| 2009-11-02 10:21:50 | BUILDING PLAN REVIEW |
| | PERMIT: 09100126 |
| | ADD: 3001 OKEECHOBEE BLVD |
| | CONT: DONNIE BENNETT LIGHTING |
| | TEL: (561)685-2316 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. PLANS CURRENTLY READ |
| | THAT TTHEY ARE DESIGNED BY THE 2003 & 2006 IBC. PLEASE |
| | CORRECT CODE AND VERSION. |
| | |
| | 2) THE VALUE OF TTHE MONUMENT SIGN IS INDICATED AS |
| | $6,000.00 FORTHE INSTALATION OF FOUNDATION AND 342 SQ |
| | FT SIGN. THE CALCULATED VALUE IS AS FOLLOWS: |
| | |
| | 282 SQ FT OF ALUMINUM CLAAD BASE @ 38.75 / SQ FT= $ |
| | 10,927.00 |
| | 60 SQ FT OF DOUBLE FACE SIGNAGE @ 7,860.00 |
| | ____________ |
| | TOTAL $18,787.00 |
| | |
| | BALANCE DUE IS $309.96 |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | COPIED SIGNATURE -NO SEAL |
| | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. |
| | |
| | 4) DISCREPANCY IN WIND ZONES SHEET 1 INDICATES THE |
| | LOCATION AND WIND ZONE AS 140 MPH AND IN THE HIGH |
| | VELOCITY WINDLOAD. THE HIGH VELOCITY WIND ZONES ARE |
| | DADE AND BROWARD COUNTIES AT A 146 MPH AND EXPOSURE |
| | "C", THE CITY OF WEST PALM BEACH IS LOCATED IN A WIND |
| | -BORNE DEBRIS REGION OR A 140 MPH WIND ZONE, AND THIS |
| | LOCATION A EXPOSURE"B". YOU MAY DESIGN TO TTHE HIGHER |
| | STANDARD BUT ALL THE WIND INFORMATION WILL NEED TO BE |
| | CORRECT. |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 4.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 4.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 4.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED |
| | IN THIS CHAPTER. SEE SECTION 1609 FOR WIND AND SECTION |
| | 1610 FOR LATERAL SOIL LOADS. |
| | |
| | 5) SHEET 1 ALSO INDICATES THE SOIL TO BE A MEDIUM CLAY, |
| | THERE IS NOT CLAY IN THE SOUTH END OF FLORIDA PLEASE |
| | UPDATE PLAANS . |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |