Plan Review Details - Permit 09090676
| Plan Review Stops For Permit 09090676 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-10-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-10-01 |
Time |
06:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-10-01 |
Time |
06:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2009-10-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-02 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-02 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2009-10-02 08:23:12 | **PROVISO ** | | | | | | ** PLEASE REVISE AND SUBMIT THE INFORMATION BEFORE | | | ROUGH. THIS WILL BE A REVISION. | | | | | | 1) NOTE: PLEASE SEE 13-415.AB.5, 13-415.B.1, LIGHT | | | FIXTURE AND WATTAGE INFORMATION FOR BATHROOM IS NOT | | | PERMITTED TO EXCEED TABLE ALLOWANCES. PLEASE PROVIDE | | | FIXTURE INFORMATION AS PLANS ONLY STATE 2X2 FIXTURE? | | | | | | 2) NOTE: EMERGENCY LIGHTS ARE SHOWN CIRCUITED TO OTHER | | | THAN THE LOCAL LIGHTING BRANCH CIRCUIT. PLEASE SEE | | | 700.12F AS THE CODE REQUIRES EMERGENCY AND EXIT LIGHTS | | | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. | | | | | | 3) NOTE: PLANS CONTAIN A NOTE WHICH MENTIONS NEW | | | LIGHTING WIRING TO BE #14, HOWEVER THIS WOULD DEPEND ON | | | THE EXISTING BRANCH CIRCUIT IN WHICH LIGHTS WILL BE | | | CONNECTED. | | | 310.16,240.4 ETC VIF | | | | | | 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1,.1.2. THE NEW | | | LIGHTING CONTROLS FOR EACH NEW ROOM MUST MEET | | | PRESCRIPTIVE REQUIREMENTS FOR SOME SORT OF AUTOMATED | | | LIGHTING CONTROLS. THIS REQUIRES ONLY NEW BEING | | | INSTALLED NOT OTHER AREAS OF THE OFFICE/TENANT SPACE. | | | | | | ** PLEASE BE AWARE THAT TWIST TYPE TIMERS ARE NOT | | | PERMITTED PER FBC CHAPTER 11. 11-4.27.4 | | | | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2009-10-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-09 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-09 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2009-10-09 13:59:37 | *****APPROVED***** | | | | | | | | | SINGLE PLAN SHEET A-1 STAMPED, INTIALED, AND DATED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-14 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-30 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-14 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-10-14 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2009-10-14 08:54:06 | PASSED/PROVISO: | | | 11-4.16.5 FLUSH HANDLE | | | 11-4.19.2 29" CLEARANCE | | | 11-4.19.3 MIN 15" OFF WALL | | | PDI-WH 201 AIR CHAMBERS NOT APPROVED |
|
|
|