Plan Review Details - Permit 09090338
Plan Review Stops For Permit 09090338
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2010-04-28 Cont ID  
Sent By jgomez Date 2010-04-28 Time 09:42 Rev Time 0.00
Received By jgomez Date 2010-04-28 Time 09:42 Sent To  
Notes
2010-04-28 09:46:06ACCORDING TO DOUG WISE. NEED TO VOID THIS PERMIT AND
 APPLY FOR NEW PERMIT. SCOPE OF WORK RESUBMITTED IS
 COMPLETELY DIFFERENT FROM WHAT WHAT'S SUBMITTED
 ORIGINALLY. ONLY THE PLAN REVIEW FEES ARE CHARGED ON
 THIS PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-04-08 Cont ID  
Sent By jgomez Date 2010-04-08 Time 13:22 Rev Time 0.00
Received By jgomez Date 2010-04-08 Time 13:09 Sent To  
Notes
2010-04-08 13:23:06RECEIVED 2ND SET OF PLANS. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date 2010-04-07 Cont ID  
Sent By jgomez Date 2010-04-07 Time 14:25 Rev Time 0.00
Received By jgomez Date 2010-04-07 Time 14:25 Sent To  
Notes
2010-04-07 14:36:22BUILDING REVIEW APPROVED WITH PROVISO (PLANS WILL BE
 STAMPED WHEN REQUESTED INFORMATION IS PROVIDED):
  
 1- ONLY ONE SIGNED AND SEALED SET OF PLANS WAS
 PROVIDED. NEED TO PROVIDE TWO COMPLETE SETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2010-04-05 Cont ID  
Sent By jgomez Date 2010-04-05 Time 16:06 Rev Time 0.00
Received By jgomez Date 2010-04-05 Time 15:59 Sent To  
Notes
2010-04-05 16:06:52BUILDING REVIEW APPROVED WITH PROVISO (PLANS WILL BE
 STAMPED WHEN REQUESTED INFORMATION IS PROVIDED):
  
 1- ONLY ONE SIGNED AND SEALED SET OF PLANS WAS
 PROVIDED. NEED TO PROVIDE TWO COMPLETE SETS.
  
 2- ONLY ONE SET OF WINDOWS PRODUCT APPROVAL WAS
 PROVIDED. NEED TO PROVIDE TWO SETS. PLEASE MAKE SURE
 BOTH SETS ARE REVIEWED AND APPROVED IN WRITING BY THE
 ENGINEER OF RECORD.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR WINDOW MULLIONS AS SHOWN ON PLANS ON
 THE FLORIDA ROOM. AND, ENGINEER OF RECORD TO REVIEW IT
 AND APPROVE IT IN WRITING PRIOR TO SUBMITTAL. (NONE WAS
 SUBMITTED AT THIS TIME).
  
 4- CLARIFY IF INSTALLING THE PRE-MANUFACTURED GARAGE
 WITH THIS PERMIT. PLANS FROM THE DEPARTMENT OF
 COMMUNITY AFFAIRS ARE FOR A SHED BUILDING. NOT A
 GARAGE. PROVIDE PLANS FOR AN APPROVED PRE- MANUFACTURED
 GARAGE BUILDING. PROVIDE TWO COPIES AND TWO COPIES OF
 THE ENGINEERED (SIGNED AND SEALED) ANCHORING DETAILS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-13 Cont ID  
Sent By jgomez Date 2009-10-13 Time 16:10 Rev Time 0.00
Received By jgomez Date 2009-10-13 Time 16:04 Sent To PC
Notes
2009-10-13 16:11:33RESIDENTIAL (R3) GARAGE ADDITION, BUILDING REVIEW
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION CALLS FOR NEW DETACHED GARAGE AND
 DRIVEWAY EXTENSION. PLANS SUBMITTED INCLUDE BEDROOM
 ADDITION. AS PER CONVERSATION WITH OWNER, THE BEDROOM
 ADDITION IS NOT PART OF THIS PERMIT APPLICATION. REVISE
 PLANS AS REQUIRED. ALSO, PLANS TO MATCH SURVEY.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT
 PICK UP.
  
