Plan Review Details - Permit 09090411
Plan Review Stops For Permit 09090411
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-10-20 Cont ID  
Sent By jwitmer Date 2009-10-20 Time 16:46 Rev Time 0.50
Received By jwitmer Date 2009-10-20 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-06-10 Cont ID  
Sent By btrobaug Date 2010-06-10 Time 10:00 Rev Time 0.00
Received By btrobaug Date 2010-06-10 Time 09:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-09 Cont ID  
Sent By dpalmer Date 2009-10-09 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2009-10-09 Time 19:10 Sent To  
Notes
2009-10-09 19:12:04 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE FAC 69A-3.012 AS THE NFPA-30 NOTED
 ON PLANS SHOULD BE THE 2003 EDITION. PLEASE SEE FBC
 2007 W/2009 REVISIONS ALONG WITH FAC 69A-3.012 ETC AS
 THE CURRENT EDITION OF THE NEC IS THE 2005 EDITION. ALL
 PERMIT APPLICATIONS AFTER DECEMBER 8TH, 2006 AND UP TOT
 OCT 1ST 2009 ARE UNDER THE 2005 NFPA-70.
 STATING LATEST EDITION ON PLANS IS NOT PERMITTED AS THE
 LATEST EDITION COULD PLACE PROJECT INTO ANOTHER CODE.
  
 2) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 ON PLANS AND WIRING METHODS PER NEC 514.3. PLEASE SEE
 THE NEC HANDBOOK AS SEVERAL FIGURES AND DETAILS ARE
 PROVIDED FOR REFERENCE AND MINIMUMS.
 PLEASE SHOW TYPICAL DETAILS FOR SEAL-OFFS AND WIRING
 METHOD DETAILS. 514.8
 PLEASE SHOW LOCATION OF NEW OR EXISTING EMERGENCY
 DISCONNECTS PER 514.11A, B AND C.
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 3) NOTE: CONDUCTORS, OVER CURRENT PROTECTION SIZES
 COORDINATING WITH PUMP DETAILS NEEDS TO BE ON PLANS.
 PLEASE SEE 310.16,240.4 AND 408.4 FOR PANEL SCHEDULE.
  
 ** FBC ADMINISTRATIVE SECTION FRO ADDITIONAL
 INFORMATION ON PLANS TO SHOW MINIMUM CODE COMPLIANCE.
 106.1.1,106.1.2, 106.3.5.1.2 AS ADOPTED BY THE CITY OF
 WEST PALM BEACH
  
  
  
  
 **IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-06-07 Cont ID  
Sent By mawillia Date 2010-06-07 Time 16:20 Rev Time 0.00
Received By mawillia Date 2010-06-07 Time 16:02 Sent To  
Notes
2010-06-07 16:16:12*****APPROVED*****
  
 THE COMMENT FROM THE PREVIOUS REVIEW HAS BEEN
 ADDRESSED; DRAWING # 314-G-001 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-28 Cont ID  
Sent By   Date 2009-10-28 Time 15:28 Rev Time 0.00
Received By mawillia Date 2009-10-28 Time 14:54 Sent To  
Notes
2009-10-28 15:27:17*****PARTIAL APPROVAL*****
  
  
 1. AMEND THE FOLLOWING GENERAL NOTES FOR FUEL
 INSTALLATION ON DRAWING # 314-G-001: NOTE (1) THE 2003
 EDITION OF NFPA 30 AND 30A SHALL BE REFERENCED. NOTE
 (2) & (8) REFERENCE THE CITY OF WEST PALM BEACH NOT
 PALM BEACH CITY.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-05-26 Cont ID  
Sent By vmolina Date 2010-05-26 Time 10:37 Rev Time 0.00
Received By vmolina Date 2010-05-26 Time 10:37 Sent To  
Notes
2010-05-26 10:40:45C-15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-28 Time   Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 14:15 Sent To  
Notes
2009-09-30 09:17:25MOVED TO C-26. RJR
2009-09-22 14:15:45GAVE TO RON, ROUTED ON 9/22, LM

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2010-06-23 Cont ID  
Sent By rkussner Date 2010-06-23 Time 17:32 Rev Time 0.00
Received By rkussner Date 2010-06-23 Time 17:32 Sent To  
Notes
2010-06-23 17:34:59***LANDSCAPE REVIEW PASSED WITH "PROVISO"***
  
 MUST APPLY FOR SEPARATE LANDSCAPE AND IRRIGAION
 PERMITS, GET THEM APPROVED AND SUCCESSFULLY INSPECTED
 PRIOR TO C/O. RAK

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-06-11 Cont ID  
Sent By rkussner Date 2010-06-11 Time 15:19 Rev Time 0.00
Received By rkussner Date 2010-06-11 Time 15:19 Sent To  
Notes
2010-06-11 15:32:42***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. LANDSCAPING REQUIRES A SEPARATE PERMIT. PLEASE APPLY
 FOR A LANDSCAPE PERMIT AND PROVIDE TWO COPIES OF THE
 PLAN THAT HAS BEEN SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT. . A COST ESTIMATE THAT INCLUDES
 THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR
 SHALL BE SUBMITTED WITH THE PLAN.
  
 2. PLEASE APPLY FOR AN IRRIGATION PERMIT. SUBMIT TWO
 COPIES OF AN IRRIGATION PLAN THAT SHOWS THE LAYOUT AND
 THE COMPONENTS OF THE SYSTEM.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-03-26 Cont ID  
Sent By rkussner Date 2010-03-26 Time 14:06 Rev Time 0.00
Received By rkussner Date 2010-03-26 Time 14:06 Sent To  
Notes
2010-03-26 14:13:52***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. REPEAT COMMENT: PURSUANT TO SECTION 94-443 (C) (3)
 (A), EACH ROW OF PARKING SPACES SHALL BE TERMINATED BY
 LANDSCAPE ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH
 (EXCLUDING THE REQUIRED CURB) AND NOT LESS THAN THE
 LENGTH OF THE ADJACENT PARKING STALL. THE LANDSCAPED
 ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR FLOWERING
 TREE. THE PROPOSED PARKING ROW NEEDS TO BE TERMINATED
 AT BOTH ENDS WITH LANDSCAPE ISLANDS. IN ADDITION, THE
 PROPOSED PARKING, AS SHOWN, DOES NOT FUNCTION. IT
 BLOCKS VEHICULAR TRAFFIC FROM CIRCULATING AROUND THE
 SITE AND OBSTRUCTS MOVEMENT IN AND OUT FROM THE PUMPS.
  
 3. REPEAT COMMENT: PURSUANT TO SECTION 94-443 (C) (4),
 FOR OTHER PAVED AREAS UTILIZED BY MOTOR VEHICLES,
 INCLUDING AISLES, LOADING AREAS, AND CIRCULATION AREAS,
 ADDITIONAL LANDSCAPING SHALL BE PROVIDED AS FOLLOWS:
 FOUR SQUARE FEET OF LANDSCAPED AREA SHALL BE REQUIRED
 FOR EACH 100 SQUARE FEET, OR FRACTION THEREOF. THIS
 CALCULATION HAS NOT BEEN PROVIDED AND THE CALCULATIONS
 THAT WERE PROVIDED DO NOT ALL MEET MINIMUM
 REQUIREMENTS. PLEASE SHOW HOW YOU ARRIVED AT THE OPEN
 SPACE. ALTERATIONS OF THE SITE WILL BE REQUIRED TO MEET
 THE MINIMUM STANDARDS.
  
 4. REPEAT COMMENTS: PURSUANT TO SECTION 94-443 (E), AT
 LEAST 30 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR
 OF ALL COMMERCIAL STRUCTURES SHALL BE PLANTED WITH
 TREES, SHRUBS OR HEDGES. NO FOUNDATION PLANTING HAS
 BEEN PROVIDED. THE SIDEWALK ALONG THE WEST BUILDING
 ELEVATION COULD BE REMOVED TO ALLOW FOR PLANTING.
  
 5. REPEAT COMMENT: PURSUANT TO SECTION 94-445 (4) (G)
 (3) (II), IN ALL AREAS THAT ARE TO BE PLANTED IN A
 CULTIVATED LANDSCAPE, IRRIGATION SYSTEMS SHALL BE
 DESIGNED TO HAVE 120 PERCENT COVERAGE. THIS INCLUDES
 THE RIGHTS-OF-WAY. THE PLAN INDICATES THAT ALL AREAS
 WILL RECEIVE 100% COVERAGE.
  
 6. REPEAT COMMENT: PURSUANT TO SECTION 94-443 (B) (2),
 THE BUFFER STRIP THAT SEPARATES THE NONRESIDENTIAL USE
 ADJACENT TO A PUBLIC THOROUGHFARE MAY NOT BE
 INTERRUPTED BY MORE THAN 25 PERCENT OF ITS REQUIRED
 LENGTH TO PROVIDE FOR SIGNS OR VEHICULAR INGRESS AND
 EGRESS. THE ACCESS POINTS ALONG SOUTH DIXIE HIGHWAY
 NEED TO BE REDUCED IN WIDTH THE SOUTH ACCESS SHALL BE
 REDUCED TO 24 FEET AND THE NORTH SHALL BE REDUCED TO 36
 FEET OR LESS. THIS DOES NOT MEET THE MINIMUM
 REQUIREMENTS BUT IT DECREASES THE NONCONFORMITY. THE
 ACCESS ALONG SOUTHERN BOULEVARD SHOULD BE REDUCED IF
 POSSIBLE.
  
 7. PURSUANT TO SECTION 94-448 (D) (2), ALL OF THE
 RELEVANT ITEMS ENUMERATED IN THIS SECTION SHALL BE
 SHOWN ON THE LANDSCAPE PLAN. PLEASE PROVIDE DETAILS OF
 THE VARIOUS 'VAULTS' SHOWN ON THE LANDSCAPE PLAN. THEY
 SHALL BE REMOVED IF THEY ARE NOT NEEDED.
  
 8. THE PROPOSED GATES FOR THE DUMPSTER ENCLOSURE CANNOT
 OPEN INTO A TRAVEL LANE AND THE REAR OF THE ENCLOSURE
 CANNOT ENCROACH INTO THE REQUIRED LANDSCAPE BUFFER.
  
 9. PURSUANT TO SECTION 94-443 (B) (2) (4), AT LEAST ONE
 (1) SHADE TREE SHALL BE PLANTED FOR EVERY 30 LINEAR
 FEET OR FRACTION THEREOF ALONG THE REQUIRED EAST
 BUFFER. THE TREES SHALL BE EVENLY SPACED.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-30 Cont ID  
Sent By rregueir Date 2009-09-30 Time 09:17 Rev Time 0.00
Received By rregueir Date 2009-09-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2010-10-27 Cont ID  
Sent By astelly Date 2010-10-27 Time 15:53 Rev Time 0.00
Received By astelly Date 2010-10-27 Time 15:52 Sent To  
Notes
2010-10-27 15:55:26AMY STELLY
 PLANNING AND ZONING
 822-1442
  
 PASSED W/ PROVISO
  
 VENTS MUST BE LOCATED IN ACCORDANCE WITH THE REVISED
 VENT SPACING DETAIL ATTACHED TO DRAWING.

Review Stop Z ZONING
Rev No 3 Status P Date 2010-06-24 Cont ID  
Sent By eschneid Date 2010-06-24 Time 15:17 Rev Time 0.50
Received By eschneid Date 2010-06-24 Time 15:16 Sent To  
Notes
2010-06-24 15:19:29PER ANGELLA VANN:
  
 PASSED W/PROVISOS
  
 1) PRIOR TO CSD FINAL - LANDSCAPE PERMIT REQ. AND SHALL
 BE INSTALLED AND RECEIVE FINAL (502).
  
 2) PRIOR TO CSD FINAL - ALL CONDITIONS OF ZBA SHALL BE
 COMPLIED WITH. REQ. ZONING FINAL (507).
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-04-07 Cont ID  
Sent By astelly Date 2010-04-07 Time 11:25 Rev Time 0.00
Received By astelly Date 2010-04-07 Time 11:25 Sent To  
Notes
2010-04-07 11:41:25AMY STELLY
 PLANNING AND ZONING
 561-1442
  
 THE FOLLOWING CONDITIONS FROM THE APRIL 2010 ZONING
 BOARD OF APPEALS (ZBA) MUST BE SATISFIED PRIOR TO
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY (CO):
  
 1. ALL EXTERIOR SITE LIGHTING SHALL UTILIZE FIXTURES
 THAT CONFORM TO THE ILLUMINATING ENGINEERING SOCIETY OF
 NORTH AMERICA (IESNA) FULL CUTOFF SPECIFICATIONS. A
 PHOTOMETRIC PLAN MUST BE SUBMITTED FOR REVIEW.
  
 2. THE CITY OF WEST PALM BEACH POLICE DEPARTMENT ???
 CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE THE
 CONSTRUCTION DRAWINGS TO ENSURE THE ADHERENCE TO THE
 STATE OF FLORIDA CONVENIENCE BUSINESS SECURITY ACT (FSS
 812.1701 ??? 812.175). PLANS OF THE C-STORE SHOWING ALL
 SECURITY UPGRADES MUST BE SUBMITTED FOR REVIEW.
  
 3. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 NO LOITERING AND NO TRESPASSING SIGNS SHALL BE POSTED
 AT CONSPICUOUS LOCATIONS ON THE PROPERTY.
  
 4. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. A
 LANDSCAPE PLAN MUST BE SUBMITTED FOR REVIEW.
  
 5. A SITE PLAN MUST BE SUBMITTED FOR REVIEW SHOWING
 FOUR REQUIRED PARKING SPACES.
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-12 Cont ID  
Sent By jroach Date 2009-10-12 Time 20:28 Rev Time 0.00
Received By jroach Date 2009-10-12 Time 20:28 Sent To  
Notes
2009-10-12 20:28:57ZONING PLAN REVIEW
  
 PERMIT NO.: 09090411
 ADDRESS: 4000 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT: THOMAS R. BERGSTRESSER
 TELEPHONE NO.: 813.677.7803
 SCOPE OF REVIEW: REPLACEMENT OF EXISTING UNDERGROUND
 STORAGE TANKS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO THE CITY???S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS), THE USE OF THE PROPERTY FOR MOTOR
 VEHICLE FUEL SALES AND ACCESSORY CONVENIENCE STORE
 SHALL REQUIRE THE ISSUANCE OF A CLASS B SPECIAL USE
 PERMIT BY THE ZONING BOARD OF APPEALS (ZBA). WHILE THE
 PROPERTY WAS PREVIOUSLY UTILIZED FOR SUCH USE, AS THE
 SUBJECT PROPERTY HAS BEEN ABANDONED FOR AT LEAST ONE
 (1) YEAR, THE PROPERTY IS NO LONGER
 ???GRANDFATHERED???. PLEASE CONTACT ME REGARDING
 APPLICATION FOR THE CLASS B SPECIAL USE PERMIT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved