Plan Review Details - Permit 09090569
Plan Review Stops For Permit 09090569
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-09-29 Cont ID  
Sent By kstevens Date 2009-09-29 Time 13:30 Rev Time 0.00
Received By kstevens Date 2009-09-29 Time 13:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 12:41 Rev Time 0.00
Received By kstevens Date 2009-09-28 Time 12:41 Sent To  
Notes
2009-09-28 13:13:26DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 PLUMBING PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. TYPE OF GAS, (LP OR NATURAL). INDICATE ON PLANS.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). (TOTAL
 BTU LOAD NOT INDICATED).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429. (NO OPENINGS WERE INDICATED NEAR THE TANKLESS
 WATER HEATERS. VENT SHALL BE MINIMUM DISTANCE FROM
 OPENINGS AS REQUIRED BY MANUF. INSTALLATION
 INSTRUCTIONS).
  
 6. THE MOST REMOTE OUTLET APPEARS TO BE AT LEAST 90 FT
 FROM THE METER. WITH A TOTAL LOAD OF 746,000 BTU
 MINIMUM 2 INCH PIPE IS REQUIRED FROM THE METER UP TO
 THE TEE FOR THE GRILL, WITH 1-1/2 INCH UP TO THE TEE
 FOR THE POOL HEATER, AND 1-1/4 INCH UP TO THE TEE FOR
 BETWEEN THETANKLESS WATER HEATERS WITH 1 INCH REQUIRED
 UP THRU THE SHUT OFF VALVES TO EACH TANKLESS WATER
 HEATER. TABLE G2413.4(1). -- THE P.E. PIPING TO THE
 POOL HEATER IS REQUIRED TO BE MINIMUM 1-1/4 INCH PER
 TABLE G2413.4(7) UP THRU THE SHUT OFF VALVE.
  
 B. THE PERSON RESPONSIBLE FOR THE DESIGN AND DRAWINGS
 SHALL PRINT THEIR NAME AND PLACE THEIR SIGNATURE ON THE
 PLANS SUBMITTED FOR PUBLIC RECORD. SECTIONS 106.1 &
 106.3.4.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  