 3- ENGINEER OF RECORD TO SIGN AND SEAL BOTH SETS OF
 PLANS. CHAPTER 471 FLORIDA STATUTE. SIGN AND SEAL ALL
 PAGES.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) GARAGE DOOR.
 B) EXTERIOR OUTSWING DOOR.
 C) SINGLE HUNG WINDOWS.
 D) SHINGLES.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 6- PROVIDE COMPLETE FRAMING DETAILS FOR GARAGE AND
 EXTERIOR SWING DOOR TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.
  
 7- GARAGE ROOF PITCH OF 3:12 REQUIRES 2 LAYERS OF
 UNDERLAYMENT. SEC. R905.2.2.
  
 8- REVISE WINDOW NOTE #3 ON SHEET #1. SEE PRODUCT
 APPROVAL FOR MAXIMUM SHIM ALLOWED.
  
 9- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2010-04-08 Cont ID  
Sent By jgomez Date 2010-04-08 Time 13:25 Rev Time 0.00
Received By jgomez Date 2010-04-08 Time 13:25 Sent To  
Notes
2010-04-08 13:26:31NO ELECTRICAL WORK. SCOPE OF WORK REVISED FOR
 PREMANUFACTURED SHED AND REPLACEMENT OF 3 WINDOWS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-08 Cont ID  
Sent By dpalmer Date 2009-10-08 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 15:45 Sent To  
Notes
2009-10-08 15:46:01** DENIED**
  
  
 1) NOTE: PERMIT APPLICATION STATES TO BUILD A NEW
 DETACHED GARAGE HOWEVER THE PLANS ALSO INCLUDE A
 REMODEL AND ADDITION TO THE EXISTING DWELLING INCLUDING
 NEW BEDROOM. WHAT IS THE ACTUAL SCOPE OF WORK?
 THIS AFFECTS THE REVIEW BEING DONE FOR MINIMUM CODE
 COMPLIANCE.
 PLEASE DESCRIBE PROJECT AND APPLIED SCOPE OF WORK. SEE
 NOTES BELOW AS SCOPE OF WORK FOR ELECTRICAL IS ALSO IN
 QUESTION.
 105.1, 106.1.1, 106.5 FOR CLARITY OF RECORD PLANS AND
 APPLIED SCOPE OF WORK
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE
 PLACED ON PLANS FOR MINIMUM DESIGN.
 2007 FBC W/ 2009 REVISIONS
 2002 NFPA-72
 2005 NFPA-70
  
 ** REQUIRED MINIMUMS. STATING THE NATIONAL ELECTRICAL
 CODE COULD MEAN SEVERAL CODE EDITIONS.
  
 3) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING
 DWELLING SHOWING NEW OR EXISTING SMOKE ALARMS MEETING
 CURRENT NFPA-72 CODES.
 PLEASE SEE R313.1.2 AS THIS REQUIRES SMOKE ALARMS TO BE
 BROUGHT UP TO CODE.
 PLEASE SEE NFPA-72 11.5.1, 11.8.3 FOR CURRENT
 REQUIREMENTS INSIDE AND OUTSIDE ALL SLEEPING ROOMS ETC.
  
 4) NOTE: THE ELECTRICAL PLANS CONTAINS A NOTE FOR THE
 RISER WHICH STATES TO *REMOVE AND UPGRADE* EXISTING
 SERVICE YET NO NEW INFORMATION IS SHOWN FOR NEW
 SERVICE, NEW AIC RATINGS, NEW SERVICE CONDUCTORS,
 MAINS, NO OVER CURRENT PROTECTION FOR SUB PANEL ETC.
 CODE COMPLIANCE FOR MANY ITEMS CAN NOT BE REVIEWED IF
 INFORMATION IS NOT SUBMITTED SHOWING MINIMUM.
 PLEASE SEE 230.70, 230.71, 310.16,240.4,110.9, 215.5
 ETC
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR SERVICE
 PER NEC 220
  
 6) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED GARAGE.
  
