| 2009-10-05 14:24:21 | BUILDING PLAN REVIEW |
| | PERMIT: 09100025 |
| | ADD: 444 W RAILROAD AV. |
| | CONT: (PLAN REVIEW) PBM DEV |
| | TEL: (561)715-1800 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | OCT 05-2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) THE PLANS INDICATE THE MOVING OF THE ACCESSIBLE |
| | PARKING SPACES NEXT TO THE ENTRY AND CREATING |
| | ACCESSIBLE SPACES FURTHER AWAY FROM THE ENTRY AND ALSO |
| | CAUSING THE DISSABLED TO TRAVEL BEHIND THE OTHER PARKED |
| | VEHICLES. |
| | |
| | 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES SERVING A |
| | PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST |
| | SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE. |
| | |
| | 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.1) GENERAL. |
| | ALTERATIONS TO EXISTING BUILDINGS AND FACILITIES SHALL |
| | COMPLY WITH THE FOLLOWING: |
| | |
| | (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES |
| | OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR |
| | USABILITY OF A BUILDING OR FACILITY BELOW THE |
| | REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF |
| | ALTERATION. |
| | |
| | (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE |
| | ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3, |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. |
| | |
| | |
| | 2) SHEET A-4 INDICATES THE INSTALATION OF A 5,000 GAL |
| | DESIEL FUEL DOUBLE WALL TANK. THIS IS IN EXCESS OF |
| | ALLOWABLE COMBUSTIBLE LIQUIDS FOR A CLASS LL COMBUSTILE |
| | LIQUIDS, SEE TABLE 307.7(1) WHEN OVER 240 GAL FOOTNOTE |
| | D & E. |
| | |
| | 415.6.2 FLAMMABLE AND COMBUSTIBLE LIQUIDS. THE STORAGE, |
| | HANDLING, PROCESSING AND TRANSPORTING OF FLAMMABLE AND |
| | COMBUSTIBLE LIQUIDS SHALL BE IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 415.6.2.1 MIXED OCCUPANCIES. WHERE THE STORAGE TANK |
| | AREA IS LOCATED IN A BUILDING OF TWO OR MORE |
| | OCCUPANCIES, AND THE QUANTITY OF LIQUID EXCEEDS THE |
| | MAXIMUM ALLOWABLE QUANTITY FOR ONE CONTROL AREA, THE |
| | USE SHALL BE COMPLETELY SEPARATED FROM ADJACENT FIRE |
| | AREAS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 508.3.3. PLEASE INDICATE COMPLIANCE WITH THIS SECTION. |
| | |
| | |
| | 3) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS FOR |
| | COMPLIANCE WITH: |
| | 415.6.2.5 LEAKAGE CONTAINMENT. A LIQUID-TIGHT |
| | CONTAINMENT AREA COMPATIBLE WITH THE STORED LIQUID |
| | SHALL BE PROVIDED. THE METHOD OF SPILL CONTROL, |
| | DRAINAGE CONTROL AND SECONDARY CONTAINMENT SHALL BE IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | EXCEPTION: ROOMS WHERE ONLY DOUBLE-WALL STORAGE TANKS |
| | CONFORMING TO SECTION 415.6.2.3 ARE USED TO STORE CLASS |
| | I, II AND IIIA FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL |
| | NOT BE REQUIRED TO HAVE A LEAKAGE CONTAINMENT AREA. |
| | |
| | 4) PLEASE PROVIDE ANCHORING REQUIREMENTS FOR SLIPPAGE |
| | AND UPLIFT 1604.8.1. |
| | |
| | 5) 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION |
| | RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF |
| | WHETHER WIND LOADS GOVERN THE DESIGN OF THE |
| | LATERAL-FORCE-RESISTING SYSTEM OF THE BUILDING: |
| | |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (M/S). |
| | |
| | 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 3. WIND EXPOSURE. WHERE MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF |
| | EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |