Plan Review Details - Permit 09090199
Plan Review Stops For Permit 09090199
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-21 Cont ID  
Sent By jgomez Date 2009-09-21 Time 08:46 Rev Time 0.00
Received By jgomez Date 2009-09-21 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-14 Cont ID  
Sent By jgomez Date 2009-09-14 Time 16:26 Rev Time 0.00
Received By jgomez Date 2009-09-14 Time 16:26 Sent To  
Notes
2009-09-14 16:41:27RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RAS 117 SIGNED AND SEALED CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0224.01 SUBMITTED.
  
 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 NEED TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" AS REQUIRED BY 2009 REVISIONS
 TO FBC 2007 SEC. 1609.4.3.
  
 3- CLEARLY MARK ON NOA SUBMITTED SPECIFIC BASE SHEET
 FASTENING OPTION TO BE USED TO VERIFY COMPLIANCE WITH
 THE UPLIFT LOADS OF SEC. 1609 OF FBC 2007 WITH 2009
 REVISIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved