| Plan Review Stops For Permit 09090143 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2009-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-11 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-11 |
Time |
08:08 |
Sent To |
PC |
|
| Notes |
| 2009-09-11 08:08:45 | ** PROVISO ** | | | | | | ** PLEASE SUBMIT BEFORE FINAL ELECTRICAL INSPECTION. | | | | | | 1) NOTE: PLEASE LIST ALL MINIMUM CIRCUITS AND OTHER | | | CIRCUITS. PLEASE LIST AMPERAGE AND CONDUCTOR SIZES. | | | 210.52, 310.16, 408.4 | | | | | | 2) NOTE: ALL RECEPTACLES SERVING KITCHEN COUNTER SPACES | | | SHALL BE GFI/GFI PROTECTED. 210.8A6 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
|