2009-10-06 15:42:49BUILDING PLAN REVIEW
 PERMIT: 09090605
 ADD: 111 SAPODILLA AV
 CONT: KNIGHT ELECTRIC COMANPY
 TEL: (561)689-3500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT 6/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
 SHEET A0.1 INDICATES A LEVEL 1 ALTERATION. PLEASE
 REVIEW EXIST BLDG CODE SECTION SECTION 404
 ALTERATION???LEVEL 2 -
 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
  
 2) MISSING WIND DESIGN INFORMATION:1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM
 OF THE BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3.1 WALL LOUVER
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) SHEET A1.1 PLEASE REVIEW NEW STAIR BOTTOM LANDING
 AND SWING OF NEW DOORWAY AND SECTION 1009.4 EXCEPTION#
 2. DOORS OPENING ONTO A LANDING SHALL NOT REDUCE THE
 LANDING TO LESS THAN ONE-HALF THE REQUIRED WIDTH. WHEN
 FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO A LANDING.
 PLEASE PROVIDE DIMENSIONS.
  
 6) SHEET A1.1 FOOTNOTE "G"INDICATES A NEW GAURDRAIL BUT
 IT THE PLANS MAKE IT APPEAR THERE IS A WALL STILL IN
 THAT LOCATION. PLEASE PROVIDE OPENING LIMITATIONS.
 1013.3, 1607.7.1.1 CONCENTRATED LOAD. HANDRAIL
 ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST A SINGLE
 CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), APPLIED IN
 ANY DIRECTION AT ANY POINT ALONG THE TOP, AND HAVE
 ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO TRANSFER
 THIS LOADING TO APPROPRIATE STRUCTURAL ELEMENTS OF THE
 BUILDING.
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-03 Cont ID  
Sent By dpalmer Date 2010-03-03 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2010-03-02 Time 17:04 Sent To  
Notes
2010-03-03 10:57:35** PROVISO/REDLINED **
  
  
 1) NOTE: SELECTIVE COORDINATION STUDY TO BE SUBMITTED
 FOR REVIEW BEFORE INSPECTION.
 PLEASE SEE NEC 700.27, 701.18, 240.12
 ALSO NFPA-110 CHAPTER 6, 6.5.1
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-11 Cont ID  
Sent By dpalmer Date 2009-10-11 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2009-10-11 Time 09:01 Sent To  
Notes
2009-10-11 09:54:45 
  
 ** DENIED **
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT AFTER MARCH 1ST
 2009 AND DECEMBER 31ST, 2008 ARE UNDER THE FOLLOWING
 CODES. THE LIFE SAFETY CODE ON PLANS STATE 2000 EDITION
 WHICH IS ACTUALLY FROM TWO CYCLES AGO. PLEASE SEE FAC
 69A FOR ADOPTIONS OF NFPA EDITIONS.
 FAC 69A-60.004, 69A-3.012 AS OF DECEMBER 31ST 2008
 ADOPTED THE 2006 NFPA-101, 2006 NFPA-1 AND THE 2007
 FLORIDA FIRE PREVENTION CODE.
 PLEASE SEE FBC 2007 W/ 2009 SUPPLEMENTS, FAC 69A-3.012
 AS DECEMBER 8TH, 2006 THE ELECTRICAL CODE IS THE 2005
 EDITION.
 PLEASE ADJUST PLANS TO THE FOLLOWING WHICH ARE
 RELEVANT.
  
 2007 FBC W/2009 REVISIONS.
 2005 NFPA-70
 2005 NFPA-110
 2006 NFPA-101
  
 ** FOR INFORMATION ONLY 2008 NFPA-70 WAS ADOPTED ON
 OCTOBER 1ST, 2009.
  
 2) NOTE: SEE NFPA-110 7.7.2.1 AND 7.7.2.2. THE MAKE UP
 AIR IS SHOWN FROM AN INSIDE LOADING DOCK WHICH IS
 SUPPLIED THROUGH ANOTHER OPENING. PLANS ALSO INDICATE A
 *SCREEN GATE/DOOR OPENING* AT THE SAME LOCATION WHERE
 VENTILATION IS BEING BROUGHT INTO?
 SEE MINIMUM CODES AND RATING OF AIR INTAKES.
 THIS WILL BE PART OF MECHANICAL REVIEW FOR TECHNICAL
 REVIEW COMMENTS AND IS GIVEN AS INFORMATION ONLY BY
 THIS REVIEWER. THE REVIEW OF THE VENTILATION SYSTEM IS
 NOT UNDER THIS ELECTRICAL REVIEW.
  
 3) NOTE: PLANS INDICATE WHAT WOULD BE A NEW EXIT AND
 STAIRS HOWEVER NO LIGHTING PLANS WERE SUBMITTED FOR
 GENERAL ILLUMINATION OR FOR EGRESS ILLUMINATION.
 PLEASE SEE FBC 1006.1, NFPA-101 7.8.1.3,7.9.1.1,7.9.2
 AND INDICATE.
  
 4) NOTE: PLEASE SEE NFPA-110 7.3 FOR MINIMUM LIGHTING
 REQUIRED IN NEW GENERATOR ROOM.
  
 5) NOTE: PLANS MAKE NOTE TO 700.27 FOR SELECTIVE
 COORDINATION HOWEVER NO COORDINATION STUDY AND
 DOCUMENTS WERE SUBMITTED. IF THIS INFORMATION IS NOT
 KNOWN BASED ON EQUIPMENT, BREAKERS ETC THIS CAN BE DONE
 AS A PROVISO TO BE SUBMITTED AT A LATER DATE.
  
 6) NOTE: PLEASE EXPLAIN WHAT TYPE OF GENERATOR IS BEING
 REPLACED AND LOADS SERVED? THE PLANS ALL LEND TO A 700,
 701 SYSTEM HOWEVER BASED ON PANEL SCHEDULES THERE ARE
 700, 701 AND 702 ALL WIRED INTO THE SAME PANELS ALL FED
 FROM THE SAME TRANSFER SWITCH. THIS IS NOT PERMITTED.
 A/C EQUIPMENT, GENERAL PURPOSE RECEPTACLES, GENERAL
 LIGHTING ETC ARE NOT 700 SYSTEMS AND MAY NOT BE WIRED
 INTO LIFE SAFETY/EMERGENCY SYSTEMS.
 PLEASE PROVIDE PLANS FOR LIFE SAFETY LIGHTING
 CIRCUITS/LAYOUTS. IF ALL MINIMUM LIFE SAFETY REQUIRED
 EGRESS LIGHTING IS BATTERY BACK UP THEN ALL LIGHTING
 WOULD BE CONSIDERED AS AN 702 BACK UP AND NOT BE FED
 FROM THE 700 ATS.
 SEE NEC 700.9B, SEE HANDBOOK AS THERE ARE FIGURES WHICH
 CLEARLY SHOW SYSTEM SEPARATIONS.
 RISER INDICATES A 225AMP BREAKER TO RE-FEED EM-CONTROL
 PANEL HOWEVER NO INFORMATION FOR WHAT THIS PANEL IS
 FEEDING IS SHOWN. NO TRANSFER SWITCH IS SHOWN. WILL
 THIS PANEL BE FED FROM THE GENERATOR ONLY WHEN UNDER
 EMERGENCY POWER?
 PLANS ALSO STATE EXISTING WIRING AND LOADS HAVE NOT
 BEEN VERIFIED. SOME CODE REVIEW ITEMS CAN NOT BE
 CONFIRMED IF PLANS STATE THESE MAY NOT BE THE LOADS AND
 WIRING?
  
 7) NOTE: PLEASE INDICATE THE GROUNDING FOR T-EM?
 250.20,250.30,250.66 ETC
  
 8) NOTE: PLEASE SEE NFPA- 110 7.4, 7.5 FOR LOCATIONS,
 ATTACHMENTS ETC.
  
  
 ** AS THERE WILL BE SEVERAL CHANGES MADE TO RISER,
 PLEASE CALL TO GO OVER ANY ITEMS BEFORE RESUBMITTING TO
 ALLEVIATE DELAY OF PROJECT.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-08 Cont ID  
Sent By mawillia Date 2010-03-08 Time 14:23 Rev Time 0.00
Received By mawillia Date 2010-03-08 Time 14:00 Sent To  
Notes
2010-03-08 14:23:22*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A1.1 AND E-0.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-22 Cont ID  
Sent By mcarsill Date 2009-10-22 Time 07:28 Rev Time 0.00
Received By mcarsill Date 2009-10-22 Time 07:22 Sent To  
Notes
2009-10-22 07:28:04GENERATOR REPLACEMENT - DIESEL
  
 1. WRONG CODES LISTED ON PAGE AO.1. PLEASE CORRECT CODE
 REFERENCES.
  
 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 3. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR NEW HANDRAILS DESCRIBED ON PAGE A.1.1.
  
 4. THE REFERENCES ON PAGE M-1.0 RELATED TO MAKE-UP AIR
 FROM THE LOADING DOCK IS NOT VERY CLEAR. PLEASE PROVIDE
 ADDITIONAL DETAILS.
  
 5. ANY ASBESTOS REGULATED MATERIALS SHALL BE PROPERLY
 HANDLED, COLLECTED, AND DISPOSED OF IN ACCORDANCE WITH
 FEDERAL, STATE, AND LOCAL REQUIREMENTS.
  
 6. INSTALLATION TO COMPLY WITH NFPA 110 AND NFPA 37.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2009-10-27 Cont ID  
Sent By rregueir Date 2009-10-27 Time 19:35 Rev Time 0.00
Received By rregueir Date 2009-10-27 Time 19:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-25 Cont ID  
Sent By kstevens Date 2010-02-25 Time 08:35 Rev Time 0.00
Received By kstevens Date 2010-02-25 Time 08:35 Sent To  
Notes
2010-02-25 08:35:56SENT TO C-18.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-27 Time   Rev Time 0.00
Received By shill Date 2009-09-29 Time 14:49 Sent To  
Notes
2009-09-29 14:49:35C18
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-06-18 Cont ID  
Sent By hmoser Date 2010-06-18 Time 09:47 Rev Time 0.00
Received By hmoser Date 2010-06-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By rregueir Date 2010-03-18 Time 11:40 Rev Time 0.00
Received By rregueir Date 2010-03-18 Time 11:40 Sent To  
Notes
2010-03-18 11:42:43PROVISO
  
 PROVIDE LISTING AND INSTALLATION DATA FOR DUCTWORK PER
 FBC M 607.2 & 304.1
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-27 Cont ID  
Sent By rregueir Date 2009-10-27 Time 19:36 Rev Time 0.00
Received By rregueir Date 2009-10-27 Time 19:36 Sent To  
Notes
2009-10-27 19:36:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN INDICATES THAT VENTILATION AND COMBUSTION AIR
 FOR THE GENERATOR IS TO BE TRANSFERRED THROUGH A
 LOADING DOCK INTO THE GENERATOR ROOM. THIS
 CONFIGURATION IS NOT PERMITTED. VENTILATION AIR SHALL
 BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE OF THE
 BUILDING BY AN EXTERIOR WALL OPENING OR FROM A SOURCE
 OUTSIDE THE BUILDING BY A 2-HOUR FIRE RATED AIR
 TRANSFER SYSTEM IN ACCORDANCE WITH NFPA 110-02 SECTION
 7.7.3.
  
 2. THE VENTILATION SUPPLY IS SHOWN BEING BROUGH INTO
 THE GENERATOR ROOM THROUGH A NEW 6' X 4' WALL OPENING
 IN THE BUILDING. WITH THIS OPENING, HOW WILL THE
 REQUIRED FIRE RATING OF THE GENERATOR ROOM BE
 MAINTAINED? THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING IN ACCORDANCE WITH NFPA 110-02 SECTION 7.2.1.1.
 ALSO, FIRE DAMPERS OR OTHER SELF-CLOSING DEVICES SHALL
 NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK
 FOR SUPPLY OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR
 LEVEL 1 EPSS IN ACCORDANCE WITH NFPA 110-02 SECTION
 7.7.2.3. SHOW HOW THE FIRE RATING OF THE ROOM IS TO BE
 MAINTAINED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-10-07 Cont ID  
Sent By aaponte Date 2009-10-07 Time 15:01 Rev Time 0.00
Received By aaponte Date 2009-10-07 Time 15:01 Sent To  
Notes
2009-10-07 15:01:39GENERATOR LOCATED INSIDE THE BUILDING.