| 2009-09-14 11:22:02 | ****CORRECTIONS**** |
| | ****MASTER/PROJECT ONLY (INSPECTION HOLD PLACED ON THIS |
| | PERMIT)**** |
| | ****APPLICATION BY CONTRACTOR REQUIRED PRIOR TO PERMIT |
| | ISSUANCE**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. ONE OF THE SETS IS NOT SIGNED AND SEALED BY THE |
| | ARCHITECT, FS481. |
| | |
| | 2. THE PLANS SHOW WINDOWS A AND B AT BEDROOMS AS |
| | "EGRESS" AND SHEET A2.1 INCLUDES A NOTE STATING THAT |
| | THE BEDROOM WINDOWS WILL COMPLY WITH FBC1026. THE |
| | WINDOWS ARE 4'3", 4'5", AND 3' IN HEIGHT; IT APPEARS |
| | THAT NONE COMPLY WITH THE HEIGHT REQUIREMENT OF 24". |
| | SEE FBC EXISTING BUILDING 604.1 TO SEE EXCEPTION. THE |
| | WINDOWS PROPOSED MAY MEET THE EXCEPTION, BUT IN THAT |
| | CASE PLEASE REMOVE OR REVISE THE NOTES REGARDING EGRESS |
| | AND MAKE NOTE ON THE PLAN OF THE WINDOW TYPE OF THE |
| | EXISTING WINDOWS. |
| | |
| | 3. DETAILS 2 AND 3, SHEET A3.1, BOND BREAK REQUIRED FBC |
| | R 703.6.3; PLEASE REVISE AND CHECK ALL. |
| | |
| | 4. DETAILS 2 AND 3, SHEET A3.1, A MINIMUM OF 1 3/4" |
| | PENETRATION REQUIRED INTO STRUCTURAL MEMBER (ASTM |
| | C1063); A 1 1/4" NAIL IS SPECIFIED, FBC R 703.6.2; |
| | PLEASE REVISE AND CHECK ALL. |
| | |
| | 5. CASEMENT WINDOW PRODUCT APPROVALS WERE SUBMITTED, |
| | BUT ARE NOT SHOWN AS AN OPTION ON THE PLAN. ONLY SINGLE |
| | HUNG WINDOWS WERE SPECIFIED. |
| | |
| | 6. BINDER TAB #4, AWP SERIES 1700, THE NOA IS EXPIRED. |
| | |
| | 7. BINDER TABS #5 AND #8, EFCO WINDOWS, AND #9 PGT |
| | MULLION; THE FLORIDA STATE PRODUCT APPROVALS ARE |
| | EXPIRED (2004 CODE RATHER THAN 2007), BUT THE NOAS ARE |
| | CURRENT. THE FLORIDA STATE PRODUCT APPROVAL COVER |
| | SHEETS WILL BE REMOVED; NO ACTION REQUIRED |
| | (INFORMATIONAL ONLY). |
| | |
| | 8. BINDER TAB #10, FLEMING DOOR, PRODUCT APPROVAL IS |
| | EXPIRED (2004 CODE RATHER THAN 2007). PROVIDE CURRENT |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL FAC9B72. |
| | |
| | 9. BINDER TAB #11, WOOD CONNECTORS, PRODUCT APPROVAL IS |
| | EXPIRED (2004 CODE RATHER THAN 2007). ALSO NOTE THAT |
| | ONLY THE PRODUCT APPROVAL FOR L70 WAS PROVIDED. PLEASE |
| | PROVIDE EITHER SPEC SHEETS (WITH INSTALLATION |
| | INSTRUCTIONS) AND PRODUCT APPROVAL NUMBERS FOR ALL OF |
| | THE CONNECTORS OR INCORPORATE THE INFORMATION INTO THE |
| | PLAN. |
| | |
| | 10. PLEASE NOTE THAT ONE PERMIT IS REQUIRED FOR EACH |
| | PARCEL ID. IF MORE THAN ONE STRUCTURE IS INCLUDED ON A |
| | PARCEL, THE CONTRACTOR MAY REQUEST A SEPARATE PERMIT |
| | FOR EACH STRUCTURE, BUT THIS IS NOT REQUIRED. THE |
| | CONTRACTOR MAY WISH TO FACILITATE TRACKING OF |
| | INSPECTIONS. |
| | |
| | 11. SPEC SHEETS AND FLORIDA STATE PRODUCT APPROVAL |
| | COVER SHEETS (EXPIRED) FOR AWP WINDOWS WERE INCLUDED IN |
| | THE INSIDE POCKET OF THE BINDERS. THESE DOCUMENTS WILL |
| | BE DISCARDED; NO ACTION REQUIRED (INFORMATIONAL ONLY). |
| | |