Plan Review Details - Permit 09090065
Plan Review Stops For Permit 09090065
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-09-03 Cont ID  
Sent By jnguyen Date 2009-09-03 Time 10:30 Rev Time 0.00
Received By jnguyen Date 2009-09-03 Time 08:00 Sent To  
Notes
2009-09-03 10:30:03SINCE I WAS NOT PROVIDED WITH A SITE PLAN (ONLY HAD A
 COPY OF THE PERMIT), I WENT TO GO SEE DANIEL ROBERGE &
 VINCENT NOEL IN THE ENGINEERING SERVICES DEPARTMENT TO
 ASCERTAIN WHERE THESE NEW RESTROOMS WOULD BE SITUATED
 ON PCN# 74424217000007010. THE ACTUALY PERMIT
 APPLICATION ITSELF WAS REFERENCED TO A SECONDARY
 ADDRESS OF 8537 NORTHLAKE BLVD THAT WAS NOT IN OUR
 COMMUNITYPLUS & GIS DATABASES. IN COMMUNITYPLUS, THE
 PERMIT WAS ATTACHED TO THE PRIMARY ADDRESS OF 8535
 NORTHLAKE BLVD. I RESEARCHED 8537 NORTHLAKE BLVD ONLINE
 & LATER CONFIRMED IT TO BE THE CITY OF WPB PARKS &
 RECREATION - EVERGLADES PAVILLION (THE BUILDING JUST TO
 THE NORTHWEST OF 8535 NORTH LAKE BLVD - FLORIDA FISH &
 WILDLIFE COMMISSION). I ASSIGNED THE SECONDARY ADDRESS
 OF 8547 NORTHLAKE BLVD TO THE RESTROOMS (PINPOINTED TO
 ME ON THE 2009 AERIALS). IN COMMUNITYPLUS UNDER PCN#
 74424217000007010, I ADDED SEQUENTIAL UNIT RECORDS 0001
 - 8537 NORTHLAKE BLVD & 0002 - 8547 NORTHLAKE BLVD. I
 ALSO SENT OUT AN E-MAIL NOTIFICATION FOR THE NEWLY
 ISSUED SECONDARY ADDRESS OF 8547 NORTHLAKE BLVD &
 INFORMED ALL OF THE INVOLVED PARTIES OF THE EXISTENCE
 OF 8537 NORTHLAKE BLVD. IN COMMUNITYPLUS, I MOVED THIS
 PERMIT TO BE CORRECTLY REFERENCED TO 8547 NORTHLAKE
 BLVD. HOWEVER, SINCE I WAS ONLY PROVIDED WITH A COPY OF
 THE PERMIT, PLEASE MAKE THE ADJUSTMENT ON THE ORIGINAL
 PERMIT APPLICATION FROM 8537 TO 8547 NORTHLAKE BLVD.
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]
  
  
  
  
2009-09-02 15:49:34PER DANILE ROBERGE , ENGINEERING DEPT. THE ADDRESS IS
 8537 NORTHLAKE BLVD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By jwitmer Date 2010-03-18 Time 16:51 Rev Time 0.55
Received By jwitmer Date 2010-03-18 Time 16:51 Sent To  
Notes
2010-03-18 16:53:55BUILDING PLAN REVIEW
 PERMIT: 09090065
 ADD: 8537 NORTHLAKE BLVD
 CONT: "TO BE DETERMINED"
 TEL: (561)494-1088 DANIEL ROBERGE
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). MISSING PRODUCT
 APPROVALS WILL BE CONSIDERED A REVISION WITH ASSOCIATED
 FEES AND REVIEW!
  
 1) 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 WALL LOUVERS- CONCRETE-NO PRODUCT APRROVALS WERE
 SUBMITTED ONLY A CUT SHEET!
  
 2) THE RESTROOMS IS A DESIGNATED "A" FLOOD ZONE WITH AN
 UNKNOWN FLOOD LEVEL. THE ENGINEERING DEPARTMENT IS TO
 SET THE HEIGHT FOR FINISH
 FLOOR HEIGHT OF 22.25 ' AS WELL AS A FLOOD ZONE
 CERTIFICATE AT TIME OF THE FLOOR SLAB POUR. FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
  
  
  
  
  
  
  
 JIM WITMER C. B. O.
  
  
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT: WWW.SURVEYMONKEY.COM/

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-02-03 Cont ID  
Sent By jwitmer Date 2010-02-03 Time 11:16 Rev Time 2.00
Received By jwitmer Date 2010-02-03 Time 09:15 Sent To  
Notes
2010-02-03 15:52:54BUILDING PLAN REVIEW
 PERMIT: 09090065
 ADD: 8537 NORTHLAKE BLVD
 CONT: "TO BE DETERMINED"
 TEL: (561)494-1088 DANIEL ROBERGE
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 FEB. 03/ 2010
  
 1)COMPLIED.
  
 2)2ND REQUEST, PLANS ARE INDICATED TO BE DESIGNED BY
 P.E. DANIEL ROBERGE, PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 3)COMPLIED. WORK DELETED.
  
 4) 2ND REQUEST, SHEET 11 OF 17 NOTE ON PLANS INDICATE
 TTHE USE OF A TWO ROW BOND BEAM OVER THE GLASS WINDOWS,
 THIS CAN BE ACCOMPLISHED THE ELEVATIONS ON SHEET 9 &10
 INDICATE THE USE OF A BOND BEAM CONSTRUCTION, THE WAY
 THE ELEVATION APPEARS THE INTENT IS TO USE STEEL POWER
 LINTELS INSTEAD OF A PRECAST CONCRETE LINTEL, PLEASE
 PROVIDE THE MANUFACTURES SPEC FOR THE TYPE OF LINTERL
 TO BE INSTALLED. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A ) GLASS BLOCK- COMPLIED
 5B) EXTERIOR SWING DOORS- COMPLIED.
 5C) WALL LOUVERS- CONCRETE-NO PRODUCT APRROVALS WERE
 SUBMITTED ONLY A CUT SHEET!
 5D) LINTELS- NO PRODUCT APPOVALS WERE SUBMITTED
 5E) TRUSS ANCHORS- COMPLIED.
 F) ROOF ASSEMBLIES-COMPLIED.
 G) SKYLIGHTS- LARGE MISSILE TESTED GLAZED OPENING!-
 COMPLIED.
  
 6) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) NEW COMMENT, THE LOCATION OF THE RESTROOMS IS A
 DESIGNATED "A" FLOOD ZONE WITH AN UNKNOWN FLOOD LEVEL.
 THE ENGINEERING DEPARTMENT IS TO SET THE HEIGHT FOR
 FINISH
 FLOOR AS WELL AS A FLOOD ZONE CERTIFICATE AT TIME OF
 THE FLOOR SLAB POUR. FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 8) THE WIND DESIGN CRITERIA FOR THIS BUILDING HAS NEVER
 BEEN SUBMITTED, ONLY FOR THE STRUCTURES SHOWN ON SHEET
 7 OF 17 WHICH WAS CANCELLED. PLEASE NOTE THE NEW
 LOCATION OF THE RESTROOM WILL PLACE THE STRUCTURE IN
 "C" EXPOSURE WITH HIGHER PRESSURES THAN PROVIDED AS A
 "B" EXPOSURE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-03 Cont ID  
Sent By jwitmer Date 2009-09-03 Time 16:54 Rev Time 1.20
Received By jwitmer Date 2009-09-03 Time 15:30 Sent To  
Notes
2009-09-03 16:59:34BUILDING PLAN REVIEW
 PERMIT: 09090065
 ADD: 8537 NORTHLAKE BLVD
 CONT: "TO BE DETERMINED"
 TEL: (561)494-1088 DANIEL ROBERGE
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 SEPTEMBER 03/2009
  
 1) A LICENSECED CONTRACTOR IS TO BE SIGNED ON FOR THE
 SCOPE OF WORK COVERED BY THEIR LICENSE. FL S S 489.
  
 2) PLANS ARE INDICATED TO BE DESIGNED BY P.E. DANIEL
 ROBERGE, PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 3) PERMIT APPLICATION UNDER DESCRIPTION OF WORK
 INDICATES THE ONLY WORK TO BE COVERED UNDER THIS PERMIT
 IS THE NEW RESTROOMS. SHEET 6 INDICATES A THATCHED
 CHICKEE AND SHEET 7 INDICATES NEW KIOSK. ARE THESE
 STRUCTURES ALSO TO BE INCLUDED WITHIN THE SCOPE OF THIS
 PERMIT? ADDITIONAL INFORMATION REQUIRED 106.1.2.
 PLEASE NOTE THE ONLY EXEMPTION TO THE CHICKEE NOT
 REQUIRING PERMITTING IS UNDER 102.2(H) CHICKEES
 CONSTRUCTED BY THE MICCOSUKEE TRIBE OF INDIANS OF
 FLORIDA OR THE SEMINOLE TRIBE OF FLORIDA.
  
 4) THE ELEVATIONS ON SHEET 9 &10 INDICATE THE USE OF A
 BOND BEAM CONSTRUCTION, THE WAY THE ELEVATION APPEARS
 THE INTENT IS TO USE STEEL POWER LINTELS INSTEAD OF A
 PRECAST CONCRETE LINTEL, PLEASE PROVIDE THE
 MANUFACTURES SPEC FOR STEEL LINTEL. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A ) GLASS BLOCK
 5B) EXTERIOR SWING DOORS
 5C) WALL LOUVERS- CONCRETE
 5D) LINTELS
 5E) TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 G) SKYLIGHTS- LARGE MISSILE TESTED GLAZED OPENING!
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By dpalmer Date 2010-02-02 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2010-02-01 Time 17:00 Sent To  
Notes
2010-02-02 09:59:05** PROVISO*
  
 ** THE FOLLOWING IS TO BE REVISED AND SUBMITTED FOR
 REVIEW AND STAMPING BEFORE ANY INSPECTION IS SCHEDULED.
 IF PLANS GO BACK FOR OTHER CORRECTIONS THESE
 CORRECTIONS MAY BE DONE AT THAT TIME.
  
 1) NOTE: RISER AND PLANS BOTH INDICATE *EQUIPMENT
 GROUNDING CONDUCTOR* FROM FPL TO THE METER. THIS IS NOT
 PERMITTED. THIS WOULD PARALLEL THE NEUTRAL ( GROUNDED)
 CONDUCTOR THUS CREATING OBJECTIONABLE CURRENTS.
 250.24, 250.6
  
 2) NOTE: THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 IS TOO SMALL. SHOWN AS #10, HOWEVER PER 250.66 OF THE
 NEC, THE SMALLEST CONDUCTOR PERMITTED IS #8.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 08:53 Sent To  
Notes
2009-09-24 08:53:17 
 ** DENIED **
  
  
  
 1) NOTE: PLANS NEED TO BE UNDER PERMIT APPLICATION BY A
 LICENSED CONTRACTOR BEFORE A REVIEW STATUS CAN BE IN
 PASSED EVEN ONCE PLANS ARE FOUND TO BE REVIEWED FOR
 CODE COMPLIANCE.
 ** PLANS ALSO NEED TO STATE CODEC IN WHICH DESIGN IS
 UNDER. PLEASE KEEP IN MIND THAT SINCE PERMIT
 APPLICATION IS NOT MADE, ALL PERMIT APPLICATIONS AS OF
 OCT 1ST, 2009 WILL BE UNDER THE 2008 NEC.
  
 2) NOTE: PLANS DO CONTAIN A DESIGN PROFESSIONAL ON
 TITLE BLOCKS HOWEVER NO SIGNATURE DATE OR SEAL PER FS
 471.025.
 TITLE BLOCKS ALSO NEED TO BE COMPLETE WITH ALL
 INFORMATION PER FAC 61G15-23.002.
  
 3) NOTE: PLANS CONTAIN NOTES TO INSTALL NEW FEED TO
 PANELS AND METER FROM EXISTING PANEL ON WOOD BOARD
 HOWEVER WHAT KIND OF METER WILL THIS BE? IF FEED IS
 FROM ANOTHER PANEL THEN THIS IS NOT AN FPL METER.
  
 NO RISER DIAGRAM SUBMITTED FOR REVIEW. PLEASE SUBMIT A
 COMPLETE RISER MEETING NEC MINIMUM COMPLIANCE.
 PLEASE SEE 230.70, .71, 250.50, 110.9, 215.5, ETC IF
 THIS IS A NEW SERVICE FROM FPL
 PLEASE SEE
 PLEASE SEE 225.31-225.39 IF THIS IS GOING TO FED FROM
 AN EXISTING SERVICE OR EQUIPMENT.
 PLEASE SEE 250.50, 250.32 FOR DETACHED STRUCTURES.
  
 4) NOTE: PLEASE BE SURE TO SHOW ALL CIRCUITING ON PLANS
 AND COORDINATE WITH PANEL SCHEDULE TO BE SUBMITTED.
 408.4. PLEASE BE SURE ALL OVER CURRENT PROTECTION
 DEVICES ARE SHOWN WITH CORRECT WIRING SIZES.
 240.4,310.16
  
 5) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR REQUIRED
 EXTERIOR LIGHTING CONTROLS.
  
 ** PLEASE COMPLETE PLANS. AS THERE ARE SEVERAL ITEMS
 NOT YET SHOWN ON PLANS FOR MINIMUM COMPLIANCE A REVIEW
 OF THOSE ITEMS CAN NOT BE DONE. WHEN PLANS ARE
 SUBMITTED BACK THERE MAY BE NEW COMMENTS WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-02-18 Cont ID  
Sent By   Date 2010-02-18 Time   Rev Time 2.00
Received By mgonzale Date 2010-02-16 Time 14:33 Sent To  
Notes
2010-02-16 14:37:58 
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-10-19 Cont ID  
Sent By astelly Date 2009-10-01 Time 19:04 Rev Time 4.00
Received By mgonzale Date 2009-10-19 Time 13:55 Sent To  
Notes
2009-10-19 13:55:01FAILED
 PLANS REQUIRED REVISIONS
  
 THE PLANS ARE STAMPED ON THE FRONT SHEET THAT THEY NEED
 TO APPLY FOR A PLUMBING PERMIT. ALONG THOSE LINES WE
 NEED TO STATE THEY NEED TO SHOW ON THE PLAN BEFORE IT
 IS SUBMITTED TO CONSTRUCTION SERVICES THE FOLLOWING
 CHANGES;
 SHEET 12:
  BACKFLOW PREVENTER NEEDS TO BE INSTALLED AT THE METER.
  SIZE METER
  SIZE CITY WATER SERVICE
  SIZE PIPING TO THE BATHROOM (2" IS SHOWN AND MAY NOT
 BE REQUIRED FOR TWO TOILETS AND TWO SINKS)
  CHANGE PIPE MATERIAL FROM COPPER TYPE "K" TO PVC
  STATE FLOOR ELEVATION OF BATHROOM AND RIM ELEVATION OF
 THE MANHOLE AND THE TOP OF LIFT STATION.
  THIS IS TO BE SURE THAT IF THE SEWER BACKS UP, IT
 DOES NOT BACK UP INTO THE BATHROOMS.
  CLEAN OUT REQUIRED WHERE THE LATERAL LEAVES THE
 BATHROOM. DEPENDING ON THE LENGTH OF RUN
  FROM THE BATHROOM TO THE MANHOLE TO BE TIED TO THE
 LATERAL NEEDS TO HAVE CLEAN-OUTS INSTALLED
  A MINIMUM OF EVERY 100' AND AT EVERY BEND.
 MY NOTE ON THE PLANS TO INSTALL THE CONTROL PANEL FOR
 THE LIFT STATION ON THE WALL OF THE BATHROOM IS NO
 LONGER VALID.
 MY NOTE ON THE WATER SERVICE TO THE LIFT STATION IS
 INVALID.
  
 OTHER NOTES (YOURS AND MINE) THAT ARE STILL VALID:
 SHEET 3:
 SHOW LOCATION OF SHELTER/CLASS ROOM.
 REMOVE DETAIL SHOWING FORCE MAIN TIE-IN AT NORTHLAKE,
 IT IS NOT REQUIRED
 SHOW CORING INTO EXISTING MANHOLE FOR LATERAL TO NEW
 BATHROOM
 PROVIDE RIM AND INVERT OF EXISTING MANHOLE TO BE TIED
 TO
 PROVIDE ELEVATION OF PROPOSED LATERAL TO BE TIED INTO
 MANHOLE
 SHOW LOCATION OF NEW BATHROOM
 SHEET 4:
 SHOW WATER LINE FROM BATHROOM TO METER
 REMOVE NOTE: FIBERGLASS STRUCTURE TO BE REMOVED (BY
 OTHERS). THIS NOTE IS NOT REQUIRED.
 SHEET 6:
 SHELTER LOCATION IS NOT SHOWN ON PLAN (SEE SHEET 3)
 YOU SHOW THE NEW ROAD SURFACE TO BE INSTALLED FLAT. IT
 SHOULD BE SLOPED OFF TO EITHER SIDE OR TO ONE SIDE AT A
 2% SLOPE.
 WHAT IS THE FLOOR ELEVATION OF THE SHELTER?
 SHOULD THE FLOOR HAVE A 2% SLOPE FROM THE CENTER OUT SO
 THERE IS NO PONDING OF WATER DURING OR AFTER A RAIN
 STORM.
 WHAT IS THE EXISTING GRADE AROUND THE SHELTER, IT
 SHOULD BE BUILT UP AT LEAST 6" FROM THE SURROUNDING
 ELEVATIONS AND THE EXISTING ELEVATIONS SHOULD BE GRADED
 AWAY FROM THE SHELTER.
 YOU HAVE A NOTE FOR THE CONCRETE BASE FOR EMERGENCY
 PHONE, WHERE IS THE DETAIL, IT NEEDS TO BE ON THE SAME
 SHEET.
 THE DETAIL FOR THE 6" SQUARE PINE POSTS FOR THE SHELTER
 HAVE NO DEPTH ON THEM. THE CONCRETE IS TO BE 3.5' DEEP,
 BUT HOW MUCH CONCRETE IS UNDER THE POSTS?
 ARE THE 6" SQUARE PINE POSTS TO BE PRESSURE TREATED?
 SHEET 7:
 WHAT IS THE OVER HANG ON THE ROOF OF THE KIOSKS?
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-09 Cont ID  
Sent By mawillia Date 2010-02-09 Time 15:10 Rev Time 0.00
Received By mawillia Date 2010-02-09 Time 14:59 Sent To  
Notes
2010-02-09 15:10:05*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; THE APPROPIATE PLAN SHEET (13 OF 17)
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By mcarsill Date 2009-09-18 Time 16:30 Rev Time 0.00
Received By mcarsill Date 2009-09-18 Time 16:27 Sent To  
Notes
2009-09-18 16:30:45 
 1. PLANS NOT SIGNED AND SEALED.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. ALL ECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 4. PERMIT APPLICATION INDICATES NEW RESTROOMS AT THE
 NORTH CAMPUS GRASSY WATERS PRESERVE. OTHER WORK IS
 SHOWN ON THE DRAWINGS.
  
 5. NO CAMPFIRES OR EDUCATIONAL FIRES PERMITTED IN OR
 NEAR THE CLASSROOM BUILDINGS.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2010-04-08 Time 10:06 Sent To  
Notes
2010-04-08 10:06:56INCOMING SENT TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-03 Cont ID  
Sent By rmcdouga Date 2010-03-03 Time 11:04 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2010-03-03 11:07:48C-29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-02-01 Time   Rev Time 0.00
Received By rmcdouga Date 2010-01-21 Time 10:53 Sent To  
Notes
2010-01-21 10:53:55C-29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-02 Cont ID  
Sent By lmartine Date 2009-10-21 Time 10:05 Rev Time 0.00
Received By lmartine Date 2009-09-03 Time 10:45 Sent To  
Notes
2009-09-03 10:59:41SENT TO C-20.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-14 Cont ID  
Sent By rregueir Date 2009-09-14 Time 11:34 Rev Time 0.00
Received By rregueir Date 2009-09-14 Time 11:33 Sent To  
Notes
2009-09-14 11:34:44LOUVERS AND VENTS PROVIDED TO MEET NATURAL VENTILATION
 REQUIREMENTS. NO MECHANICAL PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-03-24 Cont ID  
Sent By lwagner Date 2010-03-24 Time 10:30 Rev Time 0.00
Received By lwagner Date 2010-03-24 Time 09:16 Sent To  
Notes
2010-03-24 10:40:28PLUMBING PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-01-26 Cont ID  
Sent By kstevens Date 2010-01-26 Time 14:44 Rev Time 0.00
Received By kstevens Date 2010-01-26 Time 14:44 Sent To  
Notes
2010-01-26 14:47:52DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLANS SHALL BE SIGNED, SEALED & DATED AS REQUIRED IN
 SECTION 106.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-10 Cont ID  
Sent By kstevens Date 2009-09-10 Time 10:18 Rev Time 0.00
Received By kstevens Date 2009-09-10 Time 09:23 Sent To  
Notes
2009-09-10 10:25:36DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
  
 1. PLANS SHALL BE SIGNED, SEALED & DATED AS REQUIRED IN
 SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2010-03-11 Cont ID  
Sent By astelly Date 2010-03-11 Time 15:29 Rev Time 0.00
Received By astelly Date 2010-03-11 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2010-01-30 Cont ID  
Sent By astelly Date 2010-01-30 Time 10:32 Rev Time 0.00
Received By astelly Date 2010-01-30 Time 10:30 Sent To  
Notes
2010-01-30 10:32:46AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE NOTE THE FOLLOWING FROM 94-372:
  
 SEC. 94-372. - WATER CATCHMENT AREA.
  
 (A) ANY DEVELOPMENT PROPOSED TO TAKE PLACE WITHIN THE
 WATER CATCHMENT AREA SHALL PROVIDE AN ENVIRONMENTAL
 ASSESSMENT TO THE CITY AT THE TIME OF THE INITIAL
 APPLICATION FOR NECESSARY DEVELOPMENT APPROVALS.
  
 PLEASE CONTACT ME TO DISCUSS THE PERMIT APPLICATION
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-01 Cont ID  
Sent By astelly Date 2009-10-01 Time 16:56 Rev Time 0.00
Received By astelly Date 2009-10-01 Time 18:39 Sent To ENG
Notes
2009-10-01 19:01:32AMY F. STELLY
 PLANNING AND ZONING
 561.822-1442
  
 1. PLEASE PROVIDE A SITE PLAN WHICH ACCURATELY SHOWS
 THE LOCATION OF ALL PROPOSED IMPROVEMENTS.
 2. THE SITE PLAN MUST ALSO SHOW ALL WATER BODIES WITHIN
 THE VACINITY OF THE PROPOSED STRUCTURES.
 3. IN ACCORDANCE WITH SEC. 94-205 0F THE ZONING AND
 LAND DEVELOPMENT REGULATIONS:
 A. ALL STRUCTURES MUST BE SETBACK A MINIMUM OF 30' FROM
 THE SHORELINE OF ANY WATER BODY.
 B. ALL SETBACKS MUST BE PROPERLY DIMENSIONED.
 C. THERE IS A MINIMUM OF A 24-FOOT BUILDING SEPARATION
 BETWEEN ALL STRUCTURES. PLEASE PROPERLY DIMENSION ALL
 BUILDING SEPARATIONS FOR ALL PROPOSED STRUCTURES.
 4. IN ACCORDANCE WITH SEC. 94-372:
 A. AN ENVIRONMENTAL ASSESSMENT MUST BE PROVIDED WITH
 THE PERMIT APPLICATION.
  
  