Plan Review Details - Permit 09090676
Plan Review Stops For Permit 09090676
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-10-01 Cont ID  
Sent By shill Date 2009-10-01 Time 06:40 Rev Time 0.00
Received By shill Date 2009-10-01 Time 06:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-10-02 Cont ID  
Sent By dpalmer Date 2009-10-02 Time 08:23 Rev Time 0.00
Received By dpalmer Date 2009-10-02 Time 08:23 Sent To  
Notes
2009-10-02 08:23:12**PROVISO **
  
 ** PLEASE REVISE AND SUBMIT THE INFORMATION BEFORE
 ROUGH. THIS WILL BE A REVISION.
  
 1) NOTE: PLEASE SEE 13-415.AB.5, 13-415.B.1, LIGHT
 FIXTURE AND WATTAGE INFORMATION FOR BATHROOM IS NOT
 PERMITTED TO EXCEED TABLE ALLOWANCES. PLEASE PROVIDE
 FIXTURE INFORMATION AS PLANS ONLY STATE 2X2 FIXTURE?
  
 2) NOTE: EMERGENCY LIGHTS ARE SHOWN CIRCUITED TO OTHER
 THAN THE LOCAL LIGHTING BRANCH CIRCUIT. PLEASE SEE
 700.12F AS THE CODE REQUIRES EMERGENCY AND EXIT LIGHTS
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
  
 3) NOTE: PLANS CONTAIN A NOTE WHICH MENTIONS NEW
 LIGHTING WIRING TO BE #14, HOWEVER THIS WOULD DEPEND ON
 THE EXISTING BRANCH CIRCUIT IN WHICH LIGHTS WILL BE
 CONNECTED.
 310.16,240.4 ETC VIF
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1,.1.2. THE NEW
 LIGHTING CONTROLS FOR EACH NEW ROOM MUST MEET
 PRESCRIPTIVE REQUIREMENTS FOR SOME SORT OF AUTOMATED
 LIGHTING CONTROLS. THIS REQUIRES ONLY NEW BEING
 INSTALLED NOT OTHER AREAS OF THE OFFICE/TENANT SPACE.
  
 ** PLEASE BE AWARE THAT TWIST TYPE TIMERS ARE NOT
 PERMITTED PER FBC CHAPTER 11. 11-4.27.4
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-10-09 Cont ID  
Sent By mawillia Date 2009-10-09 Time 14:03 Rev Time 0.00
Received By mawillia Date 2009-10-09 Time 13:54 Sent To  
Notes
2009-10-09 13:59:37*****APPROVED*****
  
  
 SINGLE PLAN SHEET A-1 STAMPED, INTIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-14 Cont ID  
Sent By kstevens Date 2009-10-14 Time 08:32 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 16:42 Sent To  
Notes
2009-09-30 16:45:52B--17

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-10-14 Cont ID  
Sent By kstevens Date 2009-10-14 Time 08:32 Rev Time 0.00
Received By kstevens Date 2009-10-14 Time 08:32 Sent To  
Notes
2009-10-14 08:54:06PASSED/PROVISO:
 11-4.16.5 FLUSH HANDLE
 11-4.19.2 29" CLEARANCE
 11-4.19.3 MIN 15" OFF WALL
 PDI-WH 201 AIR CHAMBERS NOT APPROVED