Plan Review Details - Permit 09100005
Plan Review Stops For Permit 09100005
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 08:40 Rev Time 1.00
Received By jwitmer Date 2009-10-27 Time 16:41 Sent To  
Notes
2009-10-28 08:48:34 
 BUILDING PLAN REVIEW
 PERMIT: 10090005
 ADD: 1009 BANYAN BLVD
 CONT: T.B.D. CONTACT DICK VERDVIN
 TEL: (561) 644-9861
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 OCT. 28 / 2009
  
 1) PLEASE REVIEW SECTION 1009.3 EXCEPTION# 6
 FBC-BUILDING INDUSTRIAL EQUIPMENT ACCESS STAIRS AND
 LANDINGS THAT SERVE AS A COMPONENT OF THE MEANS OF
 EGRESS FROM THE INVOLVED EQUIPMENT AND DO NOT SERVE
 MORE THAN 20 PEOPLE SHALL BE PERMITTED TO HAVE A
 MINIMUM CLEAR WIDTH OF 22 INCHES (559 MM), MINIMUM
 TREAD DEPTH OF 10 INCHES (254 MM), MAXIMUM RISER HEIGHT
 OF 9 INCHES (229 MM).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
 11-04-09
 CURT CAMPBELL PROVIDED NFPA 40.2.2.10.2 FIRE ESCAPE
 LADDERS ARE PERMITTED IN ACCORDANCE WITH 7.2.9.1(3)
 MEANS OF EGRESS SHALL BE TOWERS AND ELEVATED PLATFORMS
 AROUND MACHINERY OR SIMILAR SPACES SUBJECT TO OCCUPANCY
 NOT TO EXCEED THREE PERSONS WHO ARE ALL CAPABLE OF
 USING THE LADDER.
  
 ONCE CONTRACTOR IS SIGNED ON AND LICENSURE WITHIN THE
 SCOPE OF WORK IS VERIFIED REVIEW WILL CHANGE TO A
 PASSED

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-11-10 Cont ID  
Sent By mcarsill Date 2009-11-10 Time 13:55 Rev Time 0.00
Received By mcarsill Date 2009-11-10 Time 13:30 Sent To  
Notes
2009-11-10 13:55:35DIESEL FUEL TANK TANK REPLACEMENT
  
 1. PLANS DO NOT INDICATE IF THE NEW DIESEL TANK
 COMPLIES WITH UL 142 OR UL 2085. PLEASE PROVIDE THIS
 INFORMATION ON THE PLANS.
  
 2. PLANS DO NOT INDICATE THAT THE NEW DIESEL TANK
 INSTALLATION AND APPURTENANT EQUIPMENT WILL BE
 INSTALLED IN ACCORDANCE WITH NFPA 30, THE FLAMMABLE AND
 COMBUSTIBLE LIQUIDS CODE.
  
 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD"
 TANK DESCRIBED ON THE PLANS.
  
 4. NO INFORMATION PROVIDED REGARDING PRODUCT LABELS,
 SAFETY LABELS OR WARNING LABELS OR NO SMOKING
 INFORMATION.
  
 5. PLEASE INDICATE ANY SAFETY EQUIPMENT PROVIDED NEAR
 THE PROPOSED DIESEL CONTAINMENT AREA. THIS SAFETY
 EQUIPMENT COULD INCLUDE FIRE HYDRANTS, WATER HOSES, OR
 PORTABLE FIRE EXTINGUISHERS.
  
 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAIL SHOWN ON STAIR DETAIL.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 10:50 Sent To  
Notes
2009-10-05 10:51:12TO C-40

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-18 Cont ID  
Sent By rregueir Date 2009-11-18 Time 09:32 Rev Time 0.00
Received By rregueir Date 2009-11-18 Time 09:30 Sent To  
Notes
2009-11-18 09:32:42PLANS SHALL BE REVIEWED AND APPROVED BY PALM BEACH
 COUNTY DERM PRIOR TO PERMIT ISSUANCE. FOR MORE
 INFORMATION PLEASE VISIT HTTP://WWW.PBCGOV.COM/ERM/
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-10-22 Cont ID  
Sent By astelly Date 2009-10-22 Time 14:37 Rev Time 0.00
Received By astelly Date 2009-10-22 Time 14:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved