Plan Review Details - Permit 09090334
Plan Review Stops For Permit 09090334
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-01-05 Cont ID  
Sent By rmcdouga Date 2010-01-05 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2010-01-05 Time 16:46 Sent To  
Notes
2010-01-05 16:46:57PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-21 Cont ID  
Sent By rmcdouga Date 2009-12-21 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2009-12-21 Time 14:10 Sent To  
Notes
2009-12-21 14:10:47SECOND SET OF PLANS WAS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-17 Cont ID  
Sent By rmcdouga Date 2009-12-17 Time 11:58 Rev Time 0.00
Received By rmcdouga Date 2009-12-17 Time 11:58 Sent To  
Notes
2009-12-17 12:01:29ALTHOUGH BUILDING COMMENTS HAVE BEEN ADDRESSED, ONLY
 ONE SET OF REVISED DRAWINGS WERE SUBMITTED. TWO
 COMPLETE SETS OF PLANS ARE REQUIRED. SUBMIT ADDITIONAL
 SET OF PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By rmcdouga Date 2009-10-26 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2009-10-26 Time 13:29 Sent To  
Notes
2009-10-26 13:47:152007 FBC W/2009 REVISIONS
 REPAIRS
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR ENTRY AND REAR DOORS AS REQUIRED BY DCA RULE
 9B-72.
  
 2) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE NEW
 WINDOWS AS REQUIRED BY DCA RULE 9B-72, IF THEY ARE
 BEING REPLACED. PRODUCT APPROVALS ARE NOT REQUIRED IF
 ONLY THE GLAZING IS TO BE REPLACED AND THE EXISTING
 FRAMES REMAIN IN THE OPENINGS.
  
 3) SHOW THE LOCATIONS OF THE SMOKE ALARMS ON THE PLANS
 AS REQUIRED BY FBC R313.2 AND R313.2.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2009-10-26 10:46:40 
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 09:59 Rev Time 0.00
Received By btrobaug Date 2010-01-12 Time 09:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 09:35 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 08:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By btrobaug Date 2009-10-26 Time 10:48 Rev Time 0.00
Received By btrobaug Date 2009-10-26 Time 10:41 Sent To  
Notes
2009-10-26 10:53:29 
  
 DENIED INCOMPLETE INFORMATION
  
 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO
 ELECTRICAL WORK IN THE DESCRIPTION ON THE
 APPLICATION.SUBMIT PLANS INDICATING THE SCOPE OF WORK.
 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-01-05 Cont ID  
Sent By mawillia Date 2010-01-05 Time 15:10 Rev Time 0.00
Received By mawillia Date 2010-01-05 Time 14:57 Sent To  
Notes
2010-01-05 15:04:55*****APPROVED*****
  
  
 PLAN SHEETS A-1, LS-1, AND E-1 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-12-17 Cont ID  
Sent By mawillia Date 2009-12-17 Time 13:53 Rev Time 0.00
Received By mawillia Date 2009-12-17 Time 13:26 Sent To  
Notes
2009-12-17 13:53:21*****PARTIAL APPROVAL*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED AS FOLLOWS:
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION. ON SHEET LS-1, RED-LINE TO 241 INSTEAD OF 214
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED. ON SHEET LS-1
  
 3. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF
 THE SPACE OF DETERMINED AS THE MAXIMUM PROABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER. ON SHEET LS-1
  
 4. SPECIFY INTERIOR FINISH FOR WALLS AND CEILINGS IN
 TERMRS OF CLASS A, CLASS B, OR CLASS C. ON SHEET LS-1
  
 5. SHOW THE LOCATION OF THE SMOKE ALARMS WHICH SHALL BE
 INSTALLED OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS. PLEASE BE ADVISED THAT SMOKE
 ALARMS, WITH BATTERY BACK-UP, SHALL RECEIVE THEIR
 OPERATING POWER FROM THE BUILDING ELECTRICAL SYSTEM. ON
 SHEET A-1 & E-1
  
 6. SHOW LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S). THIS MAY BE ACCOMPLISHED BY EITHER ONE
 OF THE FOLLOWING: 1) PROVIDE ONE FIRE EXTINGUISHER ON
 THE OUTSIDE COMMON TO ALL THREE DWELLING UNITS OR 2)
 PROVIDE ONE EXTINGUISHER INSIDE EACH DWELLING UNIT. ON
 SHEET LS-1
  
 7. VERIFY THAT THE NUMERICAL ADDRESS FOR THE BUILDING
 (AT LEAST 6" IN HEIGHT AND 1" IN WIDTH) IS VISIBLE FROM
 5TH STREET. IN ADDITION EACH DWELLING UNIT DESIGNATION
 (AT LEAST 3" IN HEIGHT AND 1" IN WIDTH) IS POSTED.
 UNDERSTOOD BY CONTRACTOR
  
 PLEASE BE ADVISED HOWEVER THAT ONLY ONE SET OF PLANS
 HAVE BEEN SUBMITTED; PLANS HEETS A-1, LS-1, AND E-1 TO
 BE FIRE-STAMPED WHEN AN ADDITIONAL, NO MORE THAN TWO
 ADDITIONAL, PLAN SET HAS BEEN SUBMITTED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 12:37 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 11:54 Sent To  
Notes
2009-10-26 12:36:56*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF
 THE SPACE OF DETERMINED AS THE MAXIMUM PROABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
 4. SPECIFY INTERIOR FINISH FOR WALLS AND CEILINGS IN
 TERMRS OF CLASS A, CLASS B, OR CLASS C.
  
 5. SHOW THE LOCATION OF THE SMOKE ALARMS WHICH SHALL BE
 INSTALLED OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS. PLEASE BE ADVISED THAT SMOKE
 ALARMS, WITH BATTERY BACK-UP, SHALL RECEIVE THEIR
 OPERATING POWER FROM THE BUILDING ELECTRICAL SYSTEM.
  
 6. SHOW LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S). THIS MAY BE ACCOMPLISHED BY EITHER ONE
 OF THE FOLLOWING: 1) PROVIDE ONE FIRE EXTINGUISHER ON
 THE OUTSIDE COMMON TO ALL THREE DWELLING UNITS OR 2)
 PROVIDE ONE EXTINGUISHER INSIDE EACH DWELLING UNIT.
  
 7. VERIFY THAT THE NUMERICAL ADDRESS FOR THE BUILDING
 (AT LEAST 6" IN HEIGHT AND 1" IN WIDTH) IS VISIBLE FROM
 5TH STREET. IN ADDITION EACH DWELLING UNIT DESIGNATION
 (AT LEAST 3" IN HEIGHT AND 1" IN WIDTH) IS POSTED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 09:59 Rev Time 0.00
Received By btrobaug Date 2010-01-12 Time 09:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 14:45 Sent To  
Notes
2009-12-14 14:46:32R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-28 Cont ID  
Sent By kstevens Date 2009-10-28 Time 09:59 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 10:47 Sent To  
Notes
2009-09-17 10:48:19R-15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By rmcdouga Date 2009-12-21 Time 14:15 Rev Time 0.00
Received By rmcdouga Date 2009-12-21 Time 14:15 Sent To  
Notes
2009-12-21 14:16:36MECHANICAL EQUIPMENT TO BE REPLACED LIKE FOR LIKE IN
 EXISTING LOCATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By rregueir Date 2009-10-26 Time 11:16 Rev Time 0.00
Received By rregueir Date 2009-10-26 Time 11:14 Sent To  
Notes
2009-10-26 11:15:41PROVIDE EQUIPMENT SCHEDULE FOR NEW EQUIPMENT TO BE
 INSTALLED. INDICATE WHETHER THIS IS A LIKE-FOR-LIKE
 CHANGE OUT OR IF ANY EQUIPMENT SIZES ARE BEING CHANGED.
 CHANGES IN EQUIPMENT SIZE WILL REQUIRE COOLING AND
 HEATING LOAD CALCULATIONS TO BE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By rmcdouga Date 2009-12-21 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2009-12-21 Time 14:11 Sent To  
Notes
2009-12-21 14:14:36PLUMBING PERMIT REQUIRED TO REPLACE WATER HEATERS.
 EXISTING IRRIGATION SYSTEM WAS FOUND TO BE WORKING.

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-10-28 Cont ID  
Sent By kstevens Date 2009-10-28 Time 09:49 Rev Time 0.00
Received By kstevens Date 2009-10-28 Time 09:49 Sent To  
Notes
2009-10-28 09:51:18AN IRRIGATION PERMIT AND A PLUMBING PERMIT IS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-05 Cont ID  
Sent By aaponte Date 2010-01-05 Time 13:47 Rev Time 0.00
Received By aaponte Date 2010-01-05 Time 13:47 Sent To  
Notes
2010-01-05 13:59:07PROVISO:
 A REVISED SITE PLAN SHALL BE SUBMITTED INCLUDING THE
 PARKING SPACES ALLOWED BYTHE WIDTH OF THE APPROACH. THE
 REMAINING AREA SHALL BE MARKED AS NO PARKING AREA.
 WHEEL STOPS SHALL BE AT SCALE.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By aaponte Date 2009-10-26 Time 15:27 Rev Time 0.00
Received By aaponte Date 2009-10-26 Time 15:27 Sent To  
Notes
2009-10-26 15:41:59NOTES ON PLAN A-1 INDICATE LANDSCAPING AND SPRINKLER
 SYSTEM WILL BE INSTALLED, BUT DRAWINGS DEPICTING
 PROPOSED WORK WERE NOT SUBMITTED.
 NOTES ON PLAN A-1 INDICATE REMOVAL AND REPLACEMENT OF
 WHEEL STOPS, BUT DRAWINGS DEPICTING PROPOSED WORK WERE
 NOT SUBMITTED.
 PLEASE SUBMIT SITE PLAN INDICATING LANDSCAPE
 IMPROVEMENTS AND SITE IMPROVEMENTS. PROPERTY LINES
 SHALL BE INCLUDED.
 PLEASE SUBMIT A SURVEY OF THE PROPERTY.
2009-10-26 10:52:15 
  
 DENIED/INCOMPLETE INFORMATION
  
  
 THE DESCRIPTION ON THE APPLICATION INDICATES ELECTRICAL
 WORK TO BE DONE UNDER THIS PERMIT BUT NO ELECTRICAL
 PLANS WERE SUBMITTED. SUBMIT PLANS INDICATING THE SCOPE
 OF WORK.. 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  