| 2009-10-13 11:06:48 | ****PASSED WITH PROVISO**** |
| | REVISION REQUIRED BEFORE FIRST INSPECTION |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | ISSUED AT CONTRACTOR'S RISK |
| | |
| | 1. THIS JOB IS LOCATED IN EXPOSURE C. PLEASE SEE |
| | REVISED DEFINITION, FBC R301.2.1.4. |
| | |
| | 2. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 3. SEE SHEET 5, ALUMINUM PANEL PRODUCT APPROVAL. 43PSF |
| | CIRCLED, 12" C3 ANCHOR CONNECTION (FOR 50PSF) CIRCLED. |
| | INTENT IS NOT CLEAR; TO WHICH DESIGN PRESSURE DO YOU |
| | INTEND TO USE? SEE SHEET 2, F TRACK/DIRECT MOUNT |
| | CIRCLED, BUT THIS IS A C1 CONNECTION TYPE. |
| | |
| | 4. SEE SHEET 5, CLEAR PANEL PRODUCT APPROVAL. ANCHOR |
| | SPACING FOR C2 CIRCLED, BUT ON PAGE 3, C1 MOUNTING TYPE |
| | IS CIRCLED. CODE COMPLIANCE CANNOT BE DETERMINED AS |
| | PROPOSED INSTALLATION IS NOT CLEAR BASED ON INFORMATION |
| | PROVIDED. |
| | |
| | **REVISE DESIGN PRESSURES TO COMPLY WITH EXPOSURE C AND |
| | COMPLETE INSTALLATION SCHEDULE, SUBMIT AS REVISION** |