Plan Review Details - Permit 09090480
Plan Review Stops For Permit 09090480
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-09-23 Cont ID  
Sent By jnguyen Date 2009-09-24 Time 15:13 Rev Time 0.00
Received By jnguyen Date 2009-09-23 Time 08:00 Sent To  
Notes
2009-09-24 15:12:32UPDATE ON 9/24/2009: THE CONTRACTOR, DENNIS DEATON
 CALLED ME BACK & WE REALIZED THAT WE MADE A MISTAKE FOR
 THE SITE LOCATION. IT WAS IN THE EAST PARCEL BOUNDARY
 DIRECTLY ACROSS FROM THE SWA POWER PLANT (6501 N JOG
 RD). IN GIS & COMMUNITYPLUS, I HAVE ADJUSTED THE
 ADDRESS TO 6610 @ N JOG RD & CORRECTED IT ON THE SITE
 PLANS TOO.
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]
2009-09-23 09:41:55 
  
  
 I HAVE EXAMINED THE SITE PLANS & CONTACTED THE
 CONTRACTOR, DENNIS DEATON OF GRID-ONE ELECTRICAL
 CONSTRUCTION, INC. HE HAS CONFIRMED TO ME THAT PERMIT#
 09090480 IS FOR TEMPORARY WORK OCCURRING IN THE EAST
 PARCEL BOUNDARY OF PCN# 74424234000001010. IT WILL BE
 FOR AN 18-MONTH PERIOD IN AN AREA LOCATED APPROXIMATELY
 TO THE NORTH OF THE SCALE HOUSE BUILDING AT 6790 N JOG
 RD. HE ALSO RELAYED TO ME THAT THIS PROSPECTIVE ADDRESS
 OF 6810 N JOG RD DOES NOT NEED TO BE "OFFICIALLY
 ISSUED", AS IT WON'T BE RECEIVING ANY MAIL (SO A
 NUMERICAL LABEL POSTED IS NOT REQUIRED). THEREFORE IN
 COMMUNITYPLUS, I HAVE ADDED SEQUENTIAL UNIT RECORD 0025
 - 6810 @ N JOG RD UNDER PCN# 74424234000001010 &
 CREATED IT AS A KEYCODE=3 ADDRESS POINT (MISCELLANEOUS
 PURPOSES) IN GIS. I HAVE MOVED THIS PERMIT FROM THE
 PRIMARY ADDRESS OF 6501 N JOG RD TO BE CORRECTLY
 REFERENCED TO 6810 @ N JOG RD. I ALSO MADE THE
 ADJUSTMENTS ON THE SITE PLANS FROM 6880 TO 6810 N JOG
 RD. I WILL BE RETURNING THE ASSOCIATED DOCUMENTS BACK
 TO THE ELECTRICAL BOX DOWNSTAIRS SHORTLY.
  
  
2009-09-22 11:49:42PER DEWEY PALMER, WE ARE USING LOCATION ADDR AT THIS
 TIME AS PERMIT APPL & PLANS HAVE DIFFERENT ADDRESSES &
 WE DO NOT HAVE EITHER ADDR IN SYS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-10-14 Cont ID  
Sent By rmcdouga Date 2009-10-14 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2009-10-14 Time 09:33 Sent To  
Notes
2009-10-14 09:34:51PRE-STRESSED CONCRETE POLES REVIEWED FOR WINDLOADS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-15 Cont ID  
Sent By dpalmer Date 2009-10-15 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2009-10-15 Time 08:28 Sent To  
Notes
2009-10-15 08:29:23WIND LOADS FOR LIGHT POLE SUBMITTED AND OK BY B REVIEW.
 PROCESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 10:32 Sent To PC
Notes
2009-10-10 10:33:37WIND LOAD CALCULATIONS STILL TO BE SUBMITTED BEFORE
 POLE INSPECTION

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-09-29 Cont ID  
Sent By dpalmer Date 2009-09-29 Time 16:31 Rev Time 0.00
Received By dpalmer Date 2009-09-29 Time 16:31 Sent To PC
Notes
2009-09-29 16:31:42 
 ** PROVISO **
  
 ** PLANS TO BE REVISED BEFORE INSPECTION.
  
 1) NOTE: PLEASE SEE 450.3B. ONLY IF MEETING NOTE #3 CAN
 THE MAXIMUM OVER CURRENT PROTECTION BE 500AMPS FOR THE
 TRANSFORMER T1. BASED ON THE CALCULATIONS THIS SHOULD
 BE UNDER 450AMPS. BASED ON 240.6 THE NEXT STANDARD OCP
 IS 450AMPS.
  
 2) NOTE: TIME CLOCK REQUIRED SHALL MEET FBC
 13-415.AB.1.4. SECTION REQUIRES AN ASTRONOMICAL TYPE
 TIME CLOCK WITH BACK UP FOR PROGRAMMING MEETING MINIMUM
 OF 10HRS UNDER SECTION GIVEN FOR PROGRAMMING.
  
 3) NOTE: SIGNED, DATED AND SEALED WIND LOAD
 CALCULATIONS REQUIRED TO BE SUBMITTED FOR BLDG REVIEW.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 14:03 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 14:03 Sent To  
Notes
2009-10-08 14:03:59SENT TO DVPALMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-29 Time   Rev Time 0.00
Received By lmartine Date 2009-09-22 Time 16:26 Sent To  
Notes
2009-09-22 16:26:55IN ELECTRIC BOX


Account Summary | Usage Policy | Privacy Policy