Plan Review Details - Permit 09080580
Plan Review Stops For Permit 09080580
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-12-01 Cont ID  
Sent By jwitmer Date 2009-12-01 Time 09:42 Rev Time 0.77
Received By jwitmer Date 2009-12-01 Time 09:00 Sent To  
Notes
2009-12-01 09:52:14BUILDING PLAN REVIEW
 PERMIT: 09080580
 ADD: 400 N FLAGLER DR 1ST FL SHELL
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)356-2553
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVISION REVIEW
 ACTION: DENIED
  
 1) PRODUCT APPROVAL SUBMITTED, CHANGE OF PRODUCT
 APPROVAL:
  
 1A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1B) PLEASE CIRCLE SIZE OF GLAZED PANEL, TYPE OF GLAZING
 TO BE INSTALLED, THIS INFORMATION IS FOUND ON THE
 TECHNICAL SHEET 2 OF 8 PLEASE NOTE END ZONE PRESSURES
 ARE A +68/ -129.
  
 1C) PLEASE CIRCLE THE LENGTH OF MULLION, & MULLION TYPE
 FOR THE ASSOCATED PRESSURES, THIS INFORMATION CAN BE
 FOUND ON SHEET 3 OF 8 THE TECHNICAL SHEETS.
  
 1D) PLEASE CICLE THE FRAME DIMENSIONS AND ANCHOR TYPE
 TO BE USED WITH THIS INSTALATION AND ASSOCIATED
 PRESSURES.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-10-08 Cont ID  
Sent By jwitmer Date 2009-10-08 Time 15:03 Rev Time 0.77
Received By jwitmer Date 2009-10-08 Time 15:01 Sent To  
Notes
2009-10-08 15:05:03STRUCTURAL REVISION:
 NUMBER 1/ DATED 9-25-09
 S-1
 S-2
 S-3
 S-4
 S-5
 S-6
 S-7
 S-8

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 13:20 Rev Time 0.50
Received By jwitmer Date 2009-10-05 Time 12:50 Sent To  
Notes
2009-10-05 13:19:40ASSEMBLE PLANS OK TO ISSUE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-02 Cont ID  
Sent By jwitmer Date 2009-09-02 Time 09:30 Rev Time 1.50
Received By jwitmer Date 2009-09-02 Time 08:02 Sent To  
Notes
2009-09-02 09:42:40NOTE: AWNING ARE COVERED UNDER SEPERATE PERMIT, FEES
 AND REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-02 Cont ID  
Sent By dpalmer Date 2009-10-02 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2009-10-02 Time 09:00 Sent To  
Notes
2009-10-02 09:00:44** REDLINED PLANS **
  
 1) NOTE: THE LIGHTING CONTROLS FOR ELECTRICAL ROOM
 SHALL NOT BE BY AUTOMATED CONTROLS ALONE. NEC 110.26D.
  
 2) NOTE: ALL METERS AFTER THE FIRST MEANS OF DISCONNECT
 SHALL HAVE A FLOATING NEUTRAL KIT. 250.6,250.24.
 IF A FLOATING NEUTRAL KIT IS NOT INSTALLED, THE
 EQUIPMENT GROUNDING CONDUCTOR WOULD PARALLEL THE
 NEUTRAL CREATING OBJECTIONABLE CURRENTS.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-09-16 Cont ID  
Sent By dpalmer Date 2009-09-16 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2009-09-16 Time 17:24 Sent To  
Notes
2009-09-16 17:24:26** REDLINED PLANS**
  
  
 1) NOTE: TYPE OF TIME CLOCK ON PLANS NOT PER
 13-415.AB.1.4.
 REDLINED PLANS. CONTROLS FOR EXTERIOR LIGHTS MUST BE
 ASTRONOMICAL WITH A MINIMUM OF 10HR BACK UP.
  
