Plan Review Details - Permit 09080618
Plan Review Stops For Permit 09080618
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-14 Cont ID  
Sent By shill Date 2009-09-14 Time 13:38 Rev Time 0.00
Received By shill Date 2009-09-14 Time 13:38 Sent To  
Notes
2009-09-14 13:45:07PROVISO
 REVISION REQUIRED
  
 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 ***IT IS ADVISED THAT CONTRACTOR ADDRESS THESE COMMENTS
 WHEN RESUBMITTING; OTHERWISE, A REVISION WILL BE
 REQUIRED BEFORE FIRST INSPECTION***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2009-08-25 Time 16:08 Sent To  
Notes
2009-08-25 16:08:58IN ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-10 Cont ID  
Sent By aaponte Date 2009-09-10 Time 13:36 Rev Time 0.00
Received By ajones Date 2009-09-10 Time 13:35 Sent To B
Notes
2009-09-10 13:45:41PLEASE PROVIDE A FLOOR PLAN AND A FACADE INDICATING THE
 LOCATION OF PROPOSED AWNINGS.
 A SEPARATE SIGN PERMIT IS REQUIRED. PLEASE PROVIDE
 DIMENSIONS AND TEXT PROPOSED FOR SIGN. PLEASE INCLUDE
 INFORMATION ON FRONTAGE WIDTH FOR THE PURPOSE OF
 CALCULATING MAXIMUM SIGN ALLOWED.