Plan Review Details - Permit 09090612
Plan Review Stops For Permit 09090612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-16 Time 13:24 Rev Time 0.50
Received By jwitmer Date 2009-12-16 Time 13:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-10-21 Cont ID  
Sent By jwitmer Date 2009-10-21 Time 16:02 Rev Time 0.77
Received By jwitmer Date 2009-10-21 Time 16:02 Sent To  
Notes
2009-10-21 16:05:11GENERATOR PROVISO:
 THE INSTALLED ELEVATION OF THE EQUIPMENT SHALL BE
 REQUIRED TO BE DETERMINED
 AND CERTIFIED BY A QUALIFIED SURVEYOR, ENGINEER OR
 ARCHITECT, AS MEETING AT LEAST
 THE MINIMUM REQUIRED (BASE FLOOD ELEVATION PLUS SIX
 INCHES), FOR THE
 SPECIAL FLOOD HAZARD AREA IN WHICH IT IS INSTALLED.
  
 SPECIAL FLOOD ZONE AREA: A5
 BASE FLOOD: 7'-6"
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-03-04 Cont ID  
Sent By dpalmer Date 2010-03-04 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2010-03-04 Time 15:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-21 Cont ID  
Sent By dpalmer Date 2009-12-21 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2009-12-21 Time 10:40 Sent To  
Notes
2010-01-05 11:10:51** DENIED *
  
 1) NOTE: PREVIOUS REVIEW NOTES MENTIONED THE REQUIRED
 8HR BACK UP TIME. THE RESPONSE MENTIONED 6 PLUS HRS
 HOWEVER NOT MEETING THE MINIMUM TIMES PER CFR TITLE 24
 12.2.
 PLEASE CLARIFY WHERE THE ADDITION BACK UP WILL BE
 PROVIDED. WILL THIS BE BY ADDITIONAL BATTERY BACK UP?
  
 2) NOTE: THE APPLIED VALUE FOR COMPLETED SCOPE OF WORK
 IS TO INCLUDE THE FOLLOWING PER FBC 108.3 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 DESIGN COST, ALL LABOR, MATERIALS, EQUIPMENT ETC EVEN
 IF ANY OF THESE ITEMS ARE OWNER SUPPLIED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-21 Cont ID  
Sent By dpalmer Date 2009-10-21 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2009-10-21 Time 14:44 Sent To  
Notes
2009-10-21 14:44:33** DENIED **
  
  
  
 1) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR
 ALL PROPOSED *WIRELESS* SYSTEMS PROPOSED ON PLANS.
 PLEASE SEE 230.76,230.79,225.39 AS ALL DEVICES SHALL BE
 RATED FOR THE LOAD SERVED FOR DISCONNECTING MEANS OF
 SERVICE ENTRANCE OR FEEDERS.
 IT IS UNCLEAR WHY MOST OF THE EQUIPMENT ON PLANS IS
 LABELED AS *WIRELESS*.
 110.3,90.7
  
 2) NOTE: PLEASE PROVIDE NOTES FOR SIGNAGE REQUIRED PER
 230.2E, 702.8
  
 3) NOTE: PLANS INDICATED *EXISTING BATTERY CABINETS*.
 PLEASE INDICATE TIME FOR BACK UP OF EXISTING SYSTEMS.
  
 4) NOTE: PLEASE INDICATE VERTICAL SUPPORT OF CONDUCTORS
 PER 300.19
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE ON PLANS.
 2005 NFPA-70
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-11-05 Cont ID  
Sent By mawillia Date 2009-11-05 Time 15:20 Rev Time 0.00
Received By mawillia Date 2009-11-05 Time 15:13 Sent To  
Notes
2009-11-05 15:20:15*****APPROVED*****
  
  
 PLAN SHEET C3 STAMPED, INITIALED, AND DATED.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-12-16 Cont ID  
Sent By kstevens Date 2009-12-16 Time 14:45 Rev Time 0.00
Received By kstevens Date 2009-12-16 Time 14:45 Sent To  
Notes
2009-12-16 14:47:08PER CONVERSATION WITH ARMONDO ALVEREZ THE UNDERGROUND
 PIPING SHALL BE PE PIPE AND THE ABOVEGROUND PIPING
 SHALL BE SCHEDULE 40 STEEL. 12/16/09 KSTEVENS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-10-06 Cont ID  
Sent By kstevens Date 2009-10-06 Time 15:47 Rev Time 0.00
Received By kstevens Date 2009-10-06 Time 15:47 Sent To  
Notes
2009-10-06 16:22:00DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. - THE ISOMETRIC SUBMITTED INDICATES
 THAT THE METER IS LOCATED ON THE ROOF. THE METER SHALL
 BE LOCATED ON THE GROUND LEVEL OUTSIDE THE BUILDING. -
 PER CONVERSATION WITH FLORIDA PUBLIC UTILITIES, THE
 METER SHALL NOT BE ON THE ROOF.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- INDICATE DISTANCE FROM
 METER ON THE GROUND LEVEL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-02 Cont ID  
Sent By jgomez Date 2010-03-02 Time 08:28 Rev Time 0.00
Received By jgomez Date 2010-03-02 Time 08:28 Sent To  
Notes
2010-03-02 08:33:54SENT TO D. PALMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-30 Cont ID  
Sent By dpalmer Date 2009-11-30 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-11-30 Time 14:39 Sent To  
Notes
2009-11-30 14:40:02C-3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-05 Time   Rev Time 0.00
Received By rmcdouga Date 2009-09-29 Time 08:21 Sent To  
Notes
2009-10-01 08:22:29SENT TO C-29

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-02 Cont ID  
Sent By aaponte Date 2009-12-02 Time 08:36 Rev Time 0.00
Received By aaponte Date 2009-12-02 Time 08:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-10-15 Cont ID  
Sent By aaponte Date 2009-10-15 Time 08:41 Rev Time 0.00
Received By aaponte Date 2009-10-15 Time 08:41 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved