Plan Review Details - Permit 09100016
Plan Review Stops For Permit 09100016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-01 Cont ID  
Sent By rmcdouga Date 2009-12-01 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2009-12-01 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-20 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2009-10-20 Time 12:51 Sent To  
Notes
2009-10-20 12:56:542007 FBC W/2009 REVISIONS
 RESIDENTIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE
 CONCRETE PAD TO RESIST THE 140 MPH WIND SPEED. SPECIFY
 THE LOCATIONS, SIZE AND TYPE OF ANCHORS THAT WILL BE
 USED. FBC R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-01 Cont ID  
Sent By btrobaug Date 2009-12-01 Time 08:45 Rev Time 0.00
Received By btrobaug Date 2009-12-01 Time 08:21 Sent To B
Notes
2009-12-01 08:45:48TO LUIS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-19 Cont ID  
Sent By btrobaug Date 2009-10-19 Time 13:41 Rev Time 0.00
Received By btrobaug Date 2009-10-19 Time 13:27 Sent To  
Notes
2009-10-19 13:41:28 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A
 LOAD CALCULATION FOR THE LOADS TO BE SERVED. IDENTIFY
 LOADS TO BE SERVED, PROVIDE A PANEL SCHEDULE FOR
 GENERATOR PANEL.
  
 2} THE PAD SUBMITTED WAS BOT DRAWN BY THE CONTRACTOR OF
 RECORD THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND
 471 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-10-20 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 17:01 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
2009-10-20 17:01:52A SEPARATE PERMIT IS REQUIRED FOR GAS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-17 Cont ID  
Sent By dpalmer Date 2009-11-17 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2009-11-17 Time 15:00 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-20 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 17:02 Rev Time 0.00
Received By rmcdouga Date 2009-10-05 Time 09:40 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By lfranco Date 2009-12-07 Time 17:41 Rev Time 0.00
Received By lfranco Date 2009-12-07 Time 17:41 Sent To I
Notes
2009-12-07 17:45:00PLANNING AND ZONING: **** PASSED WITH PROVISO, APPROVED
 PLANS BASED ON LEGAL DESCRIPTION SHOWN ON SURVEY. THE
 PROPERTY ADDRESS AND STREET SHOWN ON SURVEY IS
 INCORRECT. THE SIDE SETBACK FOR THE GENERATOR ON SURVEY
 SHOWS 4'-1" VS. 4'-7" ON ENLARGED PLAN, THE REQUIRED
 SIDE SETBACK IS 7.5', GENERATOR SHALL NOT ENCROACH MORE
 THAN 4 FEET INTO THE REQUIRED SETBACK. ****
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-09 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 17:02 Rev Time 0.00
Received By lfranco Date 2009-10-09 Time 16:11 Sent To E
Notes
2009-10-09 16:12:36PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. SURVEY - THE SURVEY "PROPERTY ADDRESS" AND STREET
 NAME OF "SANDHILL WAY WEST" DOES NOT CORRELATE WITH THE
 PERMIT ADDRESS. THE SURVEY SHOWS 7500 SANDHILL WAY VS.
 7108 EAGLE TERRACE. THE LEGAL DESCRIPTION, ADDRESS AND
 SURVEY DRAWING NEED TO MATCH.
  
 3. THE LOCATION OF THE GENERATOR IS NOT TO SCALE, THE
 PROPOSED 14'-1" FROM THE PROPERTY LINE WILL PLACE THE
 GENERATOR CLOSER TO THE HOME AND ACCESSORY STRUCTURE.
 CLARIFY WHAT THE ACCESSORY STRUCTURE IS USED FOR?
 PROVIDE DRIVEWAY LOCATION ON SURVEY THAT IS WITHIN THE
 VICINITY OF THE ACCESSORY STRUCTURE. ALSO, PROVIDE THE
 GENERATOR'S ACTUAL DIMENSIONS ON THE SURVEY TO SCALE.
 PROVIDE A FLOOR PLAN OF THE TWO (2) BUILDINGS TO SHOW
 WHAT THE DISTANCE OF ANY OPENINGS ARE, SUCH AS
 WINDOWS/DOORS, IN RELATION TO THE GENERATOR. SHOW ALL
 INFORMATION ON ONE ENLARGED PLAN/SURVEY.
  
 4. THE MINIMUM REQUIRED SIDE SETBACKS FOR A
 SINGLE-FAMILY WITHIN THE EAGLE'S ISLE IS 7.5'. INDICATE
 SETBACK DIMENSIONS FROM PROPOSED GENERATOR TO ALL
 PROPERTY LINES. PURSUANT TO SECTION 94-305(B)(4) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR"):
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  