Plan Review Details - Permit 09080705
Plan Review Stops For Permit 09080705
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-23 Cont ID  
Sent By rmcdouga Date 2009-09-23 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2009-09-22 Time 06:56 Sent To  
Notes
2009-09-23 13:18:24BUILDING REVISIONS REQUIRED
  
 1) THE FLAT ROOF UPLIFT PRESSURES AND RAS 117
 CALCULATIONS ON SHEET A2.3 ARE REQUIRED TO BE REVISED
 TO EXPOSURE C.
  
 2) THE DESIGN PRESSURES LISTED IN THE PRODUCT APPROVAL
 FOR THE THERMA-TRU SINGLE OUTSWING GLAZED DOOR OF + / -
 47 ARE LOWER THAN THE REQUIRED COMPONENT AND CLADDING
 NEGATIVE PRESSURE OF -49.5 SPECIFIED ON THE PLANS.
 PROVIDE PRODUCT APPROVALS FOR DOOR WITH ADEQUATE DESIGN
 PRESSURES.
  
 3) THE DOUBLE OUTSWING OPAQUE OUTSWING DOOR THAT WAS
 CLOUDED ON THE PRODUCT APPROVAL WITH DESIGN PRESSURES
 OF + /- 40 IS TOO LOW. HOWEVER, THE ONE WITH THE
 COASTAL ALUMNIUM ASTRAGAL HAS DESIGN PRESSURES OF +/-
 55 AND DO MEET THE REQUIRED OPENING PRESSURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-02 Cont ID  
Sent By rmcdouga Date 2009-09-02 Time 06:36 Rev Time 0.00
Received By rmcdouga Date 2009-09-02 Time 06:35 Sent To  
Notes
2009-09-02 07:28:412007 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) THE STRUCTURE IS LOCATED WITHIN 500 FEET OF THE
 INTRACOASTAL WATERWAY. THEREFORE, BASED ON THE 2009
 REVISIONS TO THE 2007 FBC SECTIONS R301.2.1.4.2 AND
 R301.2.1.4.3 THE EXPOSURE CATEGORY WOULD BE " C" NOT
 "B". PLEASE REVISE PLANS AND COMPONENT AND CLADDING
 PRESSURES ACCORDINGLY.
  
 3) SUBMIT TWO COPIES OF THE MANUFACTURERS
 SPECIFICATIONS AND EVALUATION REPORTS FOR THE ICYNENE
 SPRAY FOAM INSULATION.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 8" CAST-CRETE LINTELS AS REQUIRED BY DCA RULE 9B-72.
  
 5) ON SHEET A6.1 THE WINDOW SCHEDULE INCORRECTLY
 SPECIFIES 2 X 4 X 1/8 FOR SEVERAL OF THE 1 X MULLIONS
 FOR NOA NO. 06-0125.06. THIS NOA IS FOR 1" MULLIONS.
 PLEASE CORRECT.
  
 6) PRODUCT APPROVALS WERE SUBMITTED FOR 2 X MULLIONS
 WITH NOA NO. 06-0125.08, BUT WERE NOT SPECIFIED ON THE
 SCHEDULE. PLEASE CLARIFY.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOW AND THE MULLION #113 IN THE SCHEDULE
 AND WITH PRODUCT APPROVAL FL9064 AND FL 9187.
  
 8) THE PRODUCT APPROVAL SUBMITTALS FOR THE THERMA-TRU
 OPAQUE DOUBLE DOORS WITH FL5262.5 IS MISSING THE
 INSTALLATION DRAWINGS ( DRAWING NO. FL-5262.5-68). ALSO
 THE PRODUCT NAMI PRODUCT CERTIFICATION SUBMITTED FOR
 THIS PRODUCT INDICATES THAT IT IS NOT MISSILE IMPACT
 RATED. PLEASE CLARIFY.
  
 9) A PRODUCT EVALUATION REPORT WAS SUBMITTED FOR AN
 IMPACT GLAZED DOOR FL-10975.1, HOWEVER THE COVER SHEET
 AND INSTALLATION DRAWINGS WERE NOT SUBMITTED. ALSO,
 THIS PRODUCT APPROVAL WAS NOT SPECIFIED IN THE DOOR
 SCHEDULE ON A6.2. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-09-01 Cont ID  
Sent By btrobaug Date 2009-09-01 Time 13:16 Rev Time 0.00
Received By btrobaug Date 2009-09-01 Time 07:29 Sent To  
Notes
2009-09-01 13:27:21PROVISO
  
 DINING ROOM RECEPTACLE SPACING PER 210.52.SHEET E1.1.
  
 SHEET E2.1
  
 NO 80 AMP AS PER NOTE #13 ON RISER AND NO SCHEDULE FOR
 SAME.
  
 ALL BATH RECEPTACLE CIRCUITS PER 210.11(C)(3).
  
 DINING ROOM CIRCUITS PER 210.52(B)(1)-20 AMP SMALL
 APPLIANCE.
  
 AC-AHU #2 SHOWN LOCATED IN PANEL "A" AND "DP"
  
 AHU 1 & 2 DO NOT CORRELATE WITH THE RATINGS GIVEN ON
 SHEET M1.1

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-08-26 Cont ID  
Sent By mmiller Date 2009-08-26 Time 16:08 Rev Time 0.00
Received By mmiller Date 2009-08-26 Time 16:08 Sent To  
Notes
2009-08-26 16:08:41OK PER JILLAN PAPA & NO FEE PER JILLIAN PAPA MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-21 Cont ID  
Sent By lmartine Date 2009-09-21 Time 15:13 Rev Time 0.00
Received By lmartine Date 2009-09-21 Time 15:13 Sent To  
Notes
2009-09-21 15:13:56*****************EXPEDITED********************
 GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-10 Cont ID  
Sent By lmartine Date 2009-09-10 Time 11:23 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 17:16 Sent To  
Notes
2009-08-26 17:16:30R-2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-09-23 Cont ID  
Sent By rmcdouga Date 2009-09-23 Time 14:44 Rev Time 0.00
Received By rmcdouga Date 2009-09-23 Time 14:44 Sent To  
Notes
2009-09-23 14:47:32PLANS STAMPED / CALLED COUNTY TO VERIFY THAT IMPACT
 FEES WERE PAID

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-08-27 Cont ID  
Sent By rkussner Date 2009-08-27 Time 11:03 Rev Time 0.00
Received By rkussner Date 2009-08-27 Time 11:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-02 Cont ID  
Sent By rregueir Date 2009-09-02 Time 09:19 Rev Time 0.00
Received By rregueir Date 2009-09-02 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-08-29 Cont ID  
Sent By kstevens Date 2009-08-29 Time 17:48 Rev Time 0.00
Received By kstevens Date 2009-08-29 Time 17:48 Sent To  
Notes
2009-08-29 17:49:23SEPARATE GAS PERMIT/PLANS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-09-10 Cont ID  
Sent By ajones Date 2009-09-10 Time 08:49 Rev Time 0.00
Received By ajones Date 2009-09-10 Time 08:49 Sent To  
Notes
***NONE***