| 2009-10-10 09:11:09 | |
| | |
| | ** DENIED ** |
| | |
| | ** SOME OF THE COMMENTS BELOW WOULD TYPICALLY BE |
| | REDLINED HOWEVER NOT ALL. AS STATED IN ALL REVIEWS IF |
| | THERE ARE QUESTIONS ON ANY OF THE BELOW COMMENTS PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS REVIEWER. |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| | REFLECTED ON ELECTRICAL PLANS. |
| | 2008 NFPA-70 (NEC) |
| | 2002 NFPA-72 |
| | |
| | *** THIS IS UNDER THE 2008 NEC WHICH HAS SEVERAL |
| | CHANGES WHICH WILL AFFECT THIS PROJECT. |
| | |
| | 2) NOTE: PLEASE INCLUDE AIC RATING OF MAIN/SERVICE |
| | EQUIPMENT. 110.9 |
| | |
| | 3) NOTE: PANEL SCHEDULE NEEDS TO INCLUDE ALL BRANCH |
| | CIRCUIT SIZES SHOWING MINIMUM REQUIRED OVER CURRENT |
| | PROTECTION AND CONDUCTORS. |
| | PLEASE SEE 408.4,240.4,310.16, 210, 210.52 ETC |
| | |
| | 4) NOTE: PLEASE BE SURE TO SEE 424.3B FOR MINIMUM |
| | SIZING FOR AHU/CU. PLEASE INCLUDE AHU ON ELECTRICAL |
| | LAYOUT. |
| | |
| | 5) NOTE: CLOSET LIGHTS DO NOT MEET 410.8. SEE ASSUMED |
| | MINIMUM SHELVING PER SECTION GIVEN. |
| | |
| | 6) NOTE: PLEASE SEE 210.52 FOR MISSING WALL RECEPTACLE |
| | IN FRONT CORNER BEDROOM. AS EACH ROOM IS NOT IDENTIFIED |
| | SEPARATELY SPECIFIC ROOMS ARE HARD TO STATE. |
| | PLEASE SEE 408.4 FOR THE 2008 NEC WHICH REQUIRES ALL |
| | SPACES/ROOMS AND AREAS TO BE SPECIFIC ON PANEL |
| | SCHEDULES. THIS ORIGINAL WAS REVISED IN THE 2005 NEC. |
| | |
| | 7) NOTE: PLEASE LIST ALL ARC FAULT PROTECTED CIRCUITS |
| | PER 210.12. PLEASE SEE 2008 NEC |
| | |
| | 8) NOTE: PLEASE SEE 406.8 FOR WEATHER RESISTANT |
| | RECEPTACLES |
| | |
| | 9) NOTE: PLEASE SEE 406.11 FOR TAMPER RESISTANT |
| | RECEPTACLES. |
| | |
| | 10) NOTE: RISER INDICATES A MAIN OUTSIDE HOWEVER THE |
| | PLANS ONLY INDICATE A METER. PLEASE SHOW. |
| | 110.26 |
| | |
| | 11) NOTE: WASHER IS SHOWN IN FRONT OF DOOR AND WATER |
| | HEATER, IS THIS CORRECT? |
| | |
| | 12) NOTE: PLEASE SEE WALL SPACE AT FRONT ENTRANCE WALL |
| | WHICH IS OVER 12FT AND NEEDS AN ADDITIONAL RECEPTACLE |
| | PER 210.52. |
| | SEE WALL SPACE BETWEEN STOVE AND REFRIGERATOR. |
| | |
| | 13) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD IS |
| | REQUIRED TO BE FIGURED AT 125%. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |