| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-10-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-10-13 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-10-13 |
Time |
08:50 |
Sent To |
PC |
|
| Notes |
| 2009-10-13 09:09:15 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PRODUCT APPROVAL NOA 06-0410.06 SUBMITTED IS NO | | | LONGER VALID. THIS FILE WAS CLOSED BY THE MIAMI-DADE | | | PRODUCT CONTROL DIVISION. SEE MIAMI-DADE WEBSITE. | | | PROVIDE COPIES OF CURRENT NOA. | | | | | | 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON PAGE 41 OF SELECTED ASSEMBLY. | | | | | | 3- RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS | | | REQUIRED ON LAST PAGE OF NOA SUBMITTED. | | | ***NOTE: DESIGN PROFESSIONAL WHEN DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 | | | FLORIDA RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON | | | "EXPOSURE C". | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
|