Plan Review Details - Permit 09100254
Plan Review Stops For Permit 09100254
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-10-30 Cont ID  
Sent By mcarsill Date 2009-10-30 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2009-10-30 Time 13:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-04 Cont ID  
Sent By mawillia Date 2009-11-04 Time 13:54 Rev Time 0.00
Received By mawillia Date 2009-10-14 Time 12:08 Sent To  
Notes
2009-10-30 14:47:421. ENTIRE INSTALLATION TO COMPLY WITH NFPA 72, THE
 NATIONAL FIRE ALARM CODE.
  
 2. PLEASE INDICATE IN WRITING WHAT THE VOICE EVACUATION
 PORTION OF THE FIRE ALARM SYSTEM WILL SAY.
  
 3. THE NEW FIRE ALARM SYSTEM AT BB KING SHALL BE
 INSPECTED, TESTED, AND APPROVED BY THE BUREAU OF FIRE
 PREVENTION.
  
 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 5, ACTIVATION OF THE HOOD SUPPRESSION SYSTEM SHALL
 CAUSE THE ACTIVATION OF THE FIRE ALARM SYSTEM.
  
 6. THE ACTIVATION OF ANY FIRE ALARM EQUIPMENT WITHIN C
 BLOCK SHALL CAUSE THE FIRE ALARM SYSTEM EQUIPMENT TO
 ACTIVATE IN BB KING.
  
 7. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 8. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]
2009-10-19 12:08:25IN FIRE BOX