26 Time 17:41 Rev Time 0.00
Received By btrobaug Date 2009-10-26 Time 11:59 Sent To  
Notes
2009-10-26 17:35:54 
  
 APPLICATION #09100323 ELECTRICAL PLAN REVIEW
 403 NORTHWOOD ROAD 10/26/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE INDICATE THE CODE CYCLE THIS PROJECT WAS
 DESIGNED UNDER. 2005 NEC, 2006 NFPA 101 ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 2} SHEET E-1 ROOF POWER PLAN DOES NOT INDICATE THE
 RECEPTACLE REQUIRED BY 210.63, LOCATE SAME ON PLAN.
  
 3} NOTE #1 INCORRECTLY SITES 210.8(B)(3), SHOULD SITE
 210.8(B)(2).
  
 4}THE LIGHTING DENSITY CALCULATIONS SHEET E-2, SITE
 TABLE 415.2.B, THAT IS A REFERENCE FROM THE 2004 FBC.
 THE 2007 FBC IS CURRENT AND 415.B.1 IS THE TABLE
 CURRENTLY BEING USED, CORRECT SAME.
  
 5} SHEET E-2 FIXTURE LEGEND SCHEDULE NOTE #3
 INCORRECTLY 410.73(G), THIS ARTICLE IS FROM THE 2005
 NEC, THE CURRENT 2008 ARTICLE IS 410.130(G)(1), PLEASE
 CORRECT AND CHECK ALL NOTES AND REFERENCES FOR THE
 CORRECT CODE CYCLES.
  
 6} THE RISER DIAGRAM LEGEND ON SHEET E-3 LISTS THE
 PANELS AS BEING 277/480 VOLTS IN VIOLATION OF 110.3(B).
 THE SERVICE IS 120/208 VOLTS.
  
 7} NOTE # 28 REFERS SHEET E-3SPECIFICATIONS TO 480 VOLT
 DELTA SYSTEM COLOR CODE, THE SERVICE IS A 120/208 Y,
 CORRECT NOTE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER,CITY OF WEST PALM
 BEACH/561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-10 Cont ID  
Sent By mawillia Date 2009-11-10 Time 10:33 Rev Time 0.00
Received By mawillia Date 2009-11-10 Time 10:06 Sent To  
Notes
2009-11-10 10:32:57*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1, E-2, AND FA-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 11:48 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 10:44 Sent To  
Notes
2009-10-26 11:47:20*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHAL;L COMPLY WITH NFPA 241 -
 2004 EDITION.
  
 2. THE ADDRESS LISTED IN THE SUBMITTED PLANS (403
 NORTHWOOD ROAD) DO NOT CORRELATE WITH THAT LISTED ON
 THE APPLICATION AND/OR IN OUR PERMITTING SYSTEM (401
 NORTHWOOD ROAD). THE ACTUAL PROJECT SITE ADDRESS SHALL
 BE INCLUDED IN THE TITLE BLOCK OF EACH SUBMITTTED PLAN
 SHEET.
  
 3. THE 2006 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 4. THE WIDTH OF ANY EXIT ACCESS CORRIDOR SERVING 50 OR
 MORE PERSONS SHALL NOT BE LESS THAN 44 INCHES.
  
 5. THE WIDTH OF AISLE SERVING SEATING AST TABLESSHALL
 NOT BE LESS THAN 44 INCHES WHERE SERVING AN OCCUPANT
 LOAD OF EXCEEDING 50 PERSONS.
  
 6. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR
 CLASS II.
  
 7. SHOW THE LOCATION OF THE FIRE EXTINGUISHERS WHICH
 SATISFY THE 75' TRAVEL DISTANCE.
  
 8. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS. THESE
 MAY BE SHOWN ON THE CEILING PLAN (SHEET A-4).
  
 9. ON SHEET A-1, THERE APPEARS TO BE TWO WEST DOORS
 THAT ACCESS THE EXISTING EXIT CORRIDOR, HOWEVER ONLY
 ONE SUCH DOOR IS SHOWN ON SHEET E-2. PLEASE EXPLAIN.
  
  
 TO EXPEDIT THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By kstevens Date 2009-11-09 Time 17:55 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 16:59 Sent To  
Notes
2009-11-09 17:56:31 
  
  
 PASSED/PROVISO:
  
 MANUFACTURE SHEETS REQUIRED AT TIME OF GAS PERMIT
 APPLICATION.
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-10-27 Cont ID  
Sent By kstevens Date 2009-10-27 Time 08:16 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 18:58 Sent To  
Notes
2009-10-27 08:23:17DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- NOT ALL SECTIONS INDICATE CUT
 SECTIONS. SEE HORIZONTAL SECTION FROM METER, FIRST
 VERTICAL RISER, SECTION AFTER FIRST TEE TO OVEN AND
 SECTION AFTER SECOND TEE TO FRYERS & RANGE, OFFSET &
 DROP TO WATER HEATER, SECTIONS BETWEEN FRYERS & BETWEEN
 LAST FRYER & RANGE & OFFSET & DROP TO THE OVEN.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT NUMBER ONE IS ADDRESSED.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 4. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-04 Cont ID  
Sent By lmartine Date 2009-11-03 Time 08:56 Rev Time 0.00
Received By lmartine Date 2009-11-03 Time 08:56 Sent To  
Notes
2009-11-04 09:07:31C--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-27 Cont ID  
Sent By kstevens Date 2009-10-27 Time 08:23 Rev Time 0.00
Received By kstevens Date 2009-10-19 Time 11:52 Sent To  
Notes
2009-10-19 11:58:24C--4
 $$ EXPEDITED $$

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-11-18 Cont ID  
Sent By lmartine Date 2009-11-18 Time 10:56 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 10:56 Sent To  
Notes
2009-11-18 10:57:41EXISTING USE CREDIT SEE PLANS AND RECEIPT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-11-17 Cont ID  
Sent By rregueir Date 2009-11-17 Time 11:28 Rev Time 0.00
Received By rregueir Date 2009-11-17 Time 10:13 Sent To PC
Notes
2009-11-17 11:24:06***PROVISO***
 1. REVISION REQUIRED: PROVIDE MOTIRIZED AND GRAVITY
 OPERATED (BACKDRAFT) DAMPERS AS NECESSARY TO ENSURE ALL
 REQUIRED OUTDOOR AIR FOR KSF-1 AND BOTH AIR HANDLERS IS
 BEING SUPPLIED ONLY FROM OUTDOORS RATHER THAN FROM
 INDOORS THROUGH OTHER ATTACHED DUCTS. ALL VENTILATION
 AIR SHALL BE DIRECTLY FROM THE OUTDOORS IN ACCORDANCE
 WITH FBC-M 401.4 AND FBC-M 403.2.
  
 2. REVISION REQUIRED: PROVIDE MANUFACTURER'S WIND
 RESISTANCE DATA FOR ALL APPLIANCES EXPOSED TO WIND IN
 ACCORDANCE WITH FBC-M 301.12.
  
 3. PAGE M-3: CENTRIFUGAL KITCHEN EXHAUST FAN SHALL BE
 ORIENTED TO DISCHARGE VERTICALLY IN ACCORDANCE WITH
 FBC-M 506.3.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By rregueir Date 2009-10-26 Time 19:31 Rev Time 0.00
Received By rregueir Date 2009-10-26 Time 17:41 Sent To  
Notes
2009-10-26 19:31:17REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR INTAKES FOR AIR HANDLERS AND KSF-1 ARE
 FACING AN ALLEY. MECHANICAL OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS
 STREETS, ALLEYS AND PARKING LOTS AND LOADING DOCKS IN
 ACCORDANCE WITH FBC-M 401.4.1. SELECT AN ALTERNATE
 LOCATION WHICH MEETS THE REQUIREMENTS OF THIS SECTION.
  
 2. FLOOR PLANS SHOW A 20X20 HOOD SUPPLY, 14X14 OUTSIDE
 AIR, 6 INCH ROUND EXHAUST AND 4 INCH ROUND FLUE
 PENETRATING A FIRE-RESISTANCE RATED WALL ASSEMBLY WITH
 NO PROTECTION. SHOW HOW THESE DUCT PENETRATIONS OF THE
 RATED WALL ARE TO BE PROTECTED IN ACCORDANCE WITH FBC-M
 607.5, FBC-M 607.8 AND FBC-FG 302.2.
  