 2) NOTE: NO ELECTRICAL WORK OF ANY KIND IN OTHER AREAS
 AS NOTED ON PLANS EXCEPT FOR SLAB CONDUITS. **ALL SLAB
 CONDUITS ARE AT CONTRACTORS RISK AS SIZING OF CONDUITS,
 LOCATIONS OF PANELS AND EQUIPMENT, TENANT SEPARATION
 ETC ARE NOT REVIEWED FOR CODE COMPLIANCE.
 LOCATIONS OF EQUIPMENT AND OTHER SYSTEMS ARE ALSO NOT
 REVIEWED FOR CODE COMPLIANCE.
 ** THERE ARE POSSIBLE CONFLICTS FOR CODE COMPLIANCE FOR
 SOME OF THESE ITEMS. THESE FULL CONFLICTS CAN NOT BE
 KNOWN UNTIL FUTURE BUILD OUT PLANS ARE SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-05 Cont ID  
Sent By mawillia Date 2009-10-05 Time 12:25 Rev Time 0.00
Received By mawillia Date 2009-10-05 Time 12:06 Sent To  
Notes
2009-10-05 12:22:27*****APPROVED*****
  
 PLAN SHEET A1.0 STAMPED, INITIALED, AND DATED; THIS
 SHEET WAS PREVIOULSY FIRE-STAMPED ON 9/02/09 IN
 ADDITION TO THE FA1.01 SHEET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-09-02 Cont ID  
Sent By mawillia Date 2009-09-02 Time 15:10 Rev Time 0.00
Received By mawillia Date 2009-09-02 Time 15:03 Sent To  
Notes
2009-09-02 15:10:23*****APPROVED*****
  
 PLAN SHEETS A1.0 AND FA1.01 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-11-16 Cont ID  
Sent By dpalmer Date 2009-11-16 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2009-11-16 Time 16:11 Sent To B
Notes
2009-11-16 16:11:21TO JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 13:49 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 13:49 Sent To  
Notes
2009-10-08 13:50:51SENT TO JWITMER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-30 Cont ID  
Sent By shill Date 2009-09-30 Time 12:27 Rev Time 0.00
Received By shill Date 2009-09-30 Time 12:27 Sent To  
Notes
2009-09-30 12:28:09B15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-23 Cont ID  
Sent By lmartine Date 2009-09-23 Time 16:35 Rev Time 0.00
Received By lmartine Date 2009-09-23 Time 16:35 Sent To  
Notes
2009-09-23 16:35:55IN ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-16 Time   Rev Time  
Received By   Date 2009-09-16 Time   Sent To  
Notes
2009-09-16 16:52:48THIS IS IN BIN B-22

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2009-12-01 Cont ID  
Sent By rregueir Date 2009-11-09 Time 20:31 Rev Time 0.00
Received By rregueir Date 2009-11-09 Time 20:31 Sent To  
Notes
2009-11-09 20:31:15WRONG REVIEW STOP. NEW "M" STOP CREATED FOR THIS
 REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-01 Cont ID  
Sent By rregueir Date 2009-11-09 Time 11:21 Rev Time 0.00
Received By rregueir Date 2009-11-09 Time 11:21 Sent To  
Notes
2009-12-01 11:22:18REVISED M1.01 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-03 Cont ID  
Sent By rregueir Date 2009-09-03 Time 16:26 Rev Time 0.00
Received By rregueir Date 2009-09-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By kstevens Date 2009-10-01 Time 09:45 Rev Time 0.00
Received By kstevens Date 2009-10-01 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-08-27 Cont ID  
Sent By kstevens Date 2009-08-27 Time 10:23 Rev Time 0.00
Received By kstevens Date 2009-08-27 Time 10:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By aaponte Date 2009-10-01 Time 11:55 Rev Time 0.00
Received By aaponte Date 2009-10-01 Time 11:55 Sent To  
Notes
2009-10-01 11:55:54PROVISO: LANDSCAPE NOT INLCUDED. A SEPARATE LANDSCAPE
 PERMIT WILL BE REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-10 Cont ID  
Sent By aaponte Date 2009-09-10 Time 10:23 Rev Time 0.00
Received By aaponte Date 2009-09-10 Time 10:23 Sent To  
Notes
2009-09-10 10:25:20PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 PLEASE PROVIDE DRAWINGS INDICATING EXISTING CONDITIONS
 AND DEMOLITION PLAN.


Account Summary | Usage Policy | Privacy Policy