 7) NOTE: BATH CIRCUIT(S) PER 210.11C3
  
 8) NOTE: ARC FAULT PROTECTION PER 210.12
  
 ** PLEASE KNOW THAT AS THERE IS INFORMATION NOT YET
 SHOWN FOR MINIMUM CODE COMPLIANCE THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-05 Cont ID  
Sent By jgomez Date 2010-04-05 Time 16:11 Rev Time 0.00
Received By jgomez Date 2010-04-01 Time 08:53 Sent To  
Notes
2010-04-01 08:55:57INCOMING SENT TO R-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-13 Cont ID  
Sent By jgomez Date 2009-10-13 Time 16:11 Rev Time 0.00
Received By jgomez Date 2009-09-16 Time 10:42 Sent To  
Notes
2009-09-17 10:45:00R-14

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2010-04-26 Cont ID  
Sent By rkussner Date 2010-04-26 Time 11:17 Rev Time 0.00
Received By rkussner Date 2010-04-26 Time 11:17 Sent To  
Notes
2010-04-26 11:19:32***LANDSCAPE REVIEW NOT REQUIRED***
  
 THE SCOPE OF WORK AND THE COST WAS CHANGED TO BE LESS
 THAN 50% OF THE IMPROVEMENT VALUE. THEREFORE, NO
 LANDSCAPING IS REQUIRED.---RAK

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-09-29 Cont ID  
Sent By rkussner Date 2009-09-29 Time 17:47 Rev Time 0.00
Received By rkussner Date 2009-09-29 Time 17:47 Sent To  
Notes
2009-09-29 18:00:20***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-441 (C)(2), A COMPLETE
 LANDSCAPE PLAN IS REQUIRED WHEN RENOVATIONS, REPAIR,
 ALTERATION OR REDEVELOPMENT EXCEEDS 50 PERCENT OF THE
 VALUE OF THE STRUCTURE. PLEASE SUBMIT A LANDSCAPE PLAN
 AND PROVIDE THE TABULATION NECESSARY FOR THE EVALUATION
 OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 2. PURSUANT TO SECTION 94-448 (D)(2), THE LANDSCAPE
 PLAN SHALL INCLUDE ALL OF THE ITEMS MENTIONED IN THIS
 SECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop P PLUMBING
Rev No 2 Status N Date 2010-04-08 Cont ID  
Sent By jgomez Date 2010-04-08 Time 13:24 Rev Time 0.00
Received By jgomez Date 2010-04-08 Time 13:24 Sent To  
Notes
2010-04-08 13:25:11NO PLUMBING WORK. SCOPE OF WORK REVISED FOR
 PREMANUFACTURED SHED AND REPLACING 3 WINDOWS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 09:15 Rev Time 0.00
Received By kstevens Date 2009-09-21 Time 09:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-27 Cont ID  
Sent By lfranco Date 2010-04-27 Time 13:41 Rev Time 0.50
Received By lfranco Date 2010-04-27 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-01 Cont ID  
Sent By lfranco Date 2009-10-01 Time 16:23 Rev Time 0.00
Received By lfranco Date 2009-10-01 Time 16:23 Sent To  
Notes
2009-10-02 17:02:50PLANNING AND ZONING: ***** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING. REVISIONS MAY
 GENERATE ADDITIONAL COMMENTS.
  
 2. THE SURVEY DOES NOT CORRELATE WITH THE SITE PLAN/
 FLOOR PLAN ON SHEET 1. FOR EXAMPLE, THE SURVEY DOES NOT
 SHOW THE EXISTING SHED, ADJACENT TO THE CORNER OF THE
 HOUSE, PLEASE CLARIFY.
  
 3. SHEET 1 DATED 9/9/09 - PROVIDE LOCATION OF
 COLUMN/STRUCTURAL SUPPORT FOR THE EXISTING COVERED
 PATIO. PROVIDE REMAINDER DIMENSION BETWEEN INTERIOR
 EDGE AND ACCESS DRIVE CLEARANCE. THE VEHICLE TURNING
 RADIUS FOR MANEUVERING IS VERY TIGHT; THERE IS NO ROOM
 FOR BACK-OUT SPACE FOR THE VEHICLE TO TURN AROUND TO
 EGRESS (EXIT) THE DRIVEWAY IN THE REAR. PROVIDE BACK-UP
 AREA, AT SOUTH SIDE OF A MINIMUM OF 13 FEET DEEP BY 20
 FEET WIDE (THE WIDTH DIMENSION WILL BE FROM THE
 WESTERN-MOST CORNER OF THE PROPOSED DRIVE, HEADING
 EAST). ALSO, CONSIDER ROUNDING OUT THE INTERIOR CORNER
 EDGE OF THE DRIVE-WAY TO ALLOW FOR MANEUVERING.
  
 4. PROVIDE TOTAL HEIGHT OF DETACHED GARAGE.
  
 PLEASE CONTACT ME, SHOULD YOU HAVE ANY QUESTIONS.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  