Plan Review Details - Permit 09100277
Plan Review Stops For Permit 09100277
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-17 Cont ID  
Sent By jwitmer Date 2009-11-17 Time 16:05 Rev Time 1.00
Received By jwitmer Date 2009-11-17 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-22 Cont ID  
Sent By jwitmer Date 2009-10-22 Time 15:58 Rev Time 0.55
Received By jwitmer Date 2009-10-22 Time 15:58 Sent To  
Notes
2009-10-22 16:06:16BUILDING PLAN REVIEW
 PERMIT: 09100277
 ADD: 400 S AUSTRALIAN SUITE 801
 CONT: R&D CONSTRUCTORS, INC.
 TEL: (561) 889-1751
  
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 OCT.22/2009
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLEASE REVIEW LICENSING LAWS FOR DESISGN
 PROFESSIONALS FL S S 481.229 ARCHITECTS EXCEPTIONS
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
  
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
  
 ****(B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE
 BUILDING, TOWNHOUSE, OR DOMESTIC OUTBUILDING
 APPURTENANT TO ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE,
 REGARDLESS
 OF COST; OR
  
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES
 OF A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR
 MINOR SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-17 Cont ID  
Sent By btrobaug Date 2009-11-17 Time 15:17 Rev Time 0.00
Received By btrobaug Date 2009-11-17 Time 15:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-27 Cont ID  
Sent By btrobaug Date 2009-10-27 Time 13:51 Rev Time 0.00
Received By btrobaug Date 2009-10-27 Time 13:20 Sent To  
Notes
2009-10-27 13:51:47 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 2} 13-415.1.AB.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
 INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLANS.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-13 Cont ID  
Sent By mawillia Date 2009-11-13 Time 14:27 Rev Time 0.00
Received By mawillia Date 2009-11-13 Time 13:59 Sent To  
Notes
2009-11-13 14:14:02*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; SHEETS A-1 AND E-1 WERE STAMPED, INITIALED,
 AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-11-09 Cont ID  
Sent By mawillia Date 2009-11-09 Time 15:05 Rev Time 0.00
Received By mawillia Date 2009-11-09 Time 14:41 Sent To  
Notes
2009-11-09 15:05:21*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE
 SPRINKLERS AND/OR FIRE ALARM DEVICES WITHIN THE UNIT TO
 BE REMODELED. IF SO, SEPARATE PLANS AND PERMIT SHALL BE
 REQUIRED.
  
 4. SPECIFY THE INTERIOR FINISH MATERAILS FOR THE NEW
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-12 Cont ID  
Sent By lmartine Date 2009-11-12 Time 16:29 Rev Time 0.00
Received By lmartine Date 2009-11-12 Time 16:29 Sent To  
Notes
2009-11-12 16:30:45*****************EXPEDITED******************
 B--2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-09 Time   Rev Time 0.00
Received By lmartine Date 2009-10-14 Time 15:46 Sent To  
Notes
2009-10-20 15:47:20B--19
 ROUTED ON THE 10/20

Review Stop Z ZONING
Rev No 1 Status N Date 2009-10-23 Cont ID  
Sent By eschneid Date 2009-10-23 Time 15:56 Rev Time 0.15
Received By eschneid Date 2009-10-23 Time 15:56 Sent To  
Notes
2009-10-23 15:57:35VALUE OF THIS PERMIT + 09090437 DO NOT EXCEED 50% OF
 BUILDING VALUE.