Plan Review Details - Permit 09080587
Plan Review Stops For Permit 09080587
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-23 Cont ID  
Sent By lmartine Date 2009-11-23 Time 16:54 Rev Time 0.00
Received By lmartine Date 2009-11-23 Time 16:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-02 Cont ID  
Sent By kconrad Date 2009-09-02 Time 10:10 Rev Time 0.00
Received By kconrad Date 2009-09-02 Time 10:10 Sent To  
Notes
2009-09-02 10:11:47PREINSPECT PERFORMED BY CJ. THE PROJECT VALUATION
 APPEARS TO BE LOW AND SHOULD BE A MINUMUM OF $7,500.
 WILL REQUIRE A NOC.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-10-21 Cont ID  
Sent By btrobaug Date 2009-10-21 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2009-10-21 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-10 Cont ID  
Sent By lmartine Date 2009-12-09 Time 09:26 Rev Time 0.00
Received By lmartine Date 2009-12-09 Time 09:26 Sent To  
Notes
2009-12-10 09:30:09GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-10 Cont ID  
Sent By lmartine Date 2009-11-23 Time 09:26 Rev Time 0.00
Received By lmartine Date 2009-10-21 Time 15:23 Sent To  
Notes
2009-10-21 15:28:43R20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-21 Cont ID  
Sent By rregueir Date 2010-01-21 Time 09:58 Rev Time 0.00
Received By rregueir Date 2010-01-21 Time 09:58 Sent To  
Notes
2010-01-21 09:59:02MISSING CFM AND DUCT SIZES WERE ADDED BY HAND TO PLAN
 PER PHONE CONVERSATION WITH CONTRACTOR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-23 Cont ID  
Sent By rregueir Date 2009-11-23 Time 11:15 Rev Time 0.00
Received By rregueir Date 2009-11-23 Time 11:15 Sent To  
Notes
2009-11-23 11:29:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE EQUIPMENT SCHEDULE PER FBC-B 106.3.5.
  
 2. PROVIDE DUCT SIZES AND CFM QUANTITIES ON PLANS. THE
 AIR DISTRIBUTION SYSTEM SHALL BE SIZED AND DESIGNED IN
 ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH
 AS ACCA MANUAL D OR OTHER STANDARDS, IN ACCORDANCE WITH
 FBC-B 610.AB.1, BASED ON THE FOLLOWING:
  
 A. CALCULATION OF THE SUPPLY AIR FOR EACH ROOM SHALL BE
 BASED ON THE GREATER OF THE HEATING LOAD OR SENSIBLE
 COOLING LOAD FOR THAT ROOM.
  
 B. DUCT SIZE SHALL BE DETERMINED BY THE SUPPLY AIR
 REQUIREMENTS OF EACH ROOM, THE AVAILABLE STATIC
 PRESSURE AND THE TOTAL EQUIVALENT LENGTH OF THE VARIOUS
 DUCT RUNS.
  
 C. FRICTION LOSS DATA SHALL CORRESPOND TO THE TYPE OF
 MATERIAL USED IN DUCT CONSTRUCTION.
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-11-03 Cont ID  
Sent By jroach Date 2009-11-03 Time 18:35 Rev Time 0.00
Received By jroach Date 2009-11-03 Time 18:35 Sent To  
Notes
***NONE***