Plan Review Details - Permit 09090423
Plan Review Stops For Permit 09090423
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-14 Cont ID  
Sent By shill Date 2009-10-14 Time 15:34 Rev Time 0.00
Received By shill Date 2009-10-14 Time 15:34 Sent To  
Notes
2009-10-14 15:35:20SEE PROVISO ON PLAN FROM PREVIOUS BLDG REVIEW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-24 Cont ID  
Sent By jwitmer Date 2009-09-24 Time 18:28 Rev Time 1.50
Received By jwitmer Date 2009-09-24 Time 17:00 Sent To  
Notes
2009-09-24 17:56:26BUILDING PROVISO:
 1014.2 EGRESS THROUGH INTERVENING SPACES.
 (2)MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL OR PARTIAL HEIGHT FIXED WALLS
 OR SIMILAR CONSTRUCTION THAT WILL
 MAINTAIN THE REQUIRED WIDTH AND LEAD DIRECTLY FROM THE
 RETAIL AREA TO THE EXIT WITHOUT OBSTRUCTIONS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-13 Cont ID  
Sent By dpalmer Date 2009-10-13 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2009-10-13 Time 16:52 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-25 Cont ID  
Sent By dpalmer Date 2009-09-25 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2009-09-25 Time 10:22 Sent To  
Notes
2009-09-25 10:22:28 
 ** DENIED PLANS **
  
  
  
 1) NOTE: AS OF DECEMBER 31ST, 2008. THE CURRENT EDITION
 OF NFPA- 101 IS THE 2006. THE PLANS STATE 2003. PLEASE
 ADJUST.
  
 2) NOTE: THERE IS A NEED FOR PLANS TO COORDINATE FOR
 SERVICE. ARCHITECTURAL PLANS INDICATE THAT EXISTING
 PANELS AND DISCONNECT ARE LOCATED INSIDE TO BE REMOVED.
 HOWEVER THE ELECTRICAL RISER INDICATES THE MAIN
 DISCONNECT AS EXISTING AND IT BEING LOCATED OUTSIDE.
 PLEASE SHOW LOCATION AND COORDINATE PLANS AS TO WHETHER
 OR NOT SERVICE IS NEW AND LOCATION.
 PLEASE SEE NEC 110.26, 230.70, 230.71, 110.9 ETC
 AS PLANS INDICATE ALL SERVICE EQUIPMENT AND MAIN BEING
 REMOVED PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM, AIC
 RATING OF MAIN AND SIZE OF THE NEW CONDUCTORS.
  
 3) NOTE: PLEASE SEE E-1 AS THE PLANS INDICATE THERE IS
 PANELS *B* AND *C*, YET RISER STATES PANELS A AND B.
 PLEASE ALSO SEE THAT THE PANEL *A* STATES A 2-POLE
 60AMP BREAKER FEEDING PANEL *B* HOWEVER PANEL *B* LOAD
 EXCEEDS THE RATING OF THIS BREAKER. THE LOAD IS SHOWN
 AT 72AMPS YET ONLY A 60AMP BREAKER IS SHOWN.
 215.5, 240.4, 230, 310.16,408 ETC
  
 4) NOTE:
  
 A) PLEASE COORDINATE RISER AND PANELS. PANEL *A*
 INDICATES #6 AWG FOR THE SAME 60AMP BREAKER FEEDING
 PANEL *B* YET THE RISER INDICATES #3 CONDUCTORS?? AS
 NOTED ABOVE IN COMMENT #3, THE #6 IS NOT RATED FOR LOAD
 OF PANEL *B* AS SHOWN. 310.16,240.4
  
 B) PLEASE COORDINATE THE PANEL INFORMATION FOR PANEL
 *B*. PANEL *B* STATES IT WILL BE A 42POLE 125AMP PANEL,
 YET THE PANEL IS SHOWN AS A 30 CIRCUIT/POLE PANEL.
 NEC 408, 230
  
 5) NOTE: THE SPACE BY SPACE LIGHTING ALLOWANCES DO NOT
 MEET 13-415.AB.5, 13-415.B.1. IT IS NOT PERMISSIBLE TO
 USE RETAIL FOR OTHER AREAS SUCH AS WALK IN COOLER AREA,
 BATHROOM ETC. THESE NEED TO BE SEPARATE TO SPACE BY
 SPACE.
 ** ALSO NO FIXTURE LEGEND SUBMITTED FOR ENOUGH
 INFORMATION ON LIGHTING FIXTURES FOR A COMPLETE REVIEW
 FOR CODE COMPLIANCE.
  
