| Plan Review Stops For Permit 09090230 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-12-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-28 |
Time |
13:58 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-12-28 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2009-12-28 14:03:42 | BUILDING PLAN REVIEW | | | PERMIT: 09090230 | | | ADD: 1009 BANYAN BLVD | | | CONT: TO BE DETREMINED | | | TEL: (561) 494-1106 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | PLANS APPEAR TO BE CODE COMPLIANT PLANS WILL BE STAMP | | | ONCE A LICENSED CONTRACTOR HAS SIGNED ON, LICESURE | | | CHECKED AND FEES PAID. | | | | | | BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | 1) SHEET S-03-02 METERING PUMP BUILDING: RED LINED TO | | | BE UNDER SEPERATE PERMIT, FEES AND REVIEW. | | | | | | 2) THE PLANS ALSO INDICATE THE INSTALATION OF A | | | PRE-ENGINEERED ALUMINUM CANOPY. PLANS ARE RED LINED TO | | | BE UNDER A SEPERATE PERMIT, FEES AND REVIEW. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-09-22 |
Time |
15:58 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2009-09-22 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2009-09-22 16:23:50 | BUILDING PLAN REVIEW | | | PERMIT: 09090230 | | | ADD: 1009 BANYAN BLVD | | | CONT: TO BE DETREMINED | | | TEL: (561) 494-1106 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET S-03-02 METERING PUMP BUILDING: | | | | | | 1A) THE PLANS INDICATE THIS IS TO BE A PRE-MANUFACTURED | | | BUILDING. IF THIS IS A MANUFACTURED BUILDING THAT IS | | | BROUGHT TO THE SITE THEN PLEASE PROVIDE THE STATE | | | APPROVED (STAMPED) PLANS TWO SETS. | | | RULE 9B-1 FLORIDA ADMINISTRATIVE CODE. | | | | | | 1B) THE PLANS DO NOT INDICATE HOW THE FOUNDATION AND | | | MANUFACTURED BLUIDING ARE GOING TO MEET THE | | | REQUIREMENTS OF : | | | 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED | | | IN THIS CHAPTER. SEE SECTION 1609 FOR WIND AND SECTION | | | 1610 FOR LATERAL SOIL LOADS. | | | | | | 1C) THE PLANS ALSO INDICATE THE INSTALATION OF A | | | PRE-ENGINEERED ALUMINUM CANOPY. PLEASE PROVIDE PRODUCT | | | APPROVAL FOR CANOPY. RULE 9B-72 (31) SUB-CATEGORY (D) | | | ROOFING. | | | | | | 1D) 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | | | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES | | | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER | | | NOTICE. | | | | | | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM | | | - 5:00 PM. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-12-30 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-12-30 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2009-12-30 14:05:16 | PLANS STAMPED OK. | | | REVIEW TO REMAIN IN FAILED STATUS UNTIL CONTRACTOR CAN | | | BE VERIFIED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-10 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-10 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2009-10-10 11:15:24 | | | | ** DENIED ** | | | | | | | | | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW | | | AND NOT FOR PERMIT UNDER A LICENSED CONTRACTOR. PLANS | | | SUBMITTED FOR PERMIT AFTER OCTOBER 1ST, 2009 SHALL BE | | | UNDER THE FOLLOWING CODES. | | | 2008 NFPA-70 | | | 2006 NFPA-101 | | | 2007 FBC W/ SECOND SUPPLEMENTS TO THE 2009 SUPPLEMENTS | | | | | | 2) NOTE: PLEASE SHOW CLASS/DIVISION LOCATIONS PER NEC | | | 500 | | | | | | 3) NOTE: THERE IS A NEW MANUFACTURED CONCRETE BUILDING | | | YET NO ELECTRICAL SHOWN FOR THIS BUILDING. PLANS SEEMS | | | TO INDICATE EQUIPMENT IN THIS LOCATION. | | | PLEASE ALSO SEE 250.50 GROUNDING ELECTRODE SYSTEM | | | REQUIRED FOR STRUCTURES CONTAINING ELECTRICAL. | | | PLEASE SEE 230.70 230.79 AND 225.31-225.39 FOR FEEDERS | | | OR BRANCH CIRCUITS FOR DISCONNECTING MEANS AS WELL AS | | | ANY SERVICES. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2010-01-05 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-01-05 |
Time |
14:25 |
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
2010-01-05 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2010-01-05 14:26:36 | PLEASE REFER TO PREVIOUS COMMENTS MADE BY DEAN L. | | | ANY QUESTIONS OR TO DISCUSS ENGINEERING COMMENTS FEEL | | | FREE TO | | | CONTACT ME: | | | | | | MANUEL JULIAN GONZALEZ | | | CSD ENGINEERING REVIEW | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2009-10-05 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2009-10-05 |
Time |
07:41 |
Rev Time |
3.00 |
| Received By |
dlauderm |
Date |
2009-10-03 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2009-10-05 07:40:54 | PASSED WITH PROVIOS: | | | DEAN LAUDERMILK, PROJECT COORDINATOR, | | | OFFICE 494-1083, EMAIL [email protected] | | | SHEET CU-01-03: | | | 1. LOCATION - THROUGH-OUT SHEET: CTN???S (2 AND 3??? | | | PVC) SHOWN ARE NOT DEFINED ON SHEET G-00-02. WHAT ARE | | | THEY? SAME COMMENT HOLDS TRUE ON SHEET CU-01-03. | | | 2. LOCATION - C-4: WHERE IS THE WATER METER AT THE | | | BACKFLOW PREVENTER? ALL PRODUCTION WATER IS SUPPOSED TO | | | BE MONITORED. THE METER DOES NOT SHOW UP ON SHEET | | | CD-01-02, DETAIL 7 EITHER. | | | 3. C-4: WHY DOES THE DEDICATED EYE WASH WATER LINE | | | DISAPPEAR INTO THE METER PUMP BUILDING? IT SHOULD HAVE | | | A TEE IN THE LINE INTO THE BUILDING FOR THE EYE WASH | | | STATION INSIDE. | | | SHEET D-02-02: | | | 1. LOCATION ??? A2: THE CHLORINE UNLOADING STATION IS | | | 20??? EAST OF THE GARAGE DOORS INTO THE EXISTING | | | CHLORINE BUILDING. WHY WAS THIS LOCATION CHOSEN? THE | | | PAVEMENT ALSO ENDS AT THE GARAGE DOORS. WHY NOT PLACE | | | THE CHLORINE FILL STATION AT THE GARAGE DOORS SO THERE | | | IS NOT TOO MUCH HOSE REELED OUT. AN EVEN BETTER | | | LOCATION WOULD BE INSIDE THE BUILDING AND HAVE THE FILL | | | STATION INSIDE THE CONTAINMENT STRUCTURE. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2010-01-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-01-14 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-01-14 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2010-01-14 11:13:42 | *****PARTIAL APPROVAL***** | | | | | | THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | | ADDRESSED AND/OR ACKNOWLEDGED. THE APPROPIATE PLAN | | | SHEET(S) TO BE FIRE-STAMPED AS APPROVED UPON THE | | | FOLLOWING. | | | | | | 1. A LICENSED CONTRACTOR HAS BEEN SIGNED FOR THE SCOPE | | | OF WORK. | | | | | | 2. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-09-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2009-09-30 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2009-09-30 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2009-09-30 15:46:01 | 1009 BANYAN BOULEVARD | | | | | | 1. ENSURE THAT FIRE AND PARAMEDICAL ACCESS IS | | | MAINTAINED DURING WORK ACTIVITIES. | | | | | | 2. ANY CUTTING OR WELDING OPERATIONS SHALL COMPLY WITH | | | NFPA 51B. | | | | | | 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 4. ALL STORAGE TANKS ARE TO BE PROPERLY LABELED. | | | CONTROL VALVES ARE TO BE LABELED TO ENSURE RAPID | | | CLOSURE IN THE EVENT OF AN EMERGENCY. | | | | | | 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRICAL CODE. | | | | | | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM EQUIPMENT. | | | | | | 7. DUCT SMOKE DETECTOR SHOWN ON PAGE M-02-02 WILL BE | | | CONNECTED TO WHAT FIRE ALARM EQUIPMENT. NEW OR | | | EXISTING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | WEST PALM BEACH FIRE RESCUE | | | BUREAU OF FIRE PREVENTION | | | 500 NORTH DIXIE HIGHWAY | | | WEST PALM BEACH, FLORIDA 33401 | | | (561) 804-4709 PHONE | | | (561) 804-4774 FAX | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-09-14 09:49:42 | OK PER F MITTNER 9-14-09 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-12-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-12-22 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-12-22 |
Time |
19:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-10-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-15 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2009-09-15 17:25:11 | SENT TO C-28. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2010-01-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-01-14 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-01-13 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2010-01-13 17:10:04 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED | | | | | | 1. OK | | | | | | 2. DESIGNER'S RESPONSE INDICATES EXTERIOR DUCTWORK IS | | | TO BE CONSTRUCTED OF FIBER REINFORCED PLASTIC. EXTERIOR | | | DUCTWORK SHALL BE DESIGNED AND INSTALLED FOR WIND | | | RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE | | | DUCT MANUFACTURER'S DATA DEMONSTRATING THE WIND | | | RESISTANCE CAPABILITIES OF THE PROPOSED EXTERIOR | | | DUCTWORK. | | | | | | 3. NO INFORMATION WAS PROVIDED REGARDING THE WIND | | | RESISTANCE CAPABILITIES OF THE OUTDOOR PACKAGE UNIT. | | | SCREEN WALLS DO NOT ELIMINATE THE FACT THAT THE UNIT IS | | | EXPOSED TO WIND AND SUBJECT TO WIND PRESSURES IN A HIGH | | | WIND EVENT. THE EXHAUST FAN MUST ALSO BE DESIGNED FOR | | | WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. | | | PROVIDE SUPPORTING DOCUMENTATION WHICH DEMONSTRATES | | | COMPLIANCE. | | | | | | 4. OK | | | | | | NOTE: PAGE G-00-05 DECLARES THIS AS A CATEGORY IV | | | STRUCTURE, WITH EXPOSURE CATEGORY OF C AND A WIND | | | IMPORTANCE FACTOR OF 1.15. WHEN PROVIDING WIND | | | RESISTANCE DATA FOR THE MECHANICAL EQUIPMENT AND | | | APPLIANCES ABOVE, THESE FACTORS SHALL BE TAKEN INTO | | | ACCOUNT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-09-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-09-29 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-09-29 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2009-09-29 15:06:37 | REVIEW #: 1ST **PLAN REVIEW ONLY** | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-02-02: FLOOR PLAN SHOWS LESS THAN 3 FEET | | | BETWEEN ACU 201 AND THE NORTH WALL OF THE ENCLOSURE. | | | MANUFACTURER'S DATA REQUIRES A MINIMUM OF 60 INCHES | | | CLEARANCE AT THIS LOCATION. PLEASE SHOW HOW PROPER | | | ACCESS FOR SERVICE AND MAINTENANCE OF THE APPLIANCE. | | | CLEARANCES AROUND APPLIANCES TO ELEMENTS OF PERMANENT | | | CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT AND | | | APPLIANCES, SHALL BE SUFFICIENT TO ALLOW INSPECTION, | | | SERVICE, REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH | | | ELEMENTS OF PERMANENT CONSTRUCTION IN ACCORDANCE WITH | | | FBC-M 306.1 AND IN ACCORDANCE WITH THE MANUFACTURER'S | | | INSTRUCTIONS PER FBC-M 304.1. | | | | | | 2. PAGE M-02-02: FLOOR PLAN REFERENCES STRUCTURAL DETAL | | | FOR WALL AND ROOF SUPPORT OF EXTERIOR DUCTS. NO SUCH | | | DETAIL WAS PROVIDED IN THESE PLANS. PROVIDE STRUCTURAL | | | DETAIL DESIGNED FOR WIND RESISTANT DESIGN AND | | | INSTALLATION OF EXTERIOR DUCTWORK IN ACCORDANCE WITH | | | FBC-M 301.12. | | | | | | 3. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL | | | OUTDOOR APPLIANCES EXPOSED TO WIND, SUCH AS ACU-201 AND | | | EF-201 AS WELL AS DETAILS FOR INSTALLATION AND | | | ATTACHMENT TO STRUCTURE FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBC-M 301.12. | | | | | | 4. EF-201 APPEARS TO BE ON A ROOF AT A HEIGHT EXCEEDING | | | 16 FEET ABOVE GRADE. WHERE APPLIANCES REQUIRING ACCESS | | | ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A | | | HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED | | | BY A PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF | | | WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO THE | | | EQUIPMENT AND APPLIANCES' LEVEL SERVICE SPACE IN | | | ACCORDANCE WITH FBC-M 306.5. SUCH ACCESS SHALL NOT | | | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 | | | INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER | | | THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2010-01-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2010-01-05 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2010-01-05 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2010-01-05 14:27:16 | NOTE: | | | PLANS SHALL BE STAMPED BUT WILL REMAIN IN FAILED STATUS | | | UNTIL CONTRACTOR VERIFICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-09-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-21 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-17 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2009-09-21 09:06:16 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | | | | 1. SHT P-02-01 NOTE INDICATES 1" NWP-CPVC DROP TO | | | CONNECT TO EXISTING 4" NPW. ABOVE THE NOTE ANOTHER NOTE | | | STATES 1-1/4" P2-CPVC CENTERLINE EL. 11'0" AFF. PLEASE | | | CLARIFY. SECTION 608.1. CROSS CONNECTIONS PROHIBITED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2009-10-05 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2009-09-21 |
Time |
09:54 |
Rev Time |
3.00 |
| Received By |
astelly |
Date |
2009-09-21 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|