Plan Review Details - Permit 09090030
Plan Review Stops For Permit 09090030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-05 Cont ID  
Sent By jwitmer Date 2010-04-05 Time 11:53 Rev Time 0.77
Received By jwitmer Date 2010-04-05 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By jwitmer Date 2009-09-22 Time 13:13 Rev Time 0.77
Received By jwitmer Date 2009-09-22 Time 10:30 Sent To  
Notes
2009-09-22 13:25:07BUILDING PLAN REVIEW
 PERMIT: 09090030
 ADD: 1200 S FLAGLER DR/ ROOFTOP
 CONT: J. CROMPTON ELECTRIC, INC
 TEL: (321)288-7093
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) S-2 DETAIL# 2 INDICATES THE RISE ON THE STAIRS AS 10
 INCHES, PLEASE REVIEW SECTION 1009.3 EXCEPTION# 6.
  
 2) S-3 DETAIL# 2 INDICATES A CROSS OVER BRIDGE
 ELEVATION, 106.1.2 ADDITIONAL INFORMATION REQUIRED,
 THERE IS NO INFORMATION AS TO MATERIALS AND DIMENSIONS.
  
 3) S-3 DETAIL# 2 ALSO DOES NOT INDICATE HOW THE CROSS
 OVER BRIDGE IS GOING TO BE FASTENED TO THE PRECAST
 FIBERCRETE PAD NOR HOW THE BRIDGE IS GOING TO RESIST
 THE MOMENT OF OVERTURNING.
 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED
 IN THIS CHAPTER. SEE SECTION 1609 FOR WIND .
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-09 Cont ID  
Sent By btrobaug Date 2010-04-09 Time 11:26 Rev Time 0.00
Received By btrobaug Date 2010-04-09 Time 11:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 08:22 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 08:22 Sent To  
Notes
2009-09-24 08:23:02** DENIED **
  
  
  
 1) NOTE: PLEASE SEE 445.18 AND PROVIDE METHOD TO
 COMPLY. PLEASE KEEP IN MIND A SHUNT TRIP TYPE BREAKER
 IS NOT ACCEPTABLE. IN AN EMERGENCY SITUATION AND POWER
 IN THE BUILDING NEEDS TO BE SHUT DOWN, THERE IS NOT WAY
 FOR FIRE DEPARTMENT OR OTHER PERSONAL TO SHUT DOWN
 GENERATOR UNLESS GOING TO THE ROOF TO DO SO.
 A READILY ACCESSIBLE MEANS OF SHUTTING DOWN PRIME MOVER
 SUPPLY MUST BE INSTALLED IN CLOSE PROXIMITY TO THE MAIN
 ELECTRICAL ROOM/FIRE COMMAND ROOM WHEN LOCATED ON SITE.
 A GENERATOR STATUS PANEL MUST ALSO INDICATE THE UNIT
 STATUS.
 PLEASE ALSO PLACE NOTES ON PLANS FOR REQUIRED SIGNAGE
 AT ALL OF THE ABOVE LOCATIONS.
  
 2) NOTE: THE PROPOSED VALUE IS LOW. THE VALUE IS
 REQUIRED TO INCLUDE THE FOLLOWING EVEN IF ANY OF THESE
 ARE OWNER SUPPLIED.
 DESIGN/PLANS FEE.
 ALL LABOR,
 ALL EQUIPMENT, ( GENERATOR AND ATS)
 ALL MATERIALS ETC
  
 FBC 108.3
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By mawillia Date 2010-04-06 Time 11:15 Rev Time 0.00
Received By mawillia Date 2010-04-06 Time 10:53 Sent To  
Notes
2010-04-06 11:14:52*****APPROVED****
  
 REVIEWED/APPROVED BY MIKE CARSILLO ON 03/29/2010, PLAN
 SHEETS C3, C4, C6, E4, AND E5 WERE STAMPED, INITIALED,
 AND DATED BY THIS WRITER.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By mcarsill Date 2009-09-18 Time 16:38 Rev Time 0.00
Received By mcarsill Date 2009-09-18 Time 16:31 Sent To  
Notes
2009-09-18 16:37:44 
 1. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS.
  
 2. GAS PIPING AND APPURTENANT EQUIPMENT SHALL COMPLY
 WITH THE APPROPRIATE NFPA STANDARDS. INSTALLATION SHALL
 BE PERFORMED TO RECOGNIZED STANDARDS AND IN A SAFE
 MANNER.
  
 3. THE INSTALLATION OF ANY EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXITING, EXIT ACCESS OR ACCESS TO
 ANY FIRE SAFETY EQUIPMENT. THIS EQUIPMENT WOULD INCLUDE
 ANY ROOF MANIFOLDS FOR THE STANDPIPE SYSTEM.
  
 4. NO DETAILS ON FIRESTOPPING METHODS, MATERIALS, OR
 MANNER PLANNED TO BE USED WHEN PENETRATING RATED FLOORS
 OR WALLS.
  
 5. NO EQUIPMENT SHALL BE ROUTED THROUGH ANY STAIRWELLS.
  
 6. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR THE
 PLATFORM STAIRS. WHAT MEASURES WILL BE USED TO PROVIDE
 SLIP PREVENTION.
  
 7. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-04-05 Cont ID  
Sent By lwagner Date 2010-04-05 Time 13:14 Rev Time 0.00
Received By lwagner Date 2010-04-05 Time 13:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-10-05 Cont ID  
Sent By kstevens Date 2009-09-14 Time 11:39 Rev Time 0.00
Received By kstevens Date 2009-09-14 Time 11:39 Sent To  
Notes
2009-10-05 11:40:43 
  
 PASSED/PROVISO:
  
 REGULATOR SHALL BE LISTED AND HAVE THE REQUIRED OUTLET
 CAPACITY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-24 Cont ID  
Sent By lmartine Date 2010-03-22 Time 15:56 Rev Time 0.00
Received By lmartine Date 2010-03-22 Time 15:56 Sent To  
Notes
2010-03-24 15:57:05C--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-24 Time   Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 11:26 Sent To  
Notes
2009-09-02 13:24:28SENT TO C-21.

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-10-05 Cont ID  
Sent By kstevens Date 2009-09-14 Time 10:04 Rev Time 0.00
Received By kstevens Date 2009-09-14 Time 10:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-08 Cont ID  
Sent By astelly Date 2010-04-08 Time 09:57 Rev Time 0.00
Received By astelly Date 2010-04-08 Time 14:13 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-30 Cont ID  
Sent By astelly Date 2009-09-30 Time 11:08 Rev Time 0.00
Received By astelly Date 2009-09-30 Time 11:08 Sent To G
Notes
2009-10-01 16:51:58AMY STELLY
 PLANNING AND ZONING
 561.822 - 1442
  
 THE STORAGE RACK (STEEL PLATFORM) WHICH SUPPORTS THE
 GENERATOR MUST BE SCREENED IN ACCORDANCE WITH SEC.
 94-444 OF THE ZONING CODE. THE SCREENING MUST BE
 COMPATIBLE WITH THE ARCHITECTURAL CHARACTER OF THE
 BUILDING.