Plan Review Details - Permit 09080595
Plan Review Stops For Permit 09080595
Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2010-01-21 Cont ID  
Sent By lmartine Date 2010-01-21 Time 12:33 Rev Time 0.00
Received By lmartine Date 2010-01-21 Time 12:33 Sent To  
Notes
2010-01-21 12:34:22SEE APPROVAL ON #09080587

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By hmoser Date 2009-12-02 Time 09:05 Rev Time 0.00
Received By hmoser Date 2009-12-02 Time 09:04 Sent To  
Notes
2009-12-02 09:16:54PLAN REVIEW DENIED
 1) PLEASE PROVIDE DUCT SIZE FOR TRUNK LINE , PLEASE
 PROVIDE EQUIPMENT SCHEDULE ON THE PLANS , PLEASE
 RE-WORK HEAT LOADS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732