| 2009-09-25 10:22:28 | |
| | ** DENIED PLANS ** |
| | |
| | |
| | |
| | 1) NOTE: AS OF DECEMBER 31ST, 2008. THE CURRENT EDITION |
| | OF NFPA- 101 IS THE 2006. THE PLANS STATE 2003. PLEASE |
| | ADJUST. |
| | |
| | 2) NOTE: THERE IS A NEED FOR PLANS TO COORDINATE FOR |
| | SERVICE. ARCHITECTURAL PLANS INDICATE THAT EXISTING |
| | PANELS AND DISCONNECT ARE LOCATED INSIDE TO BE REMOVED. |
| | HOWEVER THE ELECTRICAL RISER INDICATES THE MAIN |
| | DISCONNECT AS EXISTING AND IT BEING LOCATED OUTSIDE. |
| | PLEASE SHOW LOCATION AND COORDINATE PLANS AS TO WHETHER |
| | OR NOT SERVICE IS NEW AND LOCATION. |
| | PLEASE SEE NEC 110.26, 230.70, 230.71, 110.9 ETC |
| | AS PLANS INDICATE ALL SERVICE EQUIPMENT AND MAIN BEING |
| | REMOVED PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM, AIC |
| | RATING OF MAIN AND SIZE OF THE NEW CONDUCTORS. |
| | |
| | 3) NOTE: PLEASE SEE E-1 AS THE PLANS INDICATE THERE IS |
| | PANELS *B* AND *C*, YET RISER STATES PANELS A AND B. |
| | PLEASE ALSO SEE THAT THE PANEL *A* STATES A 2-POLE |
| | 60AMP BREAKER FEEDING PANEL *B* HOWEVER PANEL *B* LOAD |
| | EXCEEDS THE RATING OF THIS BREAKER. THE LOAD IS SHOWN |
| | AT 72AMPS YET ONLY A 60AMP BREAKER IS SHOWN. |
| | 215.5, 240.4, 230, 310.16,408 ETC |
| | |
| | 4) NOTE: |
| | |
| | A) PLEASE COORDINATE RISER AND PANELS. PANEL *A* |
| | INDICATES #6 AWG FOR THE SAME 60AMP BREAKER FEEDING |
| | PANEL *B* YET THE RISER INDICATES #3 CONDUCTORS?? AS |
| | NOTED ABOVE IN COMMENT #3, THE #6 IS NOT RATED FOR LOAD |
| | OF PANEL *B* AS SHOWN. 310.16,240.4 |
| | |
| | B) PLEASE COORDINATE THE PANEL INFORMATION FOR PANEL |
| | *B*. PANEL *B* STATES IT WILL BE A 42POLE 125AMP PANEL, |
| | YET THE PANEL IS SHOWN AS A 30 CIRCUIT/POLE PANEL. |
| | NEC 408, 230 |
| | |
| | 5) NOTE: THE SPACE BY SPACE LIGHTING ALLOWANCES DO NOT |
| | MEET 13-415.AB.5, 13-415.B.1. IT IS NOT PERMISSIBLE TO |
| | USE RETAIL FOR OTHER AREAS SUCH AS WALK IN COOLER AREA, |
| | BATHROOM ETC. THESE NEED TO BE SEPARATE TO SPACE BY |
| | SPACE. |
| | ** ALSO NO FIXTURE LEGEND SUBMITTED FOR ENOUGH |
| | INFORMATION ON LIGHTING FIXTURES FOR A COMPLETE REVIEW |
| | FOR CODE COMPLIANCE. |
| | |
| | 6) NOTE: NO EXTERIOR LIGHTING CALCULATIONS SUBMITTED. |
| | 13-415.AB.2.2. |
| | |
| | 7) NOTE: NO EXTERIOR LIGHTING CONTROLS PER |
| | 13-415.AB.1.4 SHOWN. MUST MEET AT LEAST ONE OF THE TWO |
| | METHODS REQUIRED. THE TC AS SHOWN ON RISER DOES NOT |
| | PROVIDE ANY INFORMATION FOR ITS USE OR THE TYPE AS |
| | REQUIRED IN SECTION ABOVE. A STANDARD SINGLE POLE TIME |
| | CLOCK DOES NOT MEET FBC SECTION GIVEN. |
| | ** THE PLANS ALSO INDICATE THE SPRINKLER PUMP TO BE ON |
| | TIME CLOCK. AS ONLY ONE IS SHOWN ON RISER IT IS BEING |
| | ASSUMED THE TC IS FOR THE SPRINKLER PUMP. SEE COMMENTS |
| | BELOW ABOUT THE PUMP. |
| | |
| | 8) NOTE: THE WALK-IN GLASS DOOR COOLER AREA DOES NOT |
| | INDICATE ANY LIGHTING OR LIGHTING CONTROLS. IS THERE |
| | NOT GOING TO BE ANY LIGHTS IN THIS AREA? THE PANEL |
| | SCHEDULE INDICATES A CIRCUIT FOR WALK IN LIGHTS AND |
| | HEATER HOWEVER NO INFORMATION ON PLANS. |
| | NFPA-101 7.8 |
| | ** PLEASE ALSO KEEP IN MIND, FBC |
| | 13-415.AB.1.1,.1.2,.1.3 ALL APPLY TO COOLER WALK IN |
| | LIGHTS. |
| | |
| | 9) NOTE: ** PLEASE COORDINATE ALL PLANS AND REQUIRED |
| | CIRCUITING/LOADS. |
| | |
| | A) THE WP GFI SHOWN ON THE MECHANICAL PLANS INDICATES |
| | THIS RECEPTACLE BEING CIRCUITED TO A-4. HOW IS THIS |
| | POSSIBLE WHEN A2,4 IS THE SAME CIRCUIT FOR CONDENSING |
| | UNIT? |
| | PLEASE SEE 210.63, 210.8B |
| | |
| | B) PLEASE SEE M SHEETS AS THE WIC EVAPORATOR CIRCUIT IS |
| | SHOWN AS 18/20, HOWEVER PER PANEL *A* SCHEDULE 18 IS |
| | PART OF THE AHU-2 CIRCUIT AND 20/22 IS THE WIC CIRCUIT. |
| | |
| | C) PLEASE SEE POWER PLANS. WHERE IS THE ELECTRICAL FOR |
| | THE WIC UNIT INSIDE THE COOLER? A J-BOX SYMBOL IS SHOWN |
| | ON PLANS, HOWEVER NO CIRCUIT, NO DISCONNECT ETC IS |
| | SHOWN. |
| | |
| | 10) NOTE: WHEN FIGURING SHOW WINDOW LOAD FOR SERVICE |
| | 220.43A MUST BE USED AND FIGURED. ONLY 220.14G MAY BE |
| | USED FOR BRANCH CIRCUIT WHEN NOT USING 200 VA PER FT. |
| | |
| | 11) NOTE: PLEASE SEE NEC 422.13 AS STORAGE TYPE WATER |
| | HEATERS ARE REQUIRED TO HAVE LOADS FIGURED AT 125%. |
| | THIS WAS A CHANGE IN THE 2005 NEC IN WHICH THESE TYPES |
| | OF WATER HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD. |
| | PLEASE SEE THE LAST LINE IN THE COMMENTARY SECTION OF |
| | 422.13 IN THE NEC HANDBOOK. |
| | |
| | 12) NOTE: THE PLANS INDICATE THERE IS GOING TO BE A |
| | SPRINKLER PUMP AND IT WILL BE ON THE TIME CLOCK. |
| | HOWEVER THE LOAD SHOWN FOR TIME CLOCK IS 180VA. THIS IS |
| | NOT POSSIBLE FOR AN IRRIGATION PUMP. THIS IS SHOWN AS |
| | SINGLE PHASE PUMP, PER NEC 430.248, EVEN THE SMALLEST |
| | 115V PUMP AS 1/6TH HP HAS A VA MUCH HIGHER THAN 180VA. |
| | WHERE IS THE PUMP GOING TO BE LOCATED? THE PLANS |
| | INDICATE THE RECEPTACLE IN THE FRONT OF THE STORE ALONG |
| | AN INSIDE COUNTER. |
| | THE LANDSCAPE PLANS DO NOT DETAIL PUMP LOCATION. |
| | |
| | ** AS THERE IS INFORMATION NOT YET COMPLETE OR SHOWN ON |
| | PLANS, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |