Plan Review Details - Permit 09090230
Plan Review Stops For Permit 09090230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-28 Cont ID  
Sent By jwitmer Date 2009-12-28 Time 13:58 Rev Time 0.77
Received By jwitmer Date 2009-12-28 Time 13:58 Sent To  
Notes
2009-12-28 14:03:42BUILDING PLAN REVIEW
 PERMIT: 09090230
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETREMINED
 TEL: (561) 494-1106
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 PLANS APPEAR TO BE CODE COMPLIANT PLANS WILL BE STAMP
 ONCE A LICENSED CONTRACTOR HAS SIGNED ON, LICESURE
 CHECKED AND FEES PAID.
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) SHEET S-03-02 METERING PUMP BUILDING: RED LINED TO
 BE UNDER SEPERATE PERMIT, FEES AND REVIEW.
  
 2) THE PLANS ALSO INDICATE THE INSTALATION OF A
 PRE-ENGINEERED ALUMINUM CANOPY. PLANS ARE RED LINED TO
 BE UNDER A SEPERATE PERMIT, FEES AND REVIEW.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By jwitmer Date 2009-09-22 Time 15:58 Rev Time 1.25
Received By jwitmer Date 2009-09-22 Time 14:38 Sent To  
Notes
2009-09-22 16:23:50BUILDING PLAN REVIEW
 PERMIT: 09090230
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETREMINED
 TEL: (561) 494-1106
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-03-02 METERING PUMP BUILDING:
  
 1A) THE PLANS INDICATE THIS IS TO BE A PRE-MANUFACTURED
 BUILDING. IF THIS IS A MANUFACTURED BUILDING THAT IS
 BROUGHT TO THE SITE THEN PLEASE PROVIDE THE STATE
 APPROVED (STAMPED) PLANS TWO SETS.
 RULE 9B-1 FLORIDA ADMINISTRATIVE CODE.
  
 1B) THE PLANS DO NOT INDICATE HOW THE FOUNDATION AND
 MANUFACTURED BLUIDING ARE GOING TO MEET THE
 REQUIREMENTS OF :
 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED
 IN THIS CHAPTER. SEE SECTION 1609 FOR WIND AND SECTION
 1610 FOR LATERAL SOIL LOADS.
  
 1C) THE PLANS ALSO INDICATE THE INSTALATION OF A
 PRE-ENGINEERED ALUMINUM CANOPY. PLEASE PROVIDE PRODUCT
 APPROVAL FOR CANOPY. RULE 9B-72 (31) SUB-CATEGORY (D)
 ROOFING.
  
 1D) 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-30 Cont ID  
Sent By dpalmer Date 2009-12-30 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2009-12-30 Time 14:04 Sent To  
Notes
2009-12-30 14:05:16PLANS STAMPED OK.
 REVIEW TO REMAIN IN FAILED STATUS UNTIL CONTRACTOR CAN
 BE VERIFIED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 10:34 Sent To  
Notes
2009-10-10 11:15:24 
 ** DENIED **
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW
 AND NOT FOR PERMIT UNDER A LICENSED CONTRACTOR. PLANS
 SUBMITTED FOR PERMIT AFTER OCTOBER 1ST, 2009 SHALL BE
 UNDER THE FOLLOWING CODES.
 2008 NFPA-70
 2006 NFPA-101
 2007 FBC W/ SECOND SUPPLEMENTS TO THE 2009 SUPPLEMENTS
  
 2) NOTE: PLEASE SHOW CLASS/DIVISION LOCATIONS PER NEC
 500
  
 3) NOTE: THERE IS A NEW MANUFACTURED CONCRETE BUILDING
 YET NO ELECTRICAL SHOWN FOR THIS BUILDING. PLANS SEEMS
 TO INDICATE EQUIPMENT IN THIS LOCATION.
 PLEASE ALSO SEE 250.50 GROUNDING ELECTRODE SYSTEM
 REQUIRED FOR STRUCTURES CONTAINING ELECTRICAL.
 PLEASE SEE 230.70 230.79 AND 225.31-225.39 FOR FEEDERS
 OR BRANCH CIRCUITS FOR DISCONNECTING MEANS AS WELL AS
 ANY SERVICES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2010-01-05 Cont ID  
Sent By mgonzale Date 2010-01-05 Time 14:25 Rev Time 0.50
Received By mgonzale Date 2010-01-05 Time 14:24 Sent To  
Notes
2010-01-05 14:26:36PLEASE REFER TO PREVIOUS COMMENTS MADE BY DEAN L.
 ANY QUESTIONS OR TO DISCUSS ENGINEERING COMMENTS FEEL
 FREE TO
 CONTACT ME:
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-10-05 Cont ID  
Sent By dlauderm Date 2009-10-05 Time 07:41 Rev Time 3.00
Received By dlauderm Date 2009-10-03 Time 10:49 Sent To  
Notes
2009-10-05 07:40:54PASSED WITH PROVIOS:
 DEAN LAUDERMILK, PROJECT COORDINATOR,
 OFFICE 494-1083, EMAIL [email protected]
 SHEET CU-01-03:
 1. LOCATION - THROUGH-OUT SHEET: CTN???S (2 AND 3???
 PVC) SHOWN ARE NOT DEFINED ON SHEET G-00-02. WHAT ARE
 THEY? SAME COMMENT HOLDS TRUE ON SHEET CU-01-03.
 2. LOCATION - C-4: WHERE IS THE WATER METER AT THE
 BACKFLOW PREVENTER? ALL PRODUCTION WATER IS SUPPOSED TO
 BE MONITORED. THE METER DOES NOT SHOW UP ON SHEET
 CD-01-02, DETAIL 7 EITHER.
 3. C-4: WHY DOES THE DEDICATED EYE WASH WATER LINE
 DISAPPEAR INTO THE METER PUMP BUILDING? IT SHOULD HAVE
 A TEE IN THE LINE INTO THE BUILDING FOR THE EYE WASH
 STATION INSIDE.
 SHEET D-02-02:
 1. LOCATION ??? A2: THE CHLORINE UNLOADING STATION IS
 20??? EAST OF THE GARAGE DOORS INTO THE EXISTING
 CHLORINE BUILDING. WHY WAS THIS LOCATION CHOSEN? THE
 PAVEMENT ALSO ENDS AT THE GARAGE DOORS. WHY NOT PLACE
 THE CHLORINE FILL STATION AT THE GARAGE DOORS SO THERE
 IS NOT TOO MUCH HOSE REELED OUT. AN EVEN BETTER
 LOCATION WOULD BE INSIDE THE BUILDING AND HAVE THE FILL
 STATION INSIDE THE CONTAINMENT STRUCTURE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-01-14 Cont ID  
Sent By mawillia Date 2010-01-14 Time 11:15 Rev Time 0.00
Received By mawillia Date 2010-01-14 Time 11:00 Sent To  
Notes
2010-01-14 11:13:42*****PARTIAL APPROVAL*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED AND/OR ACKNOWLEDGED. THE APPROPIATE PLAN
 SHEET(S) TO BE FIRE-STAMPED AS APPROVED UPON THE
 FOLLOWING.
  
 1. A LICENSED CONTRACTOR HAS BEEN SIGNED FOR THE SCOPE
 OF WORK.
  
 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-30 Cont ID  
Sent By mcarsill Date 2009-09-30 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2009-09-30 Time 15:39 Sent To  
Notes
2009-09-30 15:46:011009 BANYAN BOULEVARD
  
 1. ENSURE THAT FIRE AND PARAMEDICAL ACCESS IS
 MAINTAINED DURING WORK ACTIVITIES.
  
 2. ANY CUTTING OR WELDING OPERATIONS SHALL COMPLY WITH
 NFPA 51B.
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. ALL STORAGE TANKS ARE TO BE PROPERLY LABELED.
 CONTROL VALVES ARE TO BE LABELED TO ENSURE RAPID
 CLOSURE IN THE EVENT OF AN EMERGENCY.
  
 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM EQUIPMENT.
  
 7. DUCT SMOKE DETECTOR SHOWN ON PAGE M-02-02 WILL BE
 CONNECTED TO WHAT FIRE ALARM EQUIPMENT. NEW OR
 EXISTING.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2009-09-14 09:49:42OK PER F MITTNER 9-14-09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-22 Cont ID  
Sent By lmartine Date 2009-12-22 Time 19:13 Rev Time 0.00
Received By lmartine Date 2009-12-22 Time 19:13 Sent To  
Notes
2009-12-22 19:13:41C--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-10 Time   Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 17:18 Sent To  
Notes
2009-09-15 17:25:11SENT TO C-28.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-01-14 Cont ID  
Sent By rregueir Date 2010-01-14 Time 09:00 Rev Time 0.00
Received By rregueir Date 2010-01-13 Time 16:48 Sent To  
Notes
2010-01-13 17:10:04REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED
  
 1. OK
  
 2. DESIGNER'S RESPONSE INDICATES EXTERIOR DUCTWORK IS
 TO BE CONSTRUCTED OF FIBER REINFORCED PLASTIC. EXTERIOR
 DUCTWORK SHALL BE DESIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 DUCT MANUFACTURER'S DATA DEMONSTRATING THE WIND
 RESISTANCE CAPABILITIES OF THE PROPOSED EXTERIOR
 DUCTWORK.
  
 3. NO INFORMATION WAS PROVIDED REGARDING THE WIND
 RESISTANCE CAPABILITIES OF THE OUTDOOR PACKAGE UNIT.
 SCREEN WALLS DO NOT ELIMINATE THE FACT THAT THE UNIT IS
 EXPOSED TO WIND AND SUBJECT TO WIND PRESSURES IN A HIGH
 WIND EVENT. THE EXHAUST FAN MUST ALSO BE DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
 PROVIDE SUPPORTING DOCUMENTATION WHICH DEMONSTRATES
 COMPLIANCE.
  
 4. OK
  
 NOTE: PAGE G-00-05 DECLARES THIS AS A CATEGORY IV
 STRUCTURE, WITH EXPOSURE CATEGORY OF C AND A WIND
 IMPORTANCE FACTOR OF 1.15. WHEN PROVIDING WIND
 RESISTANCE DATA FOR THE MECHANICAL EQUIPMENT AND
 APPLIANCES ABOVE, THESE FACTORS SHALL BE TAKEN INTO
 ACCOUNT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-09-29 Cont ID  
Sent By rregueir Date 2009-09-29 Time 15:08 Rev Time 0.00
Received By rregueir Date 2009-09-29 Time 14:40 Sent To  
Notes
2009-09-29 15:06:37REVIEW #: 1ST **PLAN REVIEW ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-02-02: FLOOR PLAN SHOWS LESS THAN 3 FEET
 BETWEEN ACU 201 AND THE NORTH WALL OF THE ENCLOSURE.
 MANUFACTURER'S DATA REQUIRES A MINIMUM OF 60 INCHES
 CLEARANCE AT THIS LOCATION. PLEASE SHOW HOW PROPER
 ACCESS FOR SERVICE AND MAINTENANCE OF THE APPLIANCE.
 CLEARANCES AROUND APPLIANCES TO ELEMENTS OF PERMANENT
 CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT AND
 APPLIANCES, SHALL BE SUFFICIENT TO ALLOW INSPECTION,
 SERVICE, REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH
 ELEMENTS OF PERMANENT CONSTRUCTION IN ACCORDANCE WITH
 FBC-M 306.1 AND IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS PER FBC-M 304.1.
  
 2. PAGE M-02-02: FLOOR PLAN REFERENCES STRUCTURAL DETAL
 FOR WALL AND ROOF SUPPORT OF EXTERIOR DUCTS. NO SUCH
 DETAIL WAS PROVIDED IN THESE PLANS. PROVIDE STRUCTURAL
 DETAIL DESIGNED FOR WIND RESISTANT DESIGN AND
 INSTALLATION OF EXTERIOR DUCTWORK IN ACCORDANCE WITH
 FBC-M 301.12.
  
 3. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL
 OUTDOOR APPLIANCES EXPOSED TO WIND, SUCH AS ACU-201 AND
 EF-201 AS WELL AS DETAILS FOR INSTALLATION AND
 ATTACHMENT TO STRUCTURE FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 4. EF-201 APPEARS TO BE ON A ROOF AT A HEIGHT EXCEEDING
 16 FEET ABOVE GRADE. WHERE APPLIANCES REQUIRING ACCESS
 ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A
 HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED
 BY A PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF
 WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO THE
 EQUIPMENT AND APPLIANCES' LEVEL SERVICE SPACE IN
 ACCORDANCE WITH FBC-M 306.5. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-01-05 Cont ID  
Sent By kstevens Date 2010-01-05 Time 14:26 Rev Time 0.00
Received By kstevens Date 2010-01-05 Time 14:25 Sent To  
Notes
2010-01-05 14:27:16NOTE:
 PLANS SHALL BE STAMPED BUT WILL REMAIN IN FAILED STATUS
 UNTIL CONTRACTOR VERIFICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 09:02 Rev Time 0.00
Received By kstevens Date 2009-09-17 Time 16:53 Sent To  
Notes
2009-09-21 09:06:16DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
 1. SHT P-02-01 NOTE INDICATES 1" NWP-CPVC DROP TO
 CONNECT TO EXISTING 4" NPW. ABOVE THE NOTE ANOTHER NOTE
 STATES 1-1/4" P2-CPVC CENTERLINE EL. 11'0" AFF. PLEASE
 CLARIFY. SECTION 608.1. CROSS CONNECTIONS PROHIBITED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2009-10-05 Cont ID  
Sent By astelly Date 2009-09-21 Time 09:54 Rev Time 3.00
Received By astelly Date 2009-09-21 Time 09:54 Sent To  
Notes
***NONE***