 6) NOTE: NO EXTERIOR LIGHTING CALCULATIONS SUBMITTED.
 13-415.AB.2.2.
  
 7) NOTE: NO EXTERIOR LIGHTING CONTROLS PER
 13-415.AB.1.4 SHOWN. MUST MEET AT LEAST ONE OF THE TWO
 METHODS REQUIRED. THE TC AS SHOWN ON RISER DOES NOT
 PROVIDE ANY INFORMATION FOR ITS USE OR THE TYPE AS
 REQUIRED IN SECTION ABOVE. A STANDARD SINGLE POLE TIME
 CLOCK DOES NOT MEET FBC SECTION GIVEN.
 ** THE PLANS ALSO INDICATE THE SPRINKLER PUMP TO BE ON
 TIME CLOCK. AS ONLY ONE IS SHOWN ON RISER IT IS BEING
 ASSUMED THE TC IS FOR THE SPRINKLER PUMP. SEE COMMENTS
 BELOW ABOUT THE PUMP.
  
 8) NOTE: THE WALK-IN GLASS DOOR COOLER AREA DOES NOT
 INDICATE ANY LIGHTING OR LIGHTING CONTROLS. IS THERE
 NOT GOING TO BE ANY LIGHTS IN THIS AREA? THE PANEL
 SCHEDULE INDICATES A CIRCUIT FOR WALK IN LIGHTS AND
 HEATER HOWEVER NO INFORMATION ON PLANS.
 NFPA-101 7.8
 ** PLEASE ALSO KEEP IN MIND, FBC
 13-415.AB.1.1,.1.2,.1.3 ALL APPLY TO COOLER WALK IN
 LIGHTS.
  
 9) NOTE: ** PLEASE COORDINATE ALL PLANS AND REQUIRED
 CIRCUITING/LOADS.
  
 A) THE WP GFI SHOWN ON THE MECHANICAL PLANS INDICATES
 THIS RECEPTACLE BEING CIRCUITED TO A-4. HOW IS THIS
 POSSIBLE WHEN A2,4 IS THE SAME CIRCUIT FOR CONDENSING
 UNIT?
 PLEASE SEE 210.63, 210.8B
  
 B) PLEASE SEE M SHEETS AS THE WIC EVAPORATOR CIRCUIT IS
 SHOWN AS 18/20, HOWEVER PER PANEL *A* SCHEDULE 18 IS
 PART OF THE AHU-2 CIRCUIT AND 20/22 IS THE WIC CIRCUIT.
  
 C) PLEASE SEE POWER PLANS. WHERE IS THE ELECTRICAL FOR
 THE WIC UNIT INSIDE THE COOLER? A J-BOX SYMBOL IS SHOWN
 ON PLANS, HOWEVER NO CIRCUIT, NO DISCONNECT ETC IS
 SHOWN.
  
 10) NOTE: WHEN FIGURING SHOW WINDOW LOAD FOR SERVICE
 220.43A MUST BE USED AND FIGURED. ONLY 220.14G MAY BE
 USED FOR BRANCH CIRCUIT WHEN NOT USING 200 VA PER FT.
  
 11) NOTE: PLEASE SEE NEC 422.13 AS STORAGE TYPE WATER
 HEATERS ARE REQUIRED TO HAVE LOADS FIGURED AT 125%.
 THIS WAS A CHANGE IN THE 2005 NEC IN WHICH THESE TYPES
 OF WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD.
 PLEASE SEE THE LAST LINE IN THE COMMENTARY SECTION OF
 422.13 IN THE NEC HANDBOOK.
  
 12) NOTE: THE PLANS INDICATE THERE IS GOING TO BE A
 SPRINKLER PUMP AND IT WILL BE ON THE TIME CLOCK.
 HOWEVER THE LOAD SHOWN FOR TIME CLOCK IS 180VA. THIS IS
 NOT POSSIBLE FOR AN IRRIGATION PUMP. THIS IS SHOWN AS
 SINGLE PHASE PUMP, PER NEC 430.248, EVEN THE SMALLEST
 115V PUMP AS 1/6TH HP HAS A VA MUCH HIGHER THAN 180VA.
 WHERE IS THE PUMP GOING TO BE LOCATED? THE PLANS
 INDICATE THE RECEPTACLE IN THE FRONT OF THE STORE ALONG
 AN INSIDE COUNTER.
 THE LANDSCAPE PLANS DO NOT DETAIL PUMP LOCATION.
  
 ** AS THERE IS INFORMATION NOT YET COMPLETE OR SHOWN ON
 PLANS, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-06 Time 15:43 Rev Time 0.00
Received By lmartine Date 2009-10-06 Time 15:43 Sent To  
Notes
2009-10-06 15:44:57SEE APPROVALS BY EMORY ON SHEETS A-1 AND A1.1
 LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-10-05 Cont ID  
Sent By mawillia Date 2009-10-05 Time 13:06 Rev Time 0.00
Received By mawillia Date 2009-10-05 Time 12:38 Sent To  
Notes
2009-10-05 13:05:56*****PROVISO*****
  
 PLAN SHEETS A-3 AND A-5 WERE STAMPED, INITIALED, AND
 DATED; PLANS UNDER PROVISO, TO BE APPROVED, BASED UPON
 THE FOLLOWING:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION. ADD TO GENERAL NOTES ON SHEET A-2
  
 2. THE 2006 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED. AMEND ELECTRICAL NOTE 1 FROM 2003
 TO 2006 EDITION ON SHEET E2.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-08 Cont ID  
Sent By lmartine Date 2009-10-08 Time 16:37 Rev Time 0.00
Received By lmartine Date 2009-10-08 Time 16:37 Sent To  
Notes
2009-10-08 16:40:36IN LUIS'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-06 Time 15:46 Rev Time 0.00
Received By lmartine Date 2009-09-21 Time 14:59 Sent To  
Notes
2009-09-21 15:12:11B-1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-10-15 Cont ID  
Sent By rmcdouga Date 2009-10-15 Time 14:31 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
2009-10-15 14:33:11NO IMPACT FEES WERE DUE. PLANS STAMPED AND COPY OF
 RECEIPT SUBMITTED.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-10-09 Cont ID  
Sent By rkussner Date 2009-10-09 Time 13:38 Rev Time 0.00
Received By rkussner Date 2009-10-09 Time 13:38 Sent To  
Notes
2009-10-09 13:57:19***LANDSCAPE REVIEW PASSED WITH 'PROVISO'***
  
 1. FLIP-FLOP THE DAHOON HOLLY TREE CURRENTLY SHOWN IN
 THE LANDSCAPE ISLAND WITH THE CORDIA TREE SHOWN ALONG
 THE NORTH PERIMETER.
  
 2. REDUCE THE INSIDE WIDTH OF THE PLANTER THAT
 SURROUNDS THE DUMPSTER ENCLOSURE TO ONE FOOT AND
 INSTALL FICUS REPLENS INSTEAD OF THE PROPOSED HEDGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By rkussner Date 2009-09-23 Time 11:11 Rev Time 0.00
Received By rkussner Date 2009-09-23 Time 11:11 Sent To Z
Notes
2009-09-23 11:28:19***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-442 (A), THE LANDSCAPE PLAN
 SHALL BE SIGNED AND SEALED BY A REGISTERED LANDSCAPE
 ARCHITECT, LICENSED IN THE STATE OF FLORIDA.
  
 2. PURSUANT TO SECTION 94-443 (E)(1), AT LEAST 30
 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR OF ALL
 COMMERCIAL STRUCTURES SHALL BE PLANTED WITH TREES,
 SHRUBS OR HEDGES. THE CONCRETE SHALL BE REMOVED FROM
 THE TOP OF THE PLANTERS ALONG THE EAST SIDE OF THE
 BUILDING AND LANDSCAPING SHALL BE INSTALLED IN THOSE
 PLANTERS. FIRECRACKER PLANT WOULD BE SUGGESTED BECAUSE
 IT FLOWERS MUCH OF THE YEAR AND WILL CASCADE OVER THE
 SIDE OF THE PLANTER.
  
 3. THE PROPOSED HEDGE ALONG THE NORTH AND EAST
 PERIMETER OF THE SITE SHALL BE PLANTED ALONG THE
 INTERIOR PERIMETER OF THE SITE WITH THE GROUND COVER
 PLANTED ON THE STREET SIDE OF THE LANDSCAPE STRIP.
  
 4. PURSUANT TO SECTION 94-443 (C)(3)(B), THE TERMINAL
 LANDSCAPE ISLAND AT THE SOUTH END OF THE PARKING ROW
 SHALL HAVE A MINIMUM INSIDE DIMENSION OF FIVE (5) FEET,
 EXCLUDING THE REQUIRED CURB.
  
 5. PURSUANT TO SECTION 94-443 (C)(5)(A), LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS "TYPE D".
  
 6. PLEASE REDUCE THE LANDSCAPE STRIP ALONG THE EAST
 PERIMETER OF THE SITE TO ALLOW A 20 FOOT WIDE ACCESS
 INTO THE ALLEY FROM GEORGIA STREET. THE RIGHT-OF-WAY
 MAY NEED TO BE ALTERED TO ACCOMMODATE THE PROPOSED
 ACCESS POINTS.
  
 7. AN ADDITIONAL 81/2 FOOT WIDE PARKING STALL CAN BE
 ADDED AT THE SOUTH END OF THE CURRENT ROW OF PARKING,
 ADJACENT TO THE LAST PARKING STALL. THE LANDSCAPE
 ISLAND SHALL BE SHIFTED TOWARD THE SOUTH TO TERMINATE
 THE PARKING ROW.
  
 8., SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR. IT
 SHALL BE BROKEN DOWN INTO UNIT COST.
  
 9. PROVIDE THE TABULATION NECESSARY FOR THE EVALUATION
 OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 10. PURSUANT TO SECTION 94-448 (D) (2), ALL ELEMENTS IN
 THIS SECTION SHALL BE REQUIRED WHEN SUBMITTING A
 LANDSCAPE PLAN.
  
 11. ALL UTILITIES, OVERHEAD LINES, EASEMENTS, STREET
 LIGHTS AND ANYTHING ELSE THAT MAY IMPACT THE PROPOSED
 LANDSCAPING SHALL BE SHOWN ON THE LANDSCAPE PLAN.
  
 12. PLEASE PROVIDE A CURRENT SURVEY.
  
 13. IF THERE ARE ANY OVERHEAD LINES IN CLOSE PROXIMITY
 TO THE PROPOSED TREES, THE TREE SPECIES WILL NEED TO BE
 CHANGED TO COMPLY WITH FPL'S "PLANT THE RIGHT TREE IN
 THE RIGHT PLACE" GUIDELINES FOR WHAT CAN BE PLANTED
 NEAR OR ADJJACENT TO OVERHEAD LINES.
  
 14, PURSUANT TO SECTION 94-44 (B), WALLS THAT COMPOSE A
 DUMPSTER ENCLOSURE SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-09 Cont ID  
Sent By rregueir Date 2009-10-09 Time 12:14 Rev Time 0.00
Received By rregueir Date 2009-10-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-09-24 Cont ID  
Sent By rregueir Date 2009-09-24 Time 08:20 Rev Time 0.00
Received By rregueir Date 2009-09-24 Time 07:49 Sent To  
Notes
2009-09-24 08:20:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE MOTORIZED DAMPER(S) WITH SHUTOFF DAMPER
 CONTROLS FOR OUTSIDE AIR INTAKES IN ACCORDANCE WITH
 FBC-B 13-409.AB.3.3.
  
 2. RETURN AIR TRANSFER DUCT FROM STOCK ROOM IS TOO
 SMALL TO MEET EXCEPTIONS UNDER FBC-M 601.4. DESIGN AND
 SIZE TRANSFER DUCT TO MEET THE EXCEPTIONS UNDER THIS
 SECTION OR A FIELD TEST WILL BE REQUIRED AT FINAL
 INSPECTION TO DETERMINE COMPLIANCE WITH THE PRESSURE
 DIFFERENTIAL REQUIREMENTS OF THIS SECTION.
  
 3. PROVIDE PRODUCT APPROVAL FOR PROPOSED ROOFTOP A/C
 STAND WITH CORRESPONDING INSTALLATION INSTRUCTIONS IN
 ACCORDANCE WITH FBC-M 304.1 AND FBC-B 106.3.3.
  
 4. DUCTS ON PAGE M2 ARE SHADED TO THE POINT THAT THE
 SIZES SHOWN ON PLAN ARE ILLEGIBLE. PROVIDE A DUCT
 LAYOUT PLAN WITH CLEARLY LEGIBLE DUCT SIZES IN
 ACCORDANCE WITH FBC-M 603.1 AND FBC-B 106.1.1.
  
 5. PROPOSED CONDENSER LOCATION ON ROOF IS LESS THAN 10'
 FROM ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET OF THE ROOF EDGE IN ACCORDANCE WITH FBC-M 304.10.
 THE GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND
 EACH END OF THE APPLIANCES AND THE TOP OF THE GUARD
 SHALL BE LOCATED NOT LESS THAN 42 INCHES ABOVE THE
 ELEVATED SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL
 BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE
 LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.
  
 6. SHOW LOCATION OF TOILET ROOM EXHAUST ROOF CAP IN
 ACCORDANCE WITH FBC-M 401.4 AND FBC-B 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 07:53 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 07:48 Sent To  
Notes
2009-09-30 07:50:00PASSED/PROVISO:
 REVISION REQUIRED:
 604.9 WATER HAMMER ARRESTOR REQUIRED AT THE ICE
 MACHINE.
 606.1(7) FULL OPEN VALVE REQUIRED AT THE WATER HEATER.
 802.3/802.3.2 A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR
 THE INDIRECT WASTE RECEPTOR.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-14 Cont ID  
Sent By kdfreema Date 2009-10-14 Time 09:57 Rev Time 0.00
Received By kdfreema Date 2009-10-14 Time 09:57 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-28 Cont ID  
Sent By jwitmer Date 2009-09-28 Time 09:12 Rev Time 0.00
Received By kdfreema Date 2009-09-28 Time 09:12 Sent To  
Notes
2009-09-28 09:27:39***FAILED***
  
 1. PLEASE NOTE THE PARKING FINE RELATING TO ACCESSIBLE
 SPACES IS $252, THE DETAIL SHOWS $250. PLEASE REVISE.
  
 2. AN EXTRA PARKING SPACE CAN BE GAINED BY SHIFTING THE
 TERMINAL ISLAND AT THE SOUTH END OF THE PARKING ROW IN
 FRONT OF THE DUMPSTER. I'VE ATTACHED A GRAPHIC SHOWING
 THE PROPOSED CONFIGURATION. NOTE THAT THIS
 CONFIGURATION HAS BEEN CLEARED WITH ENGINEERING
 SERVICES AND PUBLIC WORKS BECAUSE THE DUMPSTER IS
 ROLLED OUT INTO THE ALLEY AND EMPTIED SO DIRECT ACCESS
 INTO THE ENCLOSURE BY TRUCK IS NOT A NECESSITY.
  
 3. PLEASE PROVIDE A CURRENT SURVEY OF THE PROPERY. IT
 SHOULD BE LESS THAN A YEAR OLD.
  
 4. THE HANDICAP PARKING SPACE AND ACCESS AISLE COULD BE
 TRANSPOSED TO INCREASE THE BACKOUT AREA FOR VEHICLES
 USING THE HANDICAP PARKING SPACE. THE CONFIGURATION
 SHOWN WOULD BE VERY DIFFICULT TO UTILIZE.
  
 5. THE PLANS SHALL BE REVIEWED AND APPROVED BY THE
 CITY'S CRIME PREVENTION OFFICER, KELLY CARSILLO, FOR
 ADHERENCE TO THE STATE OF FLORIDA CONVENIENCE BUSINESS
 SECURITY ACT (FSS 812.1701 - 812.175). THIS REQUIREMENT
 IS ONE OF THE CONDITIONS OF APPROVAL FOR THE CLASS B
 SPECIAL USE PERMIT WHICH WAS RECEIVED EARLIER THIS
 YEAR. MS. CARSILLO MAY BE REACHED DIRECTLY AT
 561-822-1620.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 OR [email protected] WITH QUESTIONS.