| Plan Review Stops For Permit 09100016 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-12-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-12-01 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-12-01 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-20 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-20 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2009-10-20 12:56:54 | 2007 FBC W/2009 REVISIONS | | | RESIDENTIAL GENERATOR | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE | | | CONCRETE PAD TO RESIST THE 140 MPH WIND SPEED. SPECIFY | | | THE LOCATIONS, SIZE AND TYPE OF ANCHORS THAT WILL BE | | | USED. FBC R301.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-12-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-12-01 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-12-01 |
Time |
08:21 |
Sent To |
B |
|
| Notes |
| 2009-12-01 08:45:48 | TO LUIS./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-10-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-10-19 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-10-19 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2009-10-19 13:41:28 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A | | | LOAD CALCULATION FOR THE LOADS TO BE SERVED. IDENTIFY | | | LOADS TO BE SERVED, PROVIDE A PANEL SCHEDULE FOR | | | GENERATOR PANEL. | | | | | | 2} THE PAD SUBMITTED WAS BOT DRAWN BY THE CONTRACTOR OF | | | RECORD THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN | | | MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. | | | FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND | | | 471 FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2009-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-20 |
Time |
17:01 |
Rev Time |
|
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-10-20 17:01:52 | A SEPARATE PERMIT IS REQUIRED FOR GAS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-11-17 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-11-17 |
Time |
15:00 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-20 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-05 |
Time |
09:40 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-12-07 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-12-07 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-12-07 |
Time |
17:41 |
Sent To |
I |
|
| Notes |
| 2009-12-07 17:45:00 | PLANNING AND ZONING: **** PASSED WITH PROVISO, APPROVED | | | PLANS BASED ON LEGAL DESCRIPTION SHOWN ON SURVEY. THE | | | PROPERTY ADDRESS AND STREET SHOWN ON SURVEY IS | | | INCORRECT. THE SIDE SETBACK FOR THE GENERATOR ON SURVEY | | | SHOWS 4'-1" VS. 4'-7" ON ENLARGED PLAN, THE REQUIRED | | | SIDE SETBACK IS 7.5', GENERATOR SHALL NOT ENCROACH MORE | | | THAN 4 FEET INTO THE REQUIRED SETBACK. **** | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-10-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-20 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-10-09 |
Time |
16:11 |
Sent To |
E |
|
| Notes |
| 2009-10-09 16:12:36 | PLANNING AND ZONING: **** FAILED **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. SURVEY - THE SURVEY "PROPERTY ADDRESS" AND STREET | | | NAME OF "SANDHILL WAY WEST" DOES NOT CORRELATE WITH THE | | | PERMIT ADDRESS. THE SURVEY SHOWS 7500 SANDHILL WAY VS. | | | 7108 EAGLE TERRACE. THE LEGAL DESCRIPTION, ADDRESS AND | | | SURVEY DRAWING NEED TO MATCH. | | | | | | 3. THE LOCATION OF THE GENERATOR IS NOT TO SCALE, THE | | | PROPOSED 14'-1" FROM THE PROPERTY LINE WILL PLACE THE | | | GENERATOR CLOSER TO THE HOME AND ACCESSORY STRUCTURE. | | | CLARIFY WHAT THE ACCESSORY STRUCTURE IS USED FOR? | | | PROVIDE DRIVEWAY LOCATION ON SURVEY THAT IS WITHIN THE | | | VICINITY OF THE ACCESSORY STRUCTURE. ALSO, PROVIDE THE | | | GENERATOR'S ACTUAL DIMENSIONS ON THE SURVEY TO SCALE. | | | PROVIDE A FLOOR PLAN OF THE TWO (2) BUILDINGS TO SHOW | | | WHAT THE DISTANCE OF ANY OPENINGS ARE, SUCH AS | | | WINDOWS/DOORS, IN RELATION TO THE GENERATOR. SHOW ALL | | | INFORMATION ON ONE ENLARGED PLAN/SURVEY. | | | | | | 4. THE MINIMUM REQUIRED SIDE SETBACKS FOR A | | | SINGLE-FAMILY WITHIN THE EAGLE'S ISLE IS 7.5'. INDICATE | | | SETBACK DIMENSIONS FROM PROPOSED GENERATOR TO ALL | | | PROPERTY LINES. PURSUANT TO SECTION 94-305(B)(4) OF THE | | | ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR"): | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|