 3. A METHOD A CODE COMPLIANCE FORM HAS BEEN SUBMITTED.
 HOWEVER, IF THIS SCOPE OF WORK DOES NOT CONSTITUTE A
 RENOVATION (SEE DEFINITIONS FBC-B SECTION 13-202) THEN
 DEMONSTRATION OF COMPLIANCE WITH FBC-B 13-101.6 IS
 REQUIRED WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED
 IN EXISTING BUILDINGS. ALTERNATIVELY, IF THIS SCOPE OF
 WORK CONSTITUTES A CHANGE OF OCCUPANCY (THERE IS NO
 INDICATION ON PLANS OR PERMIT APPLICATION), THIS WORK
 SHALL MEET THE REQUIREMENTS FOR RENOVATIONS IN SECTION
 101.1.3 FOR THOSE COMPONENTS WHICH ARE BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.3.1.
  
 4. PAGE M-1 SHOWS NEW CONDENSERS ON STANDS TO BE
 INSTALLED ON THE ROOF. NO INFORMATION WAS PROVIDED
 REGARDING THE STANDS OR THE INSTALLATION OF THE NEW
 APPLIANCES FOR WIND RESISTANCE. IF PRE-ENGINEERED A/C
 STANDS ARE USED, SUBMIT PRODUCT APPROVALS FOR THE
 STANDS IN ACCORDANCE WITH FBC-B 106.3.3. ALSO, PROVIDE
 PRODUCT APPROVAL FOR WALL LOUVERS PER THIS SECTION
 UNLESS THE LOUVER IS ELIMINTAED IN CONJUNCTION WITH
 COMMENT #1 ABOVE.
  
 5. PROVIDE MANUFACTURER'S DATA SHOWING ALL OUTDOOR
 APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. WHEN APPLYING FOR
 SEPARATE HOOD PERMIT, INCLUDE WIND RESISTANCE DATA FOR
 KITCHEN EXHAUST FAN AND ENGINEERED INSTALLATION DETAILS
 FOR THE FAN AND EXTERIOR DUCT SUPPORTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By kstevens Date 2009-11-09 Time 17:05 Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 16:59 Sent To  
Notes
2009-11-09 17:25:18 
  
 PASSED/PROVISO
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT
 WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS
 INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT
 LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY
 ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON
 THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT
 EACH OTHER. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. SHT P-1 SHOWS 2
 NUMBER 27'S THAT ARE INDICATED AS TURBO-FLOW CONVECTION
 OVENS ON SHT A-2 BUT INDICATED AS FRYERS ON THE GAS
 ISOMETRIC RISER DIAGRAM. ALSO SHT A-2 SHOWS THE FRYERS
 ON THE WEST WALL NOT IN LINE WITH THE RANGE. PLEASE
 IDENTIFY ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE
 THE AMOUNT ON THE LEGEND.
  
 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE
 FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58
 DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2
 WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C'S:
 A. OK
 B. OK
  
 ___FOR LAVS:
 A. OK
 B. 11-4.19.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED.
 D. OK
  
 REVISION REQUIRED FOR SHEETS A-2 & A-3 SHOWING
 REQUIREMENTS.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-10-27 Cont ID  
Sent By kstevens Date 2009-10-27 Time 07:57 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 18:58 Sent To  
Notes
2009-10-27 08:16:33DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 MUNICIPAL CODE WPB
  
 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT
 WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS
 INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT
 LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY
 ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON
 THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT
 EACH OTHER. SECTION 106.1.1.
  
 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE
 FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58
 DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2
 WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER.
  
 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C'S:
 A. 11-4.16.4 GRAB BARS
 B. 11-4.16.5 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS.
  
 4. SHTS P-1 & P-2 ALL FLOOR DRAINS, FLOOR SINKS OR
 PLUMBING FIXTURES THAT DRAIN GREASE LADEN WASTE SHALL
 CONNECT TO THE GREASE INTERCEPTOR. SECTION 1003.1.
  
 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED. PLEASE
 INDICATE THE LOCATION OF THE EXISTING SERVICE SINK OR
 SHOW THE NEW REQUIRED SERVICE SINK. THE SERVICE SINK
 SHALL ALSO CONNECT TO THE GREASE WASTE SYSTEM. SECTION
 1003.1.
  
 6. SHTS P-1 & P-2 SANITARY ISOMETRIC RISER. EVERY DRY
 VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3. EVERY DRY VENT SHALL RISE VERTICALLY TO
 A MINIMUM 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION
 905.4. THE 3 INCH VTR IS A DRY HORIZONTAL VENT AND DOES
 NOT MEET THE CODE REQUIREMENTS.
  
 7. SHT P-2 DOMESTIC WATER ISOMETRIC RISER. THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE", NOT IN THE CEILING AS INDICATED.
 PDI-WH 201.
  
 8. SHT P-3 SYMBOL LEGEND FOR THE WATER HAMMER ARRESTORS
 INDICATES "LETTER DENOTES PDI SIZE". THERE IS NO LETTER
 INDICATED ON THE DOMESTIC WATER ISOMETRIC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By eschneid Date 2009-11-09 Time 15:27 Rev Time 0.50
Received By eschneid Date 2009-11-09 Time 14:57 Sent To  
Notes
2009-11-09 15:28:52PASSED W/PROVISO
  
 THE ROOFTOP MECHANICAL SYSTEMS SHALL BE SCREENED BY
 BUILT ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE
 BUILDING - THIS INCLUDES THE NEW ROOFTOP CONDENSING
 UNITS, TO INCLUDE THE MOUNTING RACK, EXHAUST FANS AND
 ANY OTHER NEW ROOFTOP MECHANICAL EQUIPMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-27 Cont ID  
Sent By eschneid Date 2009-10-27 Time 14:28 Rev Time 0.75
Received By eschneid Date 2009-10-27 Time 14:28 Sent To  
Notes
2009-10-27 14:47:31FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE NORTHWOOD MIXED USE DISTRICT REQUIRES THAT
 STORIES AT SIDEWALK LEVEL BE NO LESS THAN 12 FEET IN
 HEIGHT FROM FINISHED FLOOR TO FINISHED CEILING [SECTION
 94-213(A)(2) ZONING AND LAND DEVELOPMENT REGULATIONS].
 SECTION A-A ON SHEET A-3 SHOWS THAT THE EXISTING
 CEILING IS 12 FEET IN HEIGHT. SHEETS A-3 AND A-4 SHOW
 THAT THE CEILING HEIGHT IS BEING LOWERED TO 10 FEET 6
 INCHES IN THE KITCHEN AND STORAGE AREAS AND 9 FEET IN
 THE BATHROOMS. NEITHER OF THESE IS PERMITTED.
  
 2) PROVIDE ELEVATIONS OF THE BUILDING WITH CLEAR
 GLAZING CALCULATIONS. PLANS REVIEWED BY ZONING STAFF IN
 JULY 2009 AS WELL AS SHEET A-1 INDICATE THAT THE
 EXISTING, EASTERN FACADE CLEAR GLAZING IS BEING BLOCKED
 AT THE BATHROOM LOCATION, AND SHEET A-1 SEEMS TO
 INDICATE THAT A SOLID WALL IS BEING INSTALLED IN PLACE
 OF GLAZING ON THE SOUTH SIDE FA??ADE. SECTION
 94-213(D)(5)B OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS DO NOT ALLOW A REDUCTION IN THE CLEAR
 GLAZED AREAS.
  
 3) THE DIFFERENT SHEETS INDICATE DIFFERENT CONDITIONS
 OF THE EASTERN WALL ADJACENT TO THE BATHROOMS.
  
 4) SECTION 94-213(D)(15) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRE THAT ROOFTOP MECHANICAL
 SYSTEMS SHALL BE SCREENED BY LANDSCAPE OR BUILT
 ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE BUILDING.
 PROVIDE DETAILS ON THE HEIGHT OF THE NEW ROOFTOP
 CONDENSING UNITS, TO INCLUDE THE MOUNTING RACK, EXHAUST
 FANS AND ANY OTHER NEW ROOFTOP MECHANICAL EQUIPMENT AND
 PROVIDE AN ELEVATION DRAWING OF HOW IT WILL BE
 SCREENED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.