Plan Review Details - Permit 09080800
| Plan Review Stops For Permit 09080800 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2009-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-08 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-08 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2009-09-08 13:54:30 | A LISTED SHUT OFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | | OF EACH REGULATOR. SECTION 409.4. -- A UNION IS | | | REQUIRED DOWNSTREAM OF THE SHUT OFF VALVE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-08-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-31 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-31 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2009-08-31 15:03:08 | DENIED | | | REFERENCE: | | | FBC-2007 RESIDENTIAL | | | FBC-2007 FUEL GAS | | | | | | 1. PIPE SIZE FROM THE METER TO BE 2 INCH SCHED 40 GALV. | | | PIPE. PLEASE INDICATE PIPE SIZE & MATERIAL. TABLE | | | 402.4(2) | | | | | | 2. PIPE SIZE TO INSIDE THE HOUSE TO BE A MINIMUM 1 | | | INCH. TABLE 402.4(2). | | | | | | 3. OTHER PIPE SIZES WILL HAVE TO BE CHANGED INSIDE THE | | | HOUSE AS THERE HAS BEEN ABOUT 50 MORE FEET ADDED TO THE | | | SYSTEM. SECTION 402. | | | | | | 4. THE PIPE SIZE FOR THE P.E. PIPE TO THE POOL HEATER | | | WILL NEED TO BE INCREASED TO 1-1/2" FROM 1-1/4". TABLE | | | 401.4(19). | | | | | | 5. INDICATE THE PIPE SIZE FROM THE METER TO THE FIRST | | | TEE AND SHOW PIPE SIZE FROM THE FIRST TEE TO THE SECOND | | | TEE. SECTION 402. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
|