Plan Review Details - Permit 09100273
Plan Review Stops For Permit 09100273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By jwitmer Date 2009-12-21 Time 15:47 Rev Time 0.55
Received By jwitmer Date 2009-12-21 Time 15:47 Sent To  
Notes
2009-12-21 15:49:00RECEIVED ENGINEERING LETTER FROM PE ROGER MESSENGER FOR
 3 RAIL SYSTEM INCREASES PRESSURES TO WITHSTAND -75 PSF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-28 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2009-10-28 Time 12:31 Sent To  
Notes
2009-10-28 13:25:40BUILDING PLAN REVIEW
 PERMIT:09100273
 ADD: 226 ALHAMBRA PL.
 CONT: ALAN TOWSLEY
 TEL: (305)613-6984
  
  
 REVIEW
 ACTION: DENIED
 OCT.28/ 2009
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS & THE 2008 NEC
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) 106.1.2* ADDITIONAL INFORMATION REQUIRED, SITE PLAN,
 SHEET# 3 INDICATES THE ROOF ON EITHER A FLAT ROOF OR A
 MONO-SLOPED ROOF, PLEASE PROVIDE THIS INFORMATION,
 SINCE SHEET# 9 INDICATES THIS IS A SLOPED ROOF WITH
 SHINGLE ROOF INSTALATION, PLEASE PROVIDE THE PICH OR
 SLOPE OF THE ROOF THE SYSTEM IS TO BE INSTALLED. THIS
 WILL ALSO EFFECT THE PRESSURES ZONES IN ALL ZONES.
  
 3) THE PLANS INDICATE HOW THE L BRACKETS WILL BE
 ATTACHED TO THE ROOF DECK AND ROOF FRAMING MEMBERS, BUT
 THE PLANS ARE LACKING THE ENGINEERING FOR THE
 ATTACHMENT OF THE RAILINGS AND THE CLIP SYSTEM FOR THE
 PANELS TO THE RAILING SYSTEM. EITHER PROVIDE
 ENGINEERING OR TESTING WHERE THE SYSTEM WILL MEET THE
 WIND PRESSURES ASSOCIATED WITH THIS WIND ZONE. 1604.4
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS,
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By btrobaug Date 2009-11-05 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2009-11-05 Time 14:35 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-05 Cont ID  
Sent By btrobaug Date 2009-11-05 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 14:52 Sent To  
Notes
2009-11-05 14:54:25SMALL BIN HOLDING BIN UNDER "A"./WRT.
2009-10-20 14:53:09TO R 13./WRT

Review Stop Z ZONING
Rev No 1 Status P Date 2009-10-27 Cont ID  
Sent By lfranco Date 2009-10-27 Time 15:23 Rev Time 0.00
Received By lfranco Date 2009-10-27 Time 15:23 Sent To E
Notes
***NONE***