Plan Review Details - Permit 09100307
Plan Review Stops For Permit 09100307
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-10-19 Cont ID  
Sent By mcarsill Date 2009-10-19 Time 07:23 Rev Time 0.00
Received By mcarsill Date 2009-10-19 Time 07:07 Sent To  
Notes
2009-10-19 07:23:37FIRE PROTECTION SYSTEMS ON FLOATING DOCKS A,B, & C
 PERMIT # 09100307
  
 1. ENTIRE STANDPIPE SYSTEM INCLUDING FIRE DEPARTMENT
 CONNECTIONS SHALL BE PRESSURE TESTED FOR TWO HOURS AT
 200 PSIG.
  
 2. KNOX LOCKING CPAS ARE TO BE PROVIDED FOR FIRE
 DEPARTMENT CONNECTIONS.
  
 3. THE TOPS OF THE FIRE DEPARTMENT CONNECTIONS SHOULD
 BE LABELED STANDPIPE AND NOT FIRE SPRINKLER SYSTEM.
  
 4. ALL FIRE HOSE VALVES SHALL BE EQUIPPED WITH 2 1/2 TO
 1 1/2 REDUCERS.
  
 5. WHEN SYSTEMS ARE COMPLETED THEY ARE TO BE FLOW
 TESTED.
  
 6. THE FIRE HYDRANTS LOCATED ON THE UPLANDS SHALL BE
 WET AND WILL ALSO BE FLOW TESTED.
  
 7. DOCKS SHALL BE PROPERLY IDENTIFIED WITH LETTERS OR
 NUMBERS.
  
  
 APPROVED
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved