Plan Review Details - Permit 09090413
Plan Review Stops For Permit 09090413
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-09 Cont ID  
Sent By dpalmer Date 2009-10-09 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2009-10-09 Time 19:00 Sent To  
Notes
2009-10-09 19:00:15 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE FAC 69A-3.012 AS THE NFPA-30 NOTED
 ON PLANS SHOULD BE THE 2003 EDITION. PLEASE SEE FBC
 2007 W/2009 REVISIONS ALONG WITH FAC 69A-3.012 ETC AS
 THE CURRENT EDITION OF THE NEC IS THE 2005 EDITION. ALL
 PERMIT APPLICATIONS AFTER DECEMBER 8TH, 2006 AND UP TOT
 OCT 1ST 2009 ARE UNDER THE 2005 NFPA-70.
 STATING LATEST EDITION ON PLANS IS NOT PERMITTED AS THE
 LATEST EDITION COULD PLACE PROJECT INTO ANOTHER CODE.
  
 2) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 ON PLANS AND WIRING METHODS PER NEC 514.3. PLEASE SEE
 THE NEC HANDBOOK AS SEVERAL FIGURES AND DETAILS ARE
 PROVIDED FOR REFERENCE AND MINIMUMS.
 PLEASE SHOW TYPICAL DETAILS FOR SEAL-OFFS AND WIRING
 METHOD DETAILS. 514.8
 PLEASE SHOW LOCATION OF NEW OR EXISTING EMERGENCY
 DISCONNECTS PER 514.11A, B AND C.
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 3) NOTE: CONDUCTORS, OVER CURRENT PROTECTION SIZES
 COORDINATING WITH PUMP DETAILS NEEDS TO BE ON PLANS.
 PLEASE SEE 310.16,240.4 AND 408.4 FOR PANEL SCHEDULE.
  
 ** FBC ADMINISTRATIVE SECTION FRO ADDITIONAL
 INFORMATION ON PLANS TO SHOW MINIMUM CODE COMPLIANCE.
 106.1.1,106.1.2, 106.3.5.1.2 AS ADOPTED BY THE CITY OF
 WEST PALM BEACH
  
  
  
  
 **IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 14:16 Sent To  
Notes
2009-09-30 08:53:29MOVED TO C-26. RJR
2009-09-22 14:17:11GAVE TO RON, ROUTED ON 9/22, LM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-30 Cont ID  
Sent By rregueir Date 2009-09-30 Time 09:05 Rev Time 0.00
Received By rregueir Date 2009-09-30 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-07 Cont ID  
Sent By aaponte Date 2009-10-07 Time 11:54 Rev Time 0.00
Received By aaponte Date 2009-10-07 Time 11:54 Sent To  
Notes
2009-10-07 11:54:51FUEL TANK SHALL BE LOCATED A MINIMUM OF 25 FEET FROM
 PUBLIC RIGHT-OF-